Kohler (Power Monitor) logging - MODBUS registers map
The following data can be automatically logger 24x7 to a database, CSV files or Excel with the help of the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software.
MODBUS offset
Description
Units
Data type
14
Alert code
Alert Code
word
15
Analog input #1 percentage
%
word
16
Analog input #2 percentage
%
word
18
Power supply voltage
VDC
word
24
Total imaginary power
kVAR
word
39
Aux 1 delay time
sec.
word
40
Aux 2 delay time
sec.
word
41
Aux 3 delay time
sec.
word
42
Aux 4 delay time
sec.
word
43
Aux S delay time
sec.
word
44
Aux 6 delay time
sec.
word
45
System voltage
volts, 10514600
word
46
System frequency
Hz, 4862
word
61
Shutdown #1 code
code
word
62
Shutdown #1 month
1-12
word
63
Shutdown #1 day
1-31
word
65
Shutdown #2 code
code
word
66
Shutdown #2 month
1-12
word
67
Shutdown #2 day
1-31
word
69
Shutdown #3 code
code
word
70
Shutdown #3 month
1-12
word
71
Shutdown #3 day
1-31
word
73
Shutdown #4 code
code
word
74
Shutdown #4 month
1-12
word
75
Shutdown #4 day
1-31
word
299
Timed run time
minutes
word