bg

Schneider Electric CM2000, Conext Gateway MODBUS registers: read online

Connect Schneider Electric to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Schneider Electric data logging and capture.

Do you not know the meter address? Scan the device address online

Schneider Electric (CM2000) - MODBUS Registers Map

Connection and addressing notes

Password registers
2028 Command Password, 2029 Display Setup Password, 2030 Full Access Front Panel Reset Password, 2031 Reset Access Password
Password range
0-9998
Reset access password
-32768 uses the Configuration password

Registers in the map: 334 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
1000Update intervalsword×0.001
1001FrequencyHzwordformula
1002Temperature inside CM enclosuredeg Cword×0.01
1003Current, phase AAwordformula
1004Current, phase BAwordformula
1005Current, phase CAwordformula
1006Current, neutralAwordformula
1007Current, groundAwordformula
1008Current, 3-phase averageAwordformula
1009Current, apparent rmsAwordformula
1010Current unbalance, phase A%word×0.1
1011Current unbalance, phase B%word×0.1
1012Current unbalance, phase C%word×0.1
1013Current unbalance, worst%word×0.1
1014Voltage, phase A to BVwordformula
1015Voltage, phase B to CVwordformula
1016Voltage, phase C to AVwordformula
1017Voltage L-L, 3-phase averageVwordformula
1018Voltage, phase A to neutralVwordformula
1019Voltage, phase B to neutralVwordformula
1020Voltage, phase C to neutralVwordformula
1021Voltage L-N, 3-phase averageVwordformula
1022Voltage unbalance, phase A-B%word×0.1
1023Voltage unbalance, phase B-C%word×0.1
1024Voltage unbalance, phase C-A%word×0.1
1025Voltage unbalance, L-L worst%word×0.1
1026Voltage unbalance, phase A%word×0.1
1027Voltage unbalance, phase B%word×0.1
1028Voltage unbalance, phase C%word×0.1
1029Voltage unbalance, L-N worst%word×0.1
1031True power factor, phase A word×0.001
1032True power factor, phase B word×0.001
1033True power factor, phase C word×0.001
1034True power factor, 3-phase total word×0.001
1035Displacement power factor, phase A word×0.001
1036Displacement power factor, phase B word×0.001
1037Displacement power factor, phase C word×0.001
1038Displacement power factor, 3-phase total word×0.001
1039Real power, phase AkWwordformula
1040Real power, phase BkWwordformula
1041Real power, phase CkWwordformula
1042Real power, 3-phase totalkWwordformula
1043Reactive power, phase Akvarwordformula
1044Reactive power, phase Bkvarwordformula
1045Reactive power, phase Ckvarwordformula
1046Reactive power, 3-phase totalkvarwordformula
1047Apparent power, phase AkVAwordformula
1048Apparent power, phase BkVAwordformula
1049Apparent power, phase CkVAwordformula
1050Apparent power, 3-phase totalkVAwordformula

This is not the complete map: 50 of 334 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (Conext Gateway) - Measurement Data

Registers in the map: 211 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
40070AC CurrentAword×10A_SF
40071Phase A CurrentAword×10A_SF
40072Phase B CurrentAword×10A_SF
40073Phase C CurrentAword×10A_SF
40074Scale factor [A_SF] smallint 
40075Phase Voltage ABVword×10V_SF
40076Phase Voltage BCVword×10V_SF
40077Phase Voltage CAVword×10V_SF
40078Phase Voltage ANVword×10V_SF
40079Phase Voltage BNVword×10V_SF
40080Phase Voltage CNVword×10V_SF
40081Scale factor [V_SF] smallint 
40082AC PowerWsmallint×10W_SF
40083Scale factor [W_SF] smallint 
40084Line FrequencyHzword×10HZ_SF
40085Scale factor [HZ_SF] smallint 
40086AC Apparent PowerVAsmallint×10VA_SF
40087Scale factor [VA_SF] smallint 
40088AC Reactive Powervarsmallint×10VAR_SF
40089Scale factor [VAR_SF] smallint 
40090AC Power Factor%smallint×10PF_SF
40091Scale factor [PF_SF] smallint 
40092AC EnergyWhdword×10WH_SF
40094Scale factor [WH_SF] smallint 
40095DC CurrentAword×10DCA_SF
40096Scale factor [DCA_SF] smallint 
40097DC VoltageVword×10DCV_SF
40098Scale factor [DCV_SF] smallint 
40099DC PowerWsmallint×10DCW_SF
40100Scale factor [DCW_SF] smallint 
40101Cabinet Temperaturedeg Csmallint×10TMP_SF
40102Heat Sink Temperaturedeg Csmallint×10TMP_SF
40103Transformer Temperaturedeg Csmallint×10TMP_SF
40104Other Temperaturedeg Csmallint×10TMP_SF
40105Scale factor [TMP_SF] smallint 
40106Enumerated value. Operating state word 
40107Vendor specific operating state code word 
40108Bitmask value. Event fields dword 
40110Reserved for future use dword 
40112Vendor defined events dword 
40114Vendor defined events dword 
40116Vendor defined events dword 
40118Vendor defined events dword 
40122Type of DER device. Default value is 4 to indicate PV device. word 
40123Continuous power output capability of the inverter.Wword×10WRTG_SF
40124Scale factor smallint 
40125Continuous capability of the inverter.VAword×10VARTG_SF
40126Scale factor smallint 
40127Continuous VAR capability of the inverter in Q1.varsmallint×10VARRTG_SF
40128Continuous VAR capability of the inverter in Q2.varsmallint×10VARRTG_SF

