Frako (EMA1496) data logging. MODBUS registers map.


This data is being extracted with help of the "Advanced Serial Data Logger" or "Advanced TCP/IP Data Logger" software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
2Phase 2 line to neutral voltsVoltssingle
4Phase 3 line to neutral voltsVoltssingle
6Phase 1 currentAmpssingle
8Phase 2 currentAmpssingle
10Phase 3 currentAmpssingle
12Phase 1 powerWattssingle
14Phase 2 powerWattssingle
16Phase 3 powerWattssingle
18Phase 1 volt ampsVoltAmpssingle
20Phase 2 volt ampsVoltAmpssingle
22Phase 3 volt ampsVoltAmpssingle
24Phase 1 volt amps reactiveVArsingle
26Phase 2 volt amps reactiveVArsingle
28Phase 3 volt amps reactiveVArsingle
30Phase 1 power factor (1)Nonesingle
32Phase 2 power factor (1)Nonesingle
34Phase 3 power factor (1)Nonesingle
36Phase 1 phase angleDegreessingle
38Phase 2 phase angleDegreessingle
40Phase 3 phase angleDegreessingle
42Average line to neutral voltsVoltssingle
46Average line currentAmpssingle
48Sum of line currentsAmpssingle
52Total system powerWattssingle
56Total system volt ampsVAsingle
60Total system varVArsingle
62Total system power factor (1)Nonesingle
66Total system phase angleDegreessingle
70Frequency of supply voltagesHzsingle
72Import wh since last reset (2)kWh/MWhsingle
74Export wh since last reset (2)kWH/MWhsingle
76Import varh since last reset (2)kVArh/MVArhsingle
78Export varh since last reset (2)kVArh/MVArhsingle
80Vah since last reset (2)kVAh/MVAhsingle
82Ah since last reset(3)Ah/kAhsingle
84Total system power demand (4)Wattssingle
86Maximum total system power demand (4)Wattssingle
100Total system va demandVAsingle
102Maximum total system va demandVAsingle
104Neutral current demandAmpssingle
106Maximum neutral current demandAmpssingle
200Line 1 to line 2 voltsVoltssingle
202Line 2 to line 3 voltsVoltssingle
204Line 3 to line 1 voltsVoltssingle
206Average line to line voltsVoltssingle
224Neutral currentAmpssingle
234Phase 1 l/n volts thd%single
236Phase 2 l/n volts thd%single
238Phase 3 l/n volts thd%single
240Phase 1 current thd%single
242Phase 2 current thd%single
244Phase 3 current thd%single
248Average line to neutral volts thd%single
250Average line current thd%single
254Total system power factor (5)Cossingle
258Phase 1 current demandAmpssingle
260Phase 2 current demandAmpssingle
262Phase 3 current demandAmpssingle
264Maximum phase 1 current demandAmpssingle
266Maximum phase 2 current demandAmpssingle
268Maximum phase 3 current demandAmpssingle
334Line 1 to line 2 volts thd%single
336Line 2 to line 3 volts thd%single
338Line 3 to line 1 volts thd%single
340Average line to line volts thd%single

Frako (EMA1496) data logging

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.