ENTES (EPR04) data logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
20
L1 phase active power
Watt
integer
22
L2 phase active power
Watt
integer
24
L3 phase active power
Watt
integer
26
L1 phase reactive power
Var
integer
28
L2 phase reactive power
Var
integer
30
L3 phase reactive power
Var
integer
32
L1 phase apparent power
VA
dword
34
L2 phase apparent power
VA
dword
36
L3 phase apparent power
VA
dword
38
L1 phase cos
 
integer
40
L2 phase cos
 
integer
42
L3 phase cos
 
integer
44
Total import active power
Watt
integer
46
Total export active power
Watt
integer
48
Total inductive reactive power
Var
integer
50
Total capacitive reactive power
Var
integer
52
Total apparent power
VA
dword
54
Average inductive cos
 
integer
56
Average capacitive cos
 
integer
58
Frequency
Hz
dword
88
Import active energy 1
Wh
int64
92
Export active energy 1
Wh
int64
96
Inductive reactive energy 1
VArh
int64
100
Capacitive reactive energy 1
VArh
int64
104
Import active energy 2
Wh
int64
108
Export active energy 2
Wh
int64
112
Inductive reactive energy 2
VArh
int64
116
Capacitive reactive energy 2
VArh
int64
136
L1 phase min. active power
Watt
integer
138
L2 phase min. active power
Watt
integer
140
L3 phase min. active power
Watt
integer
142
L1 phase min. reactive power
Var
integer
144
L2 phase min. reactive power
Var
integer
146
L3 phase min. reactive power
Var
integer
148
L1 phase min. apparent power
VA
dword
150
L2 phase min. apparent power
VA
dword
152
L3 phase min. apparent power
VA
dword
154
Total min. import active power
Watt
integer
156
Total min. export active power
Watt
integer
158
Total min. import reactive power
Var
integer
160
Total min. export reactive power
Var
integer
162
Total min. apparent power
VA
dword
182
L1 phase max. active power
Watt
integer
184
L2 phase max. active power
Watt
integer
186
L3 phase max. active power
Watt
integer
188
L1 phase max. reactive power
Var
integer
190
L2 phase max. reactive power
Var
integer
192
L3 phase max. reactive power
Var
integer
194
L1 phase max. apparent power
VA
dword
196
L2 phase max. apparent power
VA
dword
There are more MODBUS items for this device. Please download the program to discover all registers.