Mikro (DPM380) logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
4000
Negative real energy
kWh
dword
4002
Positive real energy
kWh
dword
4006
Apparent energy
kVAh
dword
4008
Negative reactive energy
kVArh
dword
4010
Positive reactive energy
kVArh
dword
4012
Total real power
W
integer
4014
Total apparent power
VA
integer
4016
Total reactive power
VAR
integer
4018
Total power factor
1
dword
4019
Frequency
Hz
dword
4020
Instantaneous current L1
A
dword
4022
Instantaneous current L2
A
dword
4024
Instantaneous current L3
A
dword
4026
Instantaneous current ln
A
dword
4028
Voltage phase L12
V
dword
4030
Voltage phase L23
V
dword
4032
Voltage phase L31
V
dword
4034
Voltage phase L1
V
dword
4036
Voltage phase L2
V
dword
4038
Voltage phase L3
V
dword
4040
Real power L1
W
integer
4042
Real power L2
W
integer
4044
Real power L3
W
integer
4046
Apparent power L1
VA
integer
4048
Apparent power L2
VA
integer
4050
Apparent power L3
VA
integer
4052
Reactive power L1
VAR
integer
4054
Reactive power L2
VAR
integer
4056
Reactive power L3
VAR
integer
4064
Real power de mand
W
integer
4066
Maximum real power demand
W
integer
4082
Thd current L1
%
dword
4083
Thd current L2
%
dword
4084
Thd current L3
%
dword
4085
Thd voltage L1
%
dword
4086
Thd voltage L2
%
dword
4087
Thd voltage L3
%
dword