Schneider Electric PowerLogic ION8600 data logger. MODBUS registers map.


This data is being extracted with help of the "Advanced Serial Data Logger" or "Advanced TCP/IP Data Logger" software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
10Vln a, Volts/Amps/Freq word
11Vln b, Volts/Amps/Freq word
12Vln c, Volts/Amps/Freq word
13Vln avg, Volts/Amps/Freq word
14Vll ab, Volts/Amps/Freq word
15Vll bc, Volts/Amps/Freq word
16Vll ca, Volts/Amps/Freq word
17Vll avg, Volts/Amps/Freq word
18I a, Volts/Amps/Freq word
19I b, Volts/Amps/Freq word
20I c, Volts/Amps/Freq word
21I avg, Volts/Amps/Freq word
22V unbal, Volts/Amps/FreqVword
23I unbal, Volts/Amps/Freq word
24Freq, Volts/Amps/Freq word
25I4, Volts/Amps/Freq word
26kW a, Power/PFkWinteger
28kW b, Power/PFkWinteger
30kW c, Power/PFkWinteger
32kW tot, Power/PFkWinteger
34kVAR a, Power/PFkVARinteger
36kVAR b, Power/PFkVARinteger
38kVAR c, Power/PFkVARinteger
40kVAR tot, Power/PFkVARinteger
42kVA a, Power/PFkVAinteger
44kVA b, Power/PFkVAinteger
46kVA c, Power/PFkVAinteger
48kVA tot, Power/PFkVAinteger
50PF sign a, Power/PF integer
52PF sign b, Power/PF integer
54PF sign c, Power/PF integer
56PF sign tot, Power/PF integer
58Vll avg mx, Min/Max/Demand integer
60I avg mx, Min/Max/Demand integer
62kW tot mx, Min/Max/DemandkWinteger
64kVAR tot mx, Min/Max/DemandkVARinteger
66kVA tot mx, Min/Max/DemandkVAinteger
68Freq mx, Min/Max/Demand integer
70Vll avg mn, Min/Max/Demand integer
72I avg mn, Min/Max/Demand integer
74Freq mn, Min/Max/Demand integer
76kW sd del-rec, Min/Max/DemandkWinteger
78kVA sd del+rec, Min/Max/DemandkVAinteger
80kVAR sd del-rec, Min/Max/DemandkVARinteger
82kW sd mx d-r, Min/Max/DemandkWinteger
84kVA sd mx d+r, Min/Max/DemandkVAinteger
86kVAR sd mx d-r, Min/Max/DemandkVARinteger
88Phase Rev, Min/Max/Demand integer
90kWh del, Energy/THDkWhinteger
92kWh rec, Energy/THDkWhinteger
94kWh del+rec, Energy/THDkWhinteger
96kWh del-rec, Energy/THDkWhinteger
98kVARh del, Energy/THDkVARhinteger
100kVARh rec, Energy/THDkVARhinteger
102kVARh del+rec, Energy/THDkVARhinteger
104kVARh del-rec, Energy/THDkVARhinteger
106kVAh del+rec, Energy/THD integer
108V1 THD mx, Energy/THD integer
110V2 THD mx, Energy/THD integer
112V3 THD mx, Energy/THD integer
114I1 THD mx, Energy/THD integer
116I2 THD mx, Energy/THD integer
118I3 THD mx, Energy/THD integer
149I a, Amp/freq/unbal word
150I b, Amp/freq/unbal word
151I c, Amp/freq/unbal word
152I 4, Amp/freq/unbal word
154I avg, Amp/freq/unbal word
155I avg mn, Amp/freq/unbal word
156I avg mx, Amp/freq/unbal word
157I avg mean 1, Amp/freq/unbal word
158Freq, Amp/freq/unbal word
159Freq mn, Amp/freq/unbal word
160Freq mx, Amp/freq/unbal word
161Freq mean 1, Amp/freq/unbal word
162V unbal, Amp/freq/unbalVword
163I unbal, Amp/freq/unbal word
164Phase Rev, Amp/freq/unbal word
165Vln a, Volts dword
167Vln b, Volts dword
169Vln c, Volts dword
171Vln avg, Volts dword
173Vln avg mx, Volts dword
177Vll ab, Volts dword
179Vll bc, Volts dword
181Vll ca, Volts dword
183Vll avg, Volts dword
185Vll avg mx, Volts dword
187Vll avg mean 1, Volts dword
197kW a, kW/kVAr/kVAkWinteger
199kW b, kW/kVAr/kVAkWinteger
201kW c, kW/kVAr/kVAkWinteger
203kW tot, kW/kVAr/kVAkWinteger
205kW tot mx, kW/kVAr/kVAkWinteger
207kVAR a, kW/kVAr/kVAkVARinteger
209kVAR b, kW/kVAr/kVAkVARinteger
211kVAR c, kW/kVAr/kVAkVARinteger
213kVAR tot, kW/kVAr/kVAkVARinteger
215kVAR tot mx, kW/kVAr/kVAkVARinteger
217kVA a, kW/kVAr/kVAkVAinteger
219kVA b, kW/kVAr/kVAkVAinteger
221kVA c, kW/kVAr/kVAkVAinteger
223kVA tot, kW/kVAr/kVAkVAinteger
225kVA tot mx, kW/kVAr/kVAkVAinteger
229kWh del, kWh/kVArhkWhinteger
231kWh rec, kWh/kVArhkWhinteger
233kVARh del, kWh/kVArhkVARhinteger
235kVARh rec, kWh/kVArhkVARhinteger
237kVAh del+rec, kWh/kVArhkVArhinteger
261PF sign a, PF/THD/Kfactor smallint
262PF sign b, PF/THD/Kfactor smallint
263PF sign c, PF/THD/Kfactor smallint
264PF sign tot, PF/THD/Kfactor smallint
265V1 THD mx, PF/THD/Kfactor smallint
266V2 THD mx, PF/THD/Kfactor smallint
267V3 THD mx, PF/THD/Kfactor smallint
268I1 THD mx, PF/THD/Kfactor smallint
269I2 THD mx, PF/THD/Kfactor smallint
270I3 THD mx, PF/THD/Kfactor smallint
271I1 K Factor, PF/THD/Kfactor smallint
272I2 K Factor, PF/THD/Kfactor smallint
273I3 K Factor, PF/THD/Kfactor smallint
274I1 Crest Factor, PF/THD/Kfactor smallint
275I2 Crest Factor, PF/THD/Kfactor smallint
276I3 Crest Factor, PF/THD/Kfactor smallint
999PO V1-Flck N 2, Flicker Count word
1000PO V1-Flck N12, Flicker Count word
1001PO V2-Flck N 2, Flicker Count word
1002PO V2-Flck N12, Flicker Count word
1003PO V3-Flck N 2, Flicker Count word
1004PO V3-Flck N12, Flicker Count word

Schneider Electric PM1000 PM1200 data logging
Schneider Electric PM9C data logging
Schneider Electric PowerLogic ION6200 data logging
Schneider Electric PowerLogic ION7300 data logging
Schneider Electric PowerLogic ION7500-ION7600 data logging
Schneider Electric PowerLogic ION7550-ION7650 data logging
Schneider Electric PowerLogic ION8300-ION8400-ION8500 data logging
Schneider Electric PowerLogic ION8600 data logging
Schneider Electric PowerLogic ION8800 data logging