Carlo Gavazzi EM21 logger. MODBUS registers map.


This data is being extracted with help of the "Advanced Serial Data Logger" or "Advanced TCP/IP Data Logger" software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
2V l2-nVoltinteger
4V l3-nVoltinteger
6V l1-l2Voltinteger
8V l2-l3Voltinteger
10V l3-l1Voltinteger
12A l1Ampereinteger
14A l2Ampereinteger
16A l3Ampereinteger
18W l1Wattinteger
20W l2Wattinteger
22W l3Wattinteger
24Va l1VAinteger
26Va l2VAinteger
28Va l3VAinteger
30Var l1varinteger
32Var l2varinteger
34Var l3varinteger
36V l-nVoltinteger
38V l-lVoltinteger
40WWattinteger
42VaVAinteger
44Varvarinteger
46Pf l1 smallint
47Pf l2 smallint
48Pf l3 smallint
49PfPFsmallint
50Phase sequence smallint
51Hz smallint
52Kwh(+) totkWhinteger
54Kvarh(+) totkvarhinteger

Carlo Gavazzi EM21 data logging

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.