Kohler (Decision Maker 550) data logger. MODBUS registers map.


This data is being extracted with help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
1L2 L3 voltageVolts ACword
2L3 L1 voltageVolts ACword
3L1 l0 voltageVolts ACword
4L2 l0 voltageVolts ACword
5L3 l0 voltageVolts ACword
6L1 currentAmps ACword
7L2 currentAmps ACword
8L3 currentAmps ACword
9FrequencyHz X 100word
10Total kwkWword
11Percent of rated kw% Rated kWword
12Total power factorPF X 100 smallint
13L1 kwkWword
14L1 power factorPF X 100 smallint
15L2 kwkWword
16L2 power factorPF X 100 smallint
17L3 kwkWword
18L3 power factorPF X 100 smallint
19Total kvarkVAR smallint
20L1 kvarkVAR smallint
21L2 kvarkVAR smallint
22L3 kvarkVAR smallint
23Total kvakVAword
24L1 kvakVAword
25L2 kvakVAword
26L3 kvakVAword
27Current lead/lagBits 0-1 Total Current - Leading = 10 Lagging = 01 Bits 2-3 L1 Current Leading = 10 Lagging = 01 Bits 4-5 L2 Current - Leading = 10 Lagging = 01 Bits 6-7 L3 Current - Leading = 10 Lagging = 01word
32Oil pressurekPa/psiword
33Coolant temperatureDegrees C/Degrees Fsmallint
34Engine speedRPMword
35Local battery voltageVolts DC X 10word
36Fuel pressurekPa/psi DDEC/MDEC/ADEC onlyword
37Fuel temperatureDegrees C/Degrees F DDEC/MDEC/ADEC onlysmallint
38Fuel rateLiters/Hour X 100 or Gallons/Hour X 100 DDEC onlyword
39Used last runLiters/Gallons DDEC onlyword
40Coolant pressurekPa/psi DDEC onlyword
41Coolant level% X 10 DDEC onlyword
42Lube oil temperatureDegrees C/Degrees F DDEC/MDEC/ADEC/Waukesha onlysmallint
43Oil level% X 10 DDEC onlyword
44Crankcase pressurekPa/psi DDEC onlyword
45Ambient temperatureDegrees C/Degrees F DDEC onlysmallint
46Ecm battery voltageVolts DC X 10 DDEC/MDEC/ADEC onlyword
47Ecm status0 = DDEC-Equipped, 1 = Non-ECM, 2 = MDEC/ADEC-Equippedword
48Intake air temperatureDegrees C/Degrees F MDEC/ADEC/Waukesha onlysmallint
49Intake air pressureDegrees C/Degrees F MDEC/ADEC onlyword
50Mdec/adec fault codesNumeric Fault Code MDEC/ADEC onlyword
60Analog input 00 (battery voltage)Volts DCword
61Analog input01User-defined and calibrated through the 550 controller. See the controller operation manual.word
62Analog input02 word
63Analog input03 word
64Analog input04 word
65Analog input05 word
66Analog input06 word
67Analog input07 word
78Master switch position0 = Error, 1 = Auto, 2 = Off, 3 = Runword
79Programming mode status1 = Off, 2 = Local, 3 = Remoteword
83Total number of startsStartsword
84Total run time hrsHRS X 100 integer
86Total run time loaded hrsHRS X 100 integer
88Total run time unloaded hrsHRS X 100 integer
90Total run time kw hrskW Hrs integer
92Rtsm total hrsHRS X 100 integer
94Rtsm loaded hrsHRS X 100 integer
96Rtsm unloaded hrsHRS X 100 integer
98Rtsm kw hrskW Hrs integer
102Operating days since maintDaysword
103Number of starts since maintStartsword
106Last start timeHr|Minword
107Last run lengthHrs X 100word
108Last run loaded0 = Unloaded, 1 = Loadedword
109Timed run time (hr:min)Hr|Minword
110Timed run remaining (hr:min)Hr|Minword
111Is timed run active1 = True, 0 = Falseword
115Time delay engine startMin | Secword
116Time delay starting aidMin | Secword
117Time delay crank onMin | Secword
118Time delay crank pauseMin | Secword
119Time delay engine cooldownMin | Secword
120Time delay crank cyclesCyclesword
121Time delay overvoltageMin | Secword
122Time delay undervoltageMin | Secword
123Time delay load shed kwMin | Secword
124Operating modeBits 0-1 : Operating Mode 1=Standby, 2=Prime Power Bit 2: Unused Bit 3: MDEC/ADEC DSC Mode 1 = Enabled, 0 = Dis- abled Bit 4: MDEC/ADEC VSG Mode 1 =EnabIed, 0 = Dis- abled Bits 5-7: Temp Sensor Typeword
125System voltageVolts ACword
126System frequencyHzword
127System phase1 = 3 Phase Delta, 2 = 3 Phase Wye, 3 = Single Phaseword
128Kw ratingkWword
129Load shed output% of kW RATINGword
130Overvoltage% of System Voltageword
131Undervoltage% of System Voltageword
132Overfrequency% of System Frequencyword
133Underfrequency% of System Frequencyword
134OverspeedHzword
135Battery voltageVolts DC X 10word
136Lo battery voltageVolts DC X 10word
137Hi battery voltageVolts DC X 10word
138Metric units1 = True, 0 = Falseword
139Nfpa 110 defaults enabled1 = True, 0 = Falseword
140Rated currentAmps ACword
141Cooldown temperature override1 = True, 0 = Falseword
There are more MODBUS items for this device. Please, download the program.

Kohler (Decision Maker 340) data logging
Kohler (Decision Maker 3500) data logging
Kohler (Decision Maker 550) data logging
Kohler (Decision Maker 6000) data logging
Kohler (M340) data logging
Kohler (MPAC 1000) data logging
Kohler (MPAC 1500) data logging
Kohler (Power Monitor) data logging

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.