EDMI (Atlas MK10) data logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
1
Serial number
 
integer
3
Export wh total ch0
 
single
5
Import wh total ch1
 
single
7
Export varh total ch2
 
single
9
Import varh total ch3
 
single
11
Va
 
single
13
Vb
 
single
15
Vc
 
single
17
Ia
 
single
19
Ib
 
single
21
Ic
 
single
23
Angle a
 
single
25
Angle b
 
single
27
Angle C
 
single
29
Va ia angle
 
single
31
Va ib angle
 
single
33
Va ic angle
 
single
35
Va va angle
 
single
37
Va vb angle
 
single
39
Va vc angle
 
single
41
Phase A watts
 
single
43
Phase B watts
 
single
45
Phase C watts
 
single
47
Phase A vars
 
single
49
Phase B vars
 
single
51
Phase C vars
 
single
53
Phase A va
 
single
55
Phase B va
 
single
57
Phase C va
 
single
59
Frequency
 
single
61
Power factor
 
single