This is not the complete map: 50 of 211 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (EM1000,EM1100,EM1200) - MODBUS Registers Map

Connection and addressing notes

Read function code
03 holding registers
Parameter set
TURBO parameters
Read mode
block or individual parameters
Scaling
none required
Data format
float and unsigned long

Registers in the map: 70 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single.

MODBUS offsetDescriptionUnitsData typeScale
3056Current average single 
3008Current, phase 1 single 
3024Current, phase 2 single 
3040Current, phase 3 single 
3058Voltage (ll) average single 
3010Voltage(ll), phase 1 2 single 
3026Voltage(ll), phase 2 3 single 
3042Voltage(ll), phase 3 1 single 
3060Voltage(ln) average single 
3012Voltage(ln), phase 1 single 
3028Voltage(ln), phase 2 single 
3044Voltage(ln), phase 3 single 
3062Frequency single 
3050Active power, total single 
3002Active power, phase 1 single 
3018Active power, phase 2 single 
3034Active power, phase 3 single 
3052Reactive power, total single 
3004Reactive power, phase 1 single 
3020Reactive power, phase 2 single 
3036Reactive power, phase 3 single 
3048Apparent power, total single 
3000Apparent power, phase 1 single 
3016Apparent power, phase 2 single 
3032Apparent power, phase 3 single 
3054Power factor total single 
3006Power factor, phase 1 single 
3022Power factor, phase 2 single 
3038Power factor, phase 3 single 
3200Forward apparent energy single 
3202Forward active energy single 
3204Forward reactive energy single 
3264Forward run seconds dword 
3266On seconds dword 
3268Number of input voltage interruptions dword 
2506Current average single 
2500Current, phase 1 single 
2502Current, phase 2 single 
2504Current, phase 3 single 
2514Voltage (ll) average single 
2508Voltage(ll), phase 1 2 single 
2510Voltage(ll), phase 2 3 single 
2512Voltage(ll), phase 3 1 single 
2522Voltage(ln) average single 
2516Voltage(ln), phase 1 single 
2518Voltage(ln), phase 2 single 
2520Voltage(ln), phase 3 single 
2530Frequency single 
2546Active power, total single 
2540Active power, phase 1 single 

This is not the complete map: 50 of 70 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (EM3502,EM3550) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Interface
RS-485
Register addressing
Modbus point map registers 001+
Energy format
ULong with MSR (most significant register) and LSR
Data format
float32 available
Third output
0 = RS-485, 2 = VAR pulse
Address and baud rate setup
front panel Setup menu

Registers in the map: 101 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
0Real energy consumption (msr)kWhdword 
2Total instantaneous real power (3 phase total)kWword 
3Total instantaneous reactive power (3 phase total)kvarword 
4Total instantaneous apparent power (3 phase total)kVAword 
5Total power factor (total kw / total kva)Ratioword×0.0001
6Voltage, L l, average of 3 phasesVword 
7Voltage, L n, average of 3 phasesVword 
8Current, average of 3 phasesAword 
9Real power, phase AkWword 
10Real power, phase BkWword 
11Real power, phase CkWword 
12Power factor, phase ARatioword×0.0001
13Power factor, phase BRatioword×0.0001
14Power factor, phase CRatioword×0.0001
15Voltage, phase A BVword 
16Voltage, phase B CVword 
17Voltage, phase A CVword 
18Voltage, phase A NVword 
19Voltage, phase B NVword 
20Voltage, phase C NVword 
21Current, instantaneous, phase AAword 
22Current, instantaneous, phase BAword 
23Current, instantaneous, phase CAword 
25Frequency (derived from phase a)Hzword×0.01
26Apparent energy consumption (msr)kVAhdword 
28Reactive energy consumption (msr)kvarhdword 
30Apparent power, phase AkVAword 
31Apparent power, phase BkVAword 
32Apparent power, phase CkVAword 
33Reactive power, phase Akvarword 
34Reactive power, phase Bkvarword 
35Reactive power, phase Ckvarword 
36Total real power present demandkWword 
37Total reactive power present demandkvarword 
38Total apparent power present demandkVAword 
39Total real power max. demandkWword 
40Total reactive power max. demandkvarword 
41Total apparent power max. demandkVAword 
42Pulse counter 1 (real energy) dword 
44Pulse counter 2 (reactive energy) dword 
46Real energy consumption phase AkWhdword 
48Real energy consumption phase BkWhdword 
50Real energy consumption phase CkWhdword 
129Single phase: A + N word 
130Ct ratio primaryAword 
131Ct ratio secondary interface word 
132Pt ratio word×100
133System voltage word 
134Theoretical maximum system powerkWword 
136Display units word 

