Schneider Electric (EMB,EME) logger. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
256Energy consumption, kwh, low word integer single
258Energy consumption, kwh, high word integer single
260Real power, kw single
262Reactive power, kvar single
264Apparant power, kva single
266Total power factor single
270Avg voltage, L n, ave of 1 single
272Avg current, average of 1 single
274Real power, phase A (same as real power, kw (3)) single
276Real Power, phase B single
278Real Power, phase C single
280Power factor, phase A (same as total pf (6)) single
282Power Factor, phase B single
284Power Factor, phase C single
286Voltage, phase A-B single
288Voltage, phase B-C single
290Voltage, phase A-C single
292Voltage, phase A N (same as avg. L N (8)) single
294Voltage, phase B-N single
296Voltage, phase C-N single
298Current, phase A (same as avg. current (9)) single
300Current, phase B single
302Current, phase C single