RISH (RM3430i) logging. MODBUS registers map.


This data is being extracted with help of the "Advanced Serial Data Logger" or "Advanced TCP/IP Data Logger" software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
2Volts 2 single
4Volts 3 single
6Current 1 single
8Current 2 single
10Current 3 single
12W1 single
14W2 single
16W3 single
18VA1 single
20VA2 single
22VA3 single
24Var1 single
26Var2 single
28Var3 single
30PF1 single
32PF2 single
34PF3 single
36Phase angle 1 single
38Phase angle 2 single
40Phase angle 3 single
42Volts ave single
44Volts sum single
46Current ave single
48Current sum single
50Watts ave single
52Watts sum single
54Va ave single
56Va sum single
58Var ave single
60Var sum single
62Pf ave single
64Pf sum single
66Phase angle ave single
68Phase angle sum single
70Freq single
72Wh import single
74Wh export single
76Varh import single
78Varh export single
80Vah single
132Volts ave max single
134Volts ave min single
140Current ave max single
142Current ave min single
144Active import energy(wh) single
146Active export energy (wh) single
148Reactive import energy (varh) single
150Reactive export energy (varh) single
152Apparent energy (vah) single
200Vl 1 2 ( calculated ) single
202Vl 2 3 ( calculated ) single
204Vl 3 1 ( calculated ) single
206V1 thd( % ) single
208V2 thd( % ) single
210V3 thd( % ) single
212I1 thd( % ) single
214I2 thd( % ) single
216I3 thd( % ) single
218System voltage thd( % ) single
220System current thd( % ) single
224I neutral single

RISH (RM1300,RM2300) data logging
RISH (RM3430i) data logging
RISH (RM3440) data logging
RISH (RM3440i) data logging
RISH (RM3490) data logging