This is not the complete map: 50 of 101 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (EM4200) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus RTU
Protocol support
BACnet MS/TP
Device address register
4207, Modbus RTU address / BACnet MAC address
Baud rate register
4209
Auto-bauding
determines baud rate and parity first
Baud rates above 38400
not recommended for Modbus
Password register
7005, always returns 0, used only for download
Report Slave ID
supported

Registers in the map: 328 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, smallint, string, word.

MODBUS offsetDescriptionUnitsData typeScale
5031Model string 
5319Product Revision string 
5323Hardware Revision string 
6999Hardware Version word 
7000Firmware version (reset system) word 
7001Firmware version (operating system) word 
7002Device ID word 
0Real energy consumptionkWhdword 
2Total instantaneous real power (3 phase total)kWword 
3Total instantaneous reactive power (3 phase total)kvarword 
4Total instantaneous apparent power (3 phase total)kVAword 
5Total power factor (total kw / total kva)Ratioword 
6Voltage, line to line, average of phasesVword 
7Voltage, line to neutral, average of phasesVword 
8Current, average of phasesAword 
9Real power, L1kWword 
10Real power, L2kWword 
11Real power, L3kWword 
12Power factor, L1Ratioword 
13Power factor, L2Ratioword 
14Power factor, L3Ratioword 
15Voltage, L1 L2Vword 
16Voltage, L2 L3Vword 
17Voltage, L3 L1Vword 
18Voltage, L1 NVword 
19Voltage, L2 NVword 
20Voltage, L3 NVword 
21Current, instantaneous, L1Aword 
22Current, instantaneous, L2Aword 
23Current, instantaneous, L3Aword 
24Present demand sub intervalkWword 
25Minimum demandkWword 
26Maximum demandkWword 
27Present demandkWword 
28Peak demandkWword 
30Ct size (100, 300, etc.)Aword 
31Count of kwh resets word 
32Count of peak demand resets word 
33Count of sub intervals word 
34Count of number readings in present sub interval word 
35System type: see manual word 
36Sub interval length word 
37Number of sub intervals per demand interval word 
38CommandBitmaskword 
256Real energy consumptionkWhsingle 
258Real energy consumption (redundant)kWhsingle 
260Total instantaneous real powerkWsingle 
262Total instantaneous reactive powerkvarsingle 
264Total instantaneous apparent powerkVAsingle 
266Total power factor (total kw / total kva)Ratiosingle 

This is not the complete map: 50 of 328 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric PM1000 PM1200 - MODBUS Registers Map

Registers in the map: 137 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single.

MODBUS offsetDescriptionUnitsData typeScale
3913Current averageAsingle 
3929Current, phase 1 (A1) single 
3943Current, phase 2 (A2) single 
3957Current, phase 3 (A3) single 
3909Line to line average voltage (VLL) single 
3911Line to neutral voltage (VLN) single 
3925Voltage phase 1 to phase 2 (V12) single 
3939Voltage phase 2 to phase 3 (V23) single 
3953Voltage phase 3 to phase 1 (V31) single 
3927Voltage phase 1 to neutral (V1) single 
3941Voltage phase 2 to neutral (V2) single 
3955Voltage phase 3 to neutral (V3) single 
3903Active power, totalWsingle 
3919Active power, phase 1 (W1) single 
3933Active power, phase 2 (W2) single 
3947Active power, phase 3 (W3) single 
3905Reactive power, totalvarsingle 
3921Reactive power, phase 1 (VAR1) single 
3935Reactive power, phase 2 (VAR2) single 
3949Reactive power, phase3 (VAR3) single 
3901Apparent power, totalVAsingle 
3917Apparent power, phase 1 (VA1) single 
3931Apparent power, phase 2 (VA2) single 
3945Apparent power, phase 3 (VA3) single 
3907Power factor averagePFsingle 
3923Power factor, phase 1 (PF1) single 
3937Power factor, phase 2 (PF2) single 
3951Power factor, phase 3 (PF3) single 
3915Frequency, hz (F) single 
3861Voltage THD, phase 1 (%V1) single 
3863Voltage THD, phase 2 (%V2) single 
3865Voltage THD, phase 3 (%V3) single 
3867Current THD, phase 1 (%A1) single 
3869Current THD, phase 2 (%A2) single 
3871Current THD, phase 3 (%A3) single 
3959Forward apparent energy (FwdVAh) single 
3961Forward active energy (FwdWh) single 
3963Forward reactive inductive energy (FwdVARh) single 
3965Forward reactive capacitive energy (FwdVARh) single 
3967Reverse apparent energy (RevVAh) single 
3969Reverse active energy (RevWh) single 
3971Reverse reactive inductive energy (RevVARh) single 
3973Reverse reactive capacitive energy (RevVARh) single 
3993On hours (On hrs) integer 
3995Forward run seconds (FwdRun secs) integer 
3997Reverse run seconds (RevRun secs) integer 
3999Number of power interruptions (Intr) integer 
3975Present demand (Present demand) single 
3977Rising demand (Rising demand) single 
3979Maximum demand (Max MD) single 

