Selec - MODBUS Registers Map - Logging
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Selec data logging and log.
Selec (EM2M-1P) - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
2
Import active energy
single
4
Export active energy
single
6
Total reactive energy
single
8
Import reactive energy
single
10
Export reactive energy
single
12
Apparent energy
single
14
Active power
single
16
Reactive power
single
18
Apparent power
single
20
Voltage L-N
single
22
Current
single
24
Power factor
single
26
Frequency
single
28
Max demand active power
single
30
Max demand reactive power
single
32
Max demand apparent power
single
149
Total kWh
single
150
Import kWh
single
151
Export kWh
single
152
Total kVArh
single
153
Import kVArh
single
154
Export kVArh
single
155
kVAh
single
Selec (MFM374) - MODBUS Registers
MODBUS offset
Description
Units
Data type
2
Voltage v2n
single
4
Voltage v3n
single
6
Average voltage ln
single
8
Voltage V12
single
10
Voltage V23
single
12
Voltage V31
single
14
Average voltage ll
single
16
Current I1
single
18
Current I2
single
20
Current I3
single
22
Average current
single
24
kW1
single
26
kW2
single
28
kW3
single
30
Kva1
single
32
Kva2
single
34
Kva3
single
36
Kvar1
single
38
Kvar2
single
40
Kvar3
single
42
Total kw
single
44
Total kva
single
46
Total kvar
single
48
PF1
single
50
PF2
single
52
PF3
single
54
Average pf
single
56
Frequency
single
58
Kwh
single
60
Kvah
single
62
Kvarh
single
1
Nm selection
word
3
Ct primary (ct secondary = 5)
word
5
Pt primary
word
Selec (MFM383A) - MODBUS Registers
MODBUS offset
Description
Units
Data type
2
Voltage v2n
single
6
Average voltage ln
single
8
Voltage V12
single
14
Average voltage ll
single
16
Current 11
single
18
Current 12
single
20
Current I3
single
22
Average current
single
24
kW1
single
26
kW2
single
28
kW3
single
30
Kva1
single
32
Kva2
single
34
Kva3
single
36
Kvar1
single
38
Kvar2
single
40
Kvar3
single
42
Total kw
single
44
Total kva
single
46
Total kvar
single
48
PF1
single
50
PF2
single
52
PF3
single
54
Average pf
single
56
Frequency
single
58
Kwh
single
Selec (MFM384) - MODBUS Registers
MODBUS offset
Description
Units
Data type
2
Voltage v2n
single
4
Voltage v3n
single
6
Average voltage ln
single
8
Voltage V12
single
10
Voltage V23
single
12
Voltage V31
single
14
Average voltage ll
single
16
Current I1
single
18
Current I2
single
20
Current I3
single
22
Average current
single
24
kW1
single
26
kW2
single
28
kW3
single
30
Kva1
single
32
Kva2
single
34
Kva3
single
36
Kvar1
single
38
Kvar2
single
40
Kvar3
single
42
Total kw
single
44
Total kva
single
46
Total kvar
single
48
PF1
single
50
PF2
single
52
PF3
single
54
Average pf
single
56
Frequency
single
58
Kwh
single
60
Kvah
single
62
Kvarh
single
64
Kw max active power
single
66
Kw min active power
single
68
Kvar max reactive power
single
70
Kvar min reactive power
single
72
Kva max apparent power
single
1
Nm selection
word
3
Ct primary (ct secondary = 5)
word
5
Pt primary
word