Kohler (Decision Maker 6000) data logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
1 | L2 L3 voltage | Volts AC | word |
2 | L3 L1 voltage | Volts AC | word |
3 | L1 l0 voltage | Volts AC | word |
4 | L2 l0 voltage | Volts AC | word |
5 | L3 l0 voltage | Volts AC | word |
6 | L1 current | Amps AC | word |
7 | L2 current | Amps AC | word |
8 | L3 current | Amps AC | word |
9 | Frequency | Hz | word |
10 | Total kw | kW | word |
11 | Percent of rated kw | % Rated kW | word |
12 | Total power factor | PF | smallint |
13 | L1 kw | kW | word |
14 | L1 power factor | PF | smallint |
15 | L2 kw | kW | word |
16 | L2 power factor | PF | smallint |
17 | L3 kw | kW | word |
18 | L3 power factor | PF | smallint |
19 | Total kvar | kVAR | smallint |
20 | L1 kvar | kVAR | smallint |
21 | L2 kvar | kVAR | smallint |
22 | L3 kvar | kVAR | smallint |
23 | Total kva | kVA | word |
24 | L1 kva | kVA | word |
25 | L2 kva | kVA | word |
26 | L3 kva | kVA | word |
27 | Current lead/lag | Bits 0-1 Total Current - Leading = 10 Lagging = 01 Bits 2-3 L1 Current Leading = 10 Lagging = 01 Bits 4-5 L2 Current - Leading = 10 Lagging = 01 Bits 6-7 L3 Current - Leading = 10 Lagging = 01 | word |
32 | Oil pressure | kPa/psi | word |
33 | Coolant temperature | Degrees C/Degrees F | smallint |
34 | Engine speed | RPM | word |
35 | Local battery voltage | Volts DC | word |
36 | Fuel pressure | kPa/psi DDEC/MDEC/ADEC only | word |
37 | Fuel temperature | Degrees C/Degrees F DDEC/MDEC/ADEC only | smallint |
38 | Fuel rate | Liters/Hour | word |
39 | Used last run | Liters/Gallons DDEC only | word |
40 | Coolant pressure | kPa/psi DDEC only | word |
41 | Coolant level | % | word |
42 | Lube oil temperature | Degrees C/Degrees F DDEC/MDEC/ADEC only | smallint |
43 | Oil level | % | word |
44 | Crankcase pressure | kPa/psi DDEC only | word |
45 | Ambient temperature | Degrees C/Degrees F DDEC only | smallint |
46 | Ecm battery voltage | Volts DC | word |
47 | Ecm status | 0 = DDEC-Equipped, 1 = Non-ECM, 2 = MDEC/ADEC-Equipped | word |
48 | Intake air temperature | Degrees C/Degrees F MDEC/ADEC only | smallint |
49 | Intake air pressure | Degrees C/Degrees F MDEC/ADEC only | word |
50 | Mdec/adec fault codes | Numeric Fault Code MDEC/ADEC only | word |
60 | Analog input 00 (battery voltage) | Volts DC | word |
61 | Analog input01 | User-defined and calibrated through the 6000 controller. See the controller operation manual. | word |
62 | Analog input02 | | word |
63 | Analog input03 | | word |
64 | Analog input04 | | word |
65 | Analog input05 | | word |
66 | Analog input06 | | word |
67 | Analog input07 | | word |
78 | Master switch position | 0 = Error, 1 = Auto, 2 = Off, 3 = Run | word |
79 | Programming mode status | 1 = Off, 2 = Local, 3 = Remote | word |
83 | Total number of starts | Starts | word |
84 | Total run time hrs | HRS | integer |
86 | Total run time loaded hrs | HRS | integer |
88 | Total run time unloaded hrs | HRS | integer |
90 | Total run time kw hrs | kW Hrs | integer |
92 | Rtsm total hrs | HRS | integer |
94 | Rtsm loaded hrs | HRS | integer |
96 | Rtsm unloaded hrs | HRS | integer |
98 | Rtsm kw hrs | kW Hrs | integer |
102 | Operating days since maint | Days | word |
103 | Number of starts since maint | Starts | word |
106 | Last start time | Hr|Min | word |
107 | Last run length | Hrs | word |
108 | Last run loaded | 0 = Unloaded, 1 = Loaded | word |
109 | Timed run time (hr:min) | Hr|Min | word |
110 | Timed run remaining (hr:min) | Hr|Min | word |
111 | Is timed run active | 1 = True, 0 = False | word |
115 | Time delay engine start | Min | Sec | word |
116 | Time delay starting aid | Min | Sec | word |
117 | Time delay crank on | Min | Sec | word |
118 | Time delay crank pause | Min | Sec | word |
119 | Time delay engine cooldown | Min | Sec | word |
120 | Time delay crank cycles | Cycles | word |
121 | Time delay overvoltage | Min | Sec | word |
122 | Time delay undervoltage | Min | Sec | word |
123 | Time delay load shed kw | Min | Sec | word |
124 | Operating mode | Bits 0-1 : Operating Mode 1=Standby, 2=Prime Power Bit 2: Unused Bit 3: MDEC/ADEC DSC Mode 1 = Enabled, 0 = Disabled Bit 4: MDEC/ADEC VSG Mode 1 =EnabIed, 0 = Dis- abled Bits 5-7: Temp Sensor Type | word |
125 | System voltage | Volts AC | word |
126 | System frequency | Hz | word |
127 | System phase | 1 = 3 Phase Delta, 2 = 3 Phase Wye, 3 = Single Phase | word |
128 | Kw rating | kW | word |
129 | Load shed output | % of kW RATING | word |
130 | Overvoltage | % of System Voltage | word |
131 | Undervoltage | % of System Voltage | word |
132 | Overfrequency | % of System Frequency | word |
133 | Underfrequency | % of System Frequency | word |
134 | Overspeed | Hz | word |
135 | Battery voltage | Volts DC | word |
136 | Lo battery voltage | Volts DC | word |
137 | Hi battery voltage | Volts DC | word |
138 | Metric units | 1 = True, 0 = False | word |
139 | Nfpa 110 defaults enabled | 1 = True, 0 = False | word |
140 | Rated current | Amps AC | word |
141 | Cooldown temperature override | 1 = True, 0 = False | word |
There are more MODBUS items for this device. Please, download the program. |
Kohler (Decision Maker 340) data logging
Kohler (Decision Maker 3500) data logging
Kohler (Decision Maker 550) data logging
Kohler (Decision Maker 6000) data logging
Kohler (M340) data logging
Kohler (MPAC 1000) data logging
Kohler (MPAC 1500) data logging
Kohler (Power Monitor) data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.