This is not the complete map: 50 of 137 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (PM2000) - MODBUS Measurements

Registers in the map: 117 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: int64, single, smallint.

MODBUS offsetDescriptionUnitsData typeScale
2675Active energy delivered (Into load)kWhsingle 
2677Active energy received (Out of load)kWhsingle 
2679Active energy delivered + receivedkWhsingle 
2681Active energy delivered- receivedkWhsingle 
2683Reactive energy deliveredkvarhsingle 
2685Reactive energy receivedkvarhsingle 
2687Reactive energy delivered + receivedkvarhsingle 
2689Reactive energy delivered - receivedkvarhsingle 
2691Apparent energy deliveredkVAhsingle 
2693Apparent energy receivedkVAhsingle 
2695Apparent energy delivered + receivedkVAhsingle 
2697Apparent energy delivered - receivedkVAhsingle 
2699Active energy delivered (Into load)kWhsingle 
2701Active energy received (Out of load)kWhsingle 
2703Active energy delivered + receivedkWhsingle 
2705Active energy delivered- receivedkWhsingle 
2707Reactive energy deliveredkvarhsingle 
2709Reactive energy receivedkvarhsingle 
2711Reactive energy delivered + receivedkvarhsingle 
2713Reactive energy delivered - receivedkvarhsingle 
2715Apparent energy deliveredkVAhsingle 
2717Apparent energy receivedkVAhsingle 
2719Apparent energy delivered + receivedkVAhsingle 
2721Apparent energy delivered - receivedkVAhsingle 
2731Reactive energy in Q1kvarhsingle 
2733Reactive energy in Q2kvarhsingle 
2737Reactive energy in Q3kvarhsingle 
2739Reactive energy in Q4kvarhsingle 
2811Active energy delivered phase AkWhsingle 
2813Active energy delivered phase BkWhsingle 
2815Active energy delivered phase CkWhsingle 
2817Reactive energy delivered phase Akvarhsingle 
2819Reactive energy delivered phase Bkvarhsingle 
2821Reactive energy delivered phase Ckvarhsingle 
2823Apparent energy delivered phase AkVAhsingle 
2825Apparent energy delivered phase BkVAhsingle 
2827Apparent energy delivered phase CkVAhsingle 
2999Current AAsingle 
3001Current BAsingle 
3003Current CAsingle 
3005Current NAsingle 
3007Current GAsingle 
3009Current avgAsingle 
3011Current unbalance A%single 
3013Current unbalance B%single 
3015Current unbalance C%single 
3017Current unbalance worst%single 
3019Voltage A-BVsingle 
3021Voltage B-CVsingle 
3023Voltage C-AVsingle 

This is not the complete map: 50 of 117 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (PM5000, PM5200) - MODBUS Mapping

Connection and addressing notes

Interface
RS-485 (Comm Port M/S)
Protocol register
6500
Address register
6501
Baud rate register
6502
Parity register
6503

Registers in the map: 310 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, single, utf8(10), utf8(40), word.

