Seneca (S203) logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
134
Voltage A
 
single
136
Voltage B
 
single
138
Voltage C
 
single
140
Voltage 3ph
 
single
192
Voltage A
 
word
193
Voltage B
 
word
194
Voltage C
 
word
195
Voltage 3ph
 
word
142
Current A
 
single
144
Current B
 
single
146
Current C
 
single
148
Current 3ph
 
single
196
Current A
 
word
197
Current B
 
word
198
Current C
 
word
199
Current 3ph
 
word
150
Active pow A
 
single
152
Active pow B
 
single
154
Active pow C
 
single
156
Active pow 3ph
 
single
200
Active pow A
 
word
201
Active pow B
 
word
202
Active pow C
 
word
203
Active pow 3ph
 
word
158
Reactive pow A
 
single
160
Reactive pow B
 
single
162
Reactive pow C
 
single
164
Reactive pow 3 ph
 
single
204
Reactive pow A
 
word
205
Reactive pow B
 
word
206
Reactive pow C
 
word
207
Reactive pow 3 ph
 
word
166
Apparent pow A
 
single
168
Apparent pow B
 
single
170
Apparent pow C
 
single
172
Apparent pow 3 ph
 
single
208
Apparent pow A
 
word
209
Apparent pow B
 
word
210
Apparent pow C
 
word
211
Apparent pow 3 ph
 
word
184
Energy A
 
single
186
Energy B
 
single
188
Energy C
 
single
190
Energy 3ph
 
single
174
Cos A
 
single
176
Cos B
 
single
178
Cos C
 
single
180
Cos 3ph
 
single
212
Cos A
 
word
213
Cos B
 
word
There are more MODBUS items for this device. Please download the program to discover all registers.

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.