Kohler (Decision Maker 550) data logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
1
L2 L3 voltage
Volts AC
word
2
L3 L1 voltage
Volts AC
word
3
L1 l0 voltage
Volts AC
word
4
L2 l0 voltage
Volts AC
word
5
L3 l0 voltage
Volts AC
word
6
L1 current
Amps AC
word
7
L2 current
Amps AC
word
8
L3 current
Amps AC
word
9
Frequency
Hz X 100
word
10
Total kw
kW
word
11
Percent of rated kw
% Rated kW
word
12
Total power factor
PF X 100
smallint
13
L1 kw
kW
word
14
L1 power factor
PF X 100
smallint
15
L2 kw
kW
word
16
L2 power factor
PF X 100
smallint
17
L3 kw
kW
word
18
L3 power factor
PF X 100
smallint
19
Total kvar
kVAR
smallint
20
L1 kvar
kVAR
smallint
21
L2 kvar
kVAR
smallint
22
L3 kvar
kVAR
smallint
23
Total kva
kVA
word
24
L1 kva
kVA
word
25
L2 kva
kVA
word
26
L3 kva
kVA
word
27
Current lead/lag
Bits 0-1 Total Current - Leading = 10 Lagging = 01 Bits 2-3 L1 Current Leading = 10 Lagging = 01 Bits 4-5 L2 Current - Leading = 10 Lagging = 01 Bits 6-7 L3 Current - Leading = 10 Lagging = 01
word
32
Oil pressure
kPa/psi
word
33
Coolant temperature
Degrees C/Degrees F
smallint
34
Engine speed
RPM
word
35
Local battery voltage
Volts DC X 10
word
36
Fuel pressure
kPa/psi DDEC/MDEC/ADEC only
word
37
Fuel temperature
Degrees C/Degrees F DDEC/MDEC/ADEC only
smallint
38
Fuel rate
Liters/Hour X 100 or Gallons/Hour X 100 DDEC only
word
39
Used last run
Liters/Gallons DDEC only
word
40
Coolant pressure
kPa/psi DDEC only
word
41
Coolant level
% X 10 DDEC only
word
42
Lube oil temperature
Degrees C/Degrees F DDEC/MDEC/ADEC/Waukesha only
smallint
43
Oil level
% X 10 DDEC only
word
44
Crankcase pressure
kPa/psi DDEC only
word
45
Ambient temperature
Degrees C/Degrees F DDEC only
smallint
46
Ecm battery voltage
Volts DC X 10 DDEC/MDEC/ADEC only
word
47
Ecm status
0 = DDEC-Equipped, 1 = Non-ECM, 2 = MDEC/ADEC-Equipped
word
48
Intake air temperature
Degrees C/Degrees F MDEC/ADEC/Waukesha only
smallint
49
Intake air pressure
Degrees C/Degrees F MDEC/ADEC only
word
50
Mdec/adec fault codes
Numeric Fault Code MDEC/ADEC only
word
60
Analog input 00 (battery voltage)
Volts DC
word
61
Analog input01
User-defined and calibrated through the 550 controller. See the controller operation manual.
word
62
Analog input02
 
word
63
Analog input03
 
word
There are more MODBUS items for this device. Please download the program to discover all registers.