MODBUS offsetDescriptionUnitsData typeScale
49Meter model utf8(40) 
29Meter name utf8(40) 
69Manufacturer utf8(40) 
89Product ID number word 
129Serial number dword 
135Hardware revision utf8(10) 
1827Number of metering system restarts word 
1828Number of control power failures word 
1833Duration of last control power failuresdword 
1835Cause of last meter reset word 
1836Yearyearword 
1837Monthmonthword 
1838Daydaysword 
1839Hourhword 
1840Minuteminword 
1841Secondsword 
1842Millisecondmsword 
1844Year word 
1845Month and day word 
1846Hour and minute word 
1847Milliseconds word 
1999Conditional energy control status word 
2001Active load timersdword 
2003Meter operation timersdword 
2005Cycle count dword 
2013Number of phases word 
2014Number of wires word 
2015Power system configuration word 
2016Nominal frequencyHzword 
2017Nominal voltageVsingle 
2019Nominal currentAsingle 
2021Nominal power factor dword 
2023Normal phase rotation word 
2024Number VTs word 
2025VT primaryVsingle 
2027VT secondaryVword 
2028Number CTs word 
2029CT primaryAword 
2030CT secondaryAword 
2033CT location for 1 or 2 CT metering word 
2034VT location for 1 or 2 VT metering word 
2035VT connection type word 
2047Peak current demand over last yearAsingle 
2049Active load timer setpointAsingle 
2125Alarm / energy LED mode word 
2129Energy channel word 
2131Pulse weightkWh, kVAh, kVAhdword 
2133Energy channel word 
2135Pulse weightkWh, kVAh, kVAhdword 
2137Energy channel word 

This is not the complete map: 50 of 310 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (PM5100, PM5300) - MODBUS Measurements

Connection and addressing notes

Interface
RS-485 (Comm Port M/S)
Protocol register
6500
Address register
6501
Baud rate register
6502
Parity register
6503

Registers in the map: 697 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, single, utf8(40), word.

MODBUS offsetDescriptionUnitsData typeScale
49Meter model utf8(40) 
29Meter name utf8(40) 
69Manufacturer utf8(40) 
89Product ID number word 
129Serial number dword 
1827Number of metering system restarts word 
1828Number of control power failures word 
1833Duration of last control power failuresdword 
1835Cause of last meter reset word 
1836Yearyearword 
1837Monthmonthword 
1838Daydaysword 
1839Hourhword 
1840Minuteminword 
1841Secondsword 
1842Millisecondmsword 
1843Day of week word 
1844Year word 
1845Month and day word 
1846Hour and minute word 
1847Milliseconds word 
1920Revenue security status word 
1999Conditional energy control status word 
2001Active load timersdword 
2003Meter operation timersdword 
2005Cycle count dword 
2007Heartbeat LED control word 
2013Number of phases word 
2014Number of wires word 
2015Power system configuration word 
2016Nominal frequencyHzword 
2017Nominal voltageVsingle 
2019Nominal currentAsingle 
2021Nominal power factor dword 
2023Normal phase rotation word 
2024Number VTs word 
2025VT primaryVsingle 
2027VT secondaryVword 
2028Number CTs word 
2029CT primaryAword 
2030CT secondaryAword 
2033CT location for 1 or 2 CT metering word 
2034VT location for 1 or 2 VT metering word 
2035VT connection type word 
2047Peak current demand over last yearAsingle 
2049Active load timer setpointAsingle 
2125Alarm / energy LED mode word 
2129Energy channel word 
2130Digital output association word 
2131Pulse weightkWh, kVAh, kVAhdword 

This is not the complete map: 50 of 697 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric PM5500 - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Interface
RS-485 (Comm Port M/S)
Default baud rate
19200
Baud rate register
6502, 0 = 9600, 1 = 19200, 2 = 38400
Parity
even
Parity register
6503, 0 = even, 1 = odd, 2 = none
Default device address
1
Address register
6501, range 1-247
Protocol register
6500, default 0 = Modbus, 1 = Jbus, 2 = Modbus ASCII 8-bit, 3 = Modbus ASCII 7-bit
ASCII timeout register
6504, default 1000 ms

Registers in the map: 1867 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (input registers). byte order big-endian. data types: dword, int64, single, utf8(10), utf8(40), word.

MODBUS offsetDescriptionUnitsData typeScale
49Meter model utf8(40) 
1636Present firmware version (DLF format) X.Y.T word 
1641Previous firmware version (DLF format) X.Y.T word 
1668Present firmware version (DLF format) X.Y.T word 
1700Present firmware version (DLF format) X.Y.T word 
2284Present firmware version (DLF format) X.Y.T word 
2289Previous firmware version (DLF format) X.Y.T word 
29Meter name utf8(40) 
69Manufacturer utf8(40) 
89Product ID number word 
129Serial number dword 
135Hardware revision utf8(10) 
1637X major word 
1638Y minor word 
1639Z quality word 
1642X major word 
1643Y minor word 
1644Z quality word 
1827Number of metering system restarts word 
1828Number of control power failures word 
1833Duration of last control power failuresdword 
1835Cause of last meter reset word 
1836Yearyearword 
1837Monthmonthword 
1838Daydaysword 
1839Hourhword 
1840Minuteminword 
1841Secondsword 
1842Millisecondmsword 
1844Year word 
1845Month and day word 
1846Hour and minute word 
1847Milliseconds word 
1919Revenue security switch status word 
1920Revenue security status word 
2001Active load timersdword 
2003Meter operation timersdword 
2013Number of phases word 
2014Number of wires word 
2015Power system configuration word 
2016Nominal frequencyHzword 
2017Nominal voltageVsingle 
2019Nominal currentAsingle 
2023Normal phase rotation word 
2024Number VTs word 
2025VT primaryVsingle 
2027VT secondaryVword 
2028Number CTs word 
2029CT primaryAword 
2030CT secondaryAword 

This is not the complete map: 50 of 1867 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (PM600) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Register type
all registers are holding registers
Register addressing
one-based
Offset compensation
meter automatically compensates for the Modbus offset of one
Address prefixes
30,000 or 40,000 can be used, e.g. Current phase A = 31,003 or 41,003

Registers in the map: 192 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: smallint.

