MODBUS offsetDescriptionUnitsData type
8Meter serial number string
16Meter type word
17Firmware version string
19Map version word
20Meter configuration word
21ASIC version word
39GE part number string
899Watts, 3-Ph total single
901VARs, 3-Ph total single
903VAs, 3-Ph total single
999Volts A-N single
1001Volts B-N single
1003Volts C-N single
1005Volts A-B single
1007Volts B-C single
1009Volts C-A single
1011Amps A single
1013Amps B single
1015Amps C single
1017Watts, 3-Ph total single
1019VARs, 3-Ph total single
1021VAs, 3-Ph total single
1023Power factor, 3-Phtotal single
1025Frequency single
1027Neutral current single
1099W-hours, received integer
1101W-hours, delivered integer
1103W-hours, net integer
1105W-hours, total integer
1107VAR-hours, positive integer
1109VAR-hours, negative integer
1111VAR-hours, net integer
1113VAR-hours, total integer
1115VA-hours, total integer
1999Amps a, average single
2001Amps b, average single
2003Amps c, average single
2005Positive watts, 3-Ph,Average single
2007Positive VARs, 3-Ph,Average single
2009Negative watts, 3-Ph,Average single
2013VAs, 3-Ph, average single
2015Positive PF, 3-Ph,Average single
2017Negative PF, 3-PF,Average single
2999Volts A-N, minimum single
3001Volts B-N, minimum single
3003Volts C-N, minimum single
3005Volts A-B, minimum single
3999Volts A-N, %THD word
4000Volts B-N, %THD word
4001Volts C-N, %THD word
4002Amps a, %THD word
4003Amps b, %THD word
4004Amps c, %THD word
4005Phase A current 0thharmonic magnitude word
4006Phase A current 1stharmonic magnitude word
4007Phase A current 2ndharmonic magnitude word
4008Phase A current 3rdharmonic magnitude word
4009Phase A current 4thharmonic magnitude word
4010Phase A current 5thharmonic magnitude word
4011Phase A current 6thharmonic magnitude word
4012Phase A current 7thharmonic magnitude word
4013Phase A voltage 0thharmonic magnitude word
4014Phase A voltage 1stharmonic magnitude word
4015Phase A voltage 2ndharmonic magnitude word
4016Phase A voltage 3rdharmonic magnitude word
4099Phase A current smallint
4100Phase B current smallint
4101Phase C current smallint
4102Angle, volts A-B smallint
4103Angle, volts B-C smallint
4104Angle, volts C-A smallint
4999Meter status word
5000Limits status7 word
5001Time since reset dword
19999Password5 word
20000Password5 word
21999Password5 word
22000Any value word
220030000 to 9999 word
22999Password5 word
24999Password5 word
30003PT multiplier and hookup word
30004Averaging method word
30005Power and energy format word
30006Operating mode screen enables word
30014User settings flags word
30015Full scale current (for load % bargraph) word
30016Meter designation string
30024COM1 setup word
30025COM2 setup word
30026COM2 address word
30027Limit #1 identifier word
30028Limit #1 out high setpoint smallint
400021 word
400031 word
400051 word
400061 word
400081 word
400091 word
400131 word
400141 word
400161 word
400171 word
400191 word
400201 word
400232 dword