Socomec Countis E34 E44 data logger - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
9999
SOCO
 
string(8)
10003
Product order ID (Countis:100, protection:200, atys:300, diris:400)
 
word
10004
Product ID
 
word
10005
JBUS table version
 
word
10006
Product software version
 
word
10009
Serial_order
 
word
10010
Serial_Reserve
 
dword
10017
Product version (Major)
 
word
10018
Product version (Minor)
 
word
10029
Product VLO
 
string(8)
10041
Vendor name
 
string(16)
10049
Product name
 
string(16)
10057
Extended name
 
string(16)
8911
Communication board version (Major)
 
word
8912
Communication board version (Minor)
 
word
8913
Communication board version (Revision)
 
word
8914
Communication board version (Build)
 
word
8918
Communication board VLO
 
string(8)
17345
Current transformer primary
A
word
17354
Synchronisation top
 
word
17601
Year
 
word
10513
Phase to phase voltage: U12
V / 100
dword
10515
Phase to phase voltage: U23
V / 100
dword
10517
Phase to phase voltage: U31
V / 100
dword
10519
Simple voltage: V1
V / 100
dword
10521
Simple voltage: V2
V / 100
dword
10523
Simple voltage: V3
V / 100
dword
10525
Frequency
Hz / 100
dword
10527
Current: I1
A / 1000
dword
10529
Current: I2
A / 1000
dword
10531
Current: I3
A / 1000
dword
10533
Neutral current
A / 1000
dword
10535
Active power
W / 0.1
integer
10537
Reactive power
var / 0.1
integer
10539
Apparent power
VA / 0.1
dword
10541
Power factor
- / 1000
integer
10543
Active power phase 1
W / 0.1
integer
10545
Active power phase 2
W / 0.1
integer
10547
Active power phase 3
W / 0.1
integer
10549
Reactive power phase 1
var / 0.1
integer
10551
Reactive power phase 2
var / 0.1
integer
10553
Reactive power phase 3
var / 0.1
integer
10555
Apparent power phase 1
VA / 0.1
dword
10557
Apparent power phase 2
VA / 0.1
dword
10559
Apparent power phase 3
VA / 0.1
dword
10561
Power factor phase 1
- / 1000
integer
10563
Power factor phase 2
- / 1000
integer
10565
Power factor phase 3
- / 1000
integer
10769
Total positive active energy (no resetable)
Wh / 0.001
dword
10771
Total positive reactive energy (no resetable)
varh / 0.001
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.