MODBUS offsetDescriptionUnitsData typeScale
2019Scale Factor A smallint 
2022Scale Factor D smallint 
2023Scale Factor E smallint 
999Update interval smallint 
1000FrequencyHzsmallint 
1002Current, phase AAsmallint×10SCALE_A
1003Current, phase BAsmallint×10SCALE_A
1004Current, phase CAsmallint×10SCALE_A
1005Current, calculated neutralAsmallint×10SCALE_A
1009Current unbalance, phase A%smallint×0.1
1010Current unbalance, phase B%smallint×0.1
1011Current unbalance, phase C%smallint×0.1
1012Current unbalance, worst%smallint×0.1
1013Voltage, phase A to BVsmallint×10SCALE_D
1014Voltage, phase B to CVsmallint×10SCALE_D
1015Voltage, phase C to AVsmallint×10SCALE_D
1017Voltage, phase A to neutralVsmallint×10SCALE_D
1018Voltage, phase B to neutralVsmallint×10SCALE_D
1019Voltage, phase C to neutralVsmallint×10SCALE_D
1021Voltage unbalance, phase A B%smallint×0.1
1022Voltage unbalance, phase B C%smallint×0.1
1023Voltage unbalance, phase C A%smallint×0.1
1024Voltage unbalance, L L worst%smallint×0.1
1025Voltage unbalance, phase A%smallint×0.1
1026Voltage unbalance, phase B%smallint×0.1
1027Voltage unbalance, phase C%smallint×0.1
1028Voltage unbalance, L N worst%smallint×0.1
1030True power factor, phase A smallint×0.001
1031True power factor, phase B smallint×0.001
1032True power factor, phase C smallint×0.001
1033True power factor, 3 phase total smallint×0.001
1038Real power, phase AkWsmallint×10SCALE_E
1039Real power, phase BkWsmallint×10SCALE_E
1040Real power, phase CkWsmallint×10SCALE_E
1041Real power, 3 phase totalkWsmallint×10SCALE_E
1042Reactive power, phase Akvarsmallint×10SCALE_E
1043Reactive power, phase Bkvarsmallint×10SCALE_E
1044Reactive power, phase Ckvarsmallint×10SCALE_E
1045Reactive power, 3 phase totalkvarsmallint×10SCALE_E
1046Apparent power, phase AkVAsmallint×10SCALE_E
1047Apparent power, phase BkVAsmallint×10SCALE_E
1048Apparent power, phase CkVAsmallint×10SCALE_E
1049Apparent power, 3 phase totalkVAsmallint×10SCALE_E
1050Thd/thd A current smallint×0.1
1051Thd/thd B current smallint×0.1
1052Thd/thd C current smallint×0.1
1054Thd/thd A voltage smallint×0.1
1055Thd/thd B voltage smallint×0.1
1056Thd/thd C voltage smallint×0.1
1077A current fundamental rms magnitudeAsmallint×10SCALE_A

This is not the complete map: 50 of 192 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (PM700) - MODBUS Registers

Registers in the map: 97 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
1000Real energy, totalkWhsingle 
1002Apparent energy, totalkVAhsingle 
1004Reactive energy, totalkvarhsingle 
1006Real power, totalkWsingle 
1008Apparent power, totalkVAsingle 
1010Reactive power, totalkvarsingle 
1012Power factor, total single 
1014Voltage, L-L, 3P averageVsingle 
1016Voltage, L-N, 3P averageVsingle 
1018Current, 3P averageAsingle 
1020FrequencyHzsingle 
1034Current, AAsingle 
1036Current, BAsingle 
1038Current, CAsingle 
1040Current, NAsingle 
1054Voltage, A-BVsingle 
1056Voltage, B-CVsingle 
1058Voltage, C-AVsingle 
1060Voltage, A-NVsingle 
1062Voltage, B-NVsingle 
1064Voltage, C-NVsingle 
1066Real power, AkWsingle 
1068Real power, BkWsingle 
1070Real power, CkWsingle 
1072Apparent power, AkVAsingle 
1074Apparent power, BkVAsingle 
1076Apparent power, CkVAsingle 
1078Reactive power, Akvarsingle 
1080Reactive power, Bkvarsingle 
1082Reactive power, Ckvarsingle 
1084Current, A, THD%single 
1086Current, B, THD%single 
1088Current, C, THD%single 
1092Voltage, A-N, THD%single 
1094Voltage, B-N, THD%single 
1096Voltage, C-N, THD%single 
1098Voltage, A-B, THD%single 
1100Voltage, B-C, THD%single 
1102Voltage, C-A, THD%single 
1022Real power, total demand presentkWsingle 
1024Apparent power, total demand presentkVAsingle 
1026Reactive power, total demand presentkvarsingle 
1028Real power, total demand peakkWsingle 
1030Apparent power, total demand peakkVAsingle 
1032Reactive power, total demand peakkvarsingle 
1042Current, A, demand presentAsingle 
1044Current, B, demand presentAsingle 
1046Current, C, demand presentAsingle 
1048Current, A, demand peakAsingle 
1050Current, B, demand peakAsingle 

This is not the complete map: 50 of 97 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (PM8000) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus RTU (COM1 protocol option 1) and Modbus TCP (Ethernet)
Interface
RS-485 (COM1)
COM1 baud rate register
54392, 0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200, 4 = 38400, 5 = 57600, 6 = 115200
COM1 protocol register
54592, 0 = ION, 1 = Modbus RTU, 2 = Modbus Master, 3 = DNP V3.00, 4 = EtherGate, 8 = Factory
COM1 serial port register
0 = 8N1, 1 = 8N2, 2 = 8E1, 3 = 8E2, 4 = 8O1, 5 = 8O2
COM1 unit ID register
56979
Ethernet protocols
Modbus TCP and Modbus RTU over TCP can be enabled in the Ethernet settings

Registers in the map: 2871 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, single, utf8(12), utf8(40), word.

MODBUS offsetDescriptionUnitsData typeScale
50Meter model utf8(40) 
1717Current version utf8(12) 
30Meter name utf8(40) 
1837Yearyearword 
1838Monthmonthword 
1839Daydaysword 
1840Hourhword 
1841Minuteminword 
1842Secondsword 
1844Day of week word 
2400Digital input status validity base unit word 
2402Digital output status validity base unit word 
2420Setpoint status validity word 
2550Digital input status validity option slot A word 
2552Digital input status validity option slot B word 
2554Digital input status validity option slot C word 
2556Digital input status validity option slot D word 
2566Digital output status validity option slot A word 
2568Digital output status validity option slot B word 
2570Digital output status validity option slot C word 
2572Digital output status validity option slot D word 
2700Active energy delivered (into load)kWhsingle 
2702Active energy received (out of load)kWhsingle 
2704Active energy delivered + receivedkWhsingle 
2706Active energy delivered receivedkWhsingle 
2708Reactive energy deliveredkvarhsingle 
2710Reactive energy receivedkvarhsingle 
2712Reactive energy delivered + receivedkvarhsingle 
2714Reactive energy delivered receivedkvarhsingle 
2716Apparent energy deliveredkVAhsingle 
2718Apparent energy receivedkVAhsingle 
2720Apparent energy delivered + receivedkVAhsingle 
2722Apparent energy delivered receivedkVAhsingle 
2724Active energy in Q1kWhsingle 
2726Active energy in Q2kWhsingle 
2728Active energy in Q3kWhsingle 
2730Active energy in Q4kWhsingle 
2732Reactive energy in Q1kvarhsingle 
2734Reactive energy in Q2kvarhsingle 
2736Reactive energy in Q3kvarhsingle 
2738Reactive energy in Q4kvarhsingle 
2740Apparent energy in Q1kVAhsingle 
2742Apparent energy in Q2kVAhsingle 
2744Apparent energy in Q3kVAhsingle 
2746Apparent energy in Q4kVAhsingle 
2748Conditional active energy delivered (into load)kWhsingle 
2750Conditional active energy received (out of load)kWhsingle 
2754Active energy delivered received, conditionalkWhsingle 
2756Conditional reactive energy in (delivered)kvarhsingle 
2758Conditional reactive energy out (received)kvarhsingle 

This is not the complete map: 50 of 2871 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (PM800) - Measurement Data

Connection and addressing notes

Protocol
Modbus ASCII
Protocol register
632, default 0 = device selectable auto, 1 = Modbus ASCII
Interface
Ethernet (PM8ECC option module)
Settings scope
PM8ECC Ethernet option module
Default baud rate
19200
Baud rate register
629, 5 = 2400, 6 = 4800, 7 = 9600, 8 = 19200, 9 = 38400
Parity
even
Parity register
630, 0 = none, 2 = even
Wire mode register
631, default 1 = 2-wire, 2 = 4-wire
Ethernet physical connection register
628, default 0 = 10T/100TX auto (half duplex)
Frame type register
634, default 0 = Ethernet II

Registers in the map: 953 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, string(16).

MODBUS offsetDescriptionUnitsData typeScale
3059Present FW module integer 
3086Model ID integer 
628Ethernet physical connection integer 
631Wire mode integer 
632Port protocol mode integer 
633PM8ECC reset counter integer 
634Frame type integer 
1100Current, phase AA/Scaleinteger 
1101Current, phase BA/Scaleinteger 
1102Current, phase CA/Scaleinteger 
1103Current, neutralA/Scaleinteger 
1104Current, groundA/Scaleinteger 
1105Current, 3-phase averageA/Scaleinteger 
1107Current, unbalance, phase A%integer×0.1
1108Current, unbalance, phase B%integer×0.1
1109Current, unbalance, phase C%integer×0.1
1110Current, unbalance, max%integer×0.1
1120Voltage, A-BV/Scaleinteger 
1121Voltage, B-CV/Scaleinteger 
1122Voltage, C-AV/Scaleinteger 
1123Voltage, L-L averageV/Scaleinteger 
1124Voltage, A-NV/Scaleinteger 
1125Voltage, B-NV/Scaleinteger 
1126Voltage, C-NV/Scaleinteger 
1127Voltage, N-RV/Scaleinteger 
1128Voltage, L-N averageV/Scaleinteger 
1129Voltage, unbalance, A-B%integer×0.1
1130Voltage, unbalance, B-C%integer×0.1
1131Voltage, unbalance, C-A%integer×0.1
1132Voltage, unbalance, max L-L%integer×0.1
1133Voltage, unbalance, A-N%integer×0.1
1134Voltage, unbalance, B-N%integer×0.1
1135Voltage, unbalance, C-N%integer×0.1
1136Voltage, unbalance, max L-N%integer×0.1
1140Real power, phase AkW/Scaleinteger 
1141Real power, phase BkW/Scaleinteger 
1142Real power, phase CkW/Scaleinteger 
1143Real power, totalkW/Scaleinteger 
1144Reactive power, phase Akvar/Scaleinteger 
1145Reactive power, phase Bkvar/Scaleinteger 
1146Reactive power, phase Ckvar/Scaleinteger 
1147Reactive power, totalkvar/Scaleinteger 
1148Apparent power, phase AkVA/Scaleinteger 
1149Apparent power, phase BkVA/Scaleinteger 
1150Apparent power, phase CkVA/Scaleinteger 
1151Apparent power, totalkVA/Scaleinteger 
1160True power factor, phase A integer×0.001
1161True power factor, phase B integer×0.001
1162True power factor, phase C integer×0.001
1163True power factor, total integer×0.001

This is not the complete map: 50 of 953 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric PM9C - Measurement Data

Connection and addressing notes

Protocol
Modbus
Register addressing
one-based Modbus register number with decimal and hexadecimal protocol address
Address example
register 101 = protocol address 100 = 0x64
Value size
number of words per value given in the table

Registers in the map: 34. function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
100Current transformer ratio (ct) word 
101Voltage transformer ratio (pt) word×0.1
102System type word 
103Type of power demand: (dmd type) word 
104Demand calculation interval (dmd time)minword 
200Reset of word 
1000I1: phase 1 currentAdword×0.001
1002I2: phase 2 currentAdword×0.001
1004I3: phase 3 currentAdword×0.001
1006In: neutral currentAdword×0.001
1008U12: line 1 to line 2 voltageVdword×0.001
1010U23: line 2 to line 3 voltageVdword×0.001
1012U31: line 3 to line 1 voltageVdword×0.001
1014V1n: line 1 to neutral voltageVdword×0.001
1016V2n: line 2 to neutral voltageVdword×0.001
1018V3n: line 3 to neutral voltageVdword×0.001
1020F: frequencyHzdword×0.01
1022P: total active power (+/- signed value)kWdword×0.01
1024Q: total reactive power (+/- signed value)kvardword×0.01
1026S: total apparent powerkVAdword×0.01
1028Pf: total power factor (+/- signed value) dword×0.01
1030Power factor sector dword 
1032Power demand: active or reactive or apparent (see reg. 104)kWdword×0.01
1034Max power demand: active or reactive or apparent (see reg. 104)kWdword×0.01
1036Operating time counter dword×0.01
1038Active energy total counterkWhdword 
1040Reactive energy total counterkvarhdword 
1042Active energy partial counterkWhdword 
1044P1: phase 1 active power (+/- signed value)kWdword×0.01
1046P2: phase 2 active power (+/- signed value)kWdword×0.01
1048P3: phase 3 active power (+/- signed value)kWdword×0.01
1050Q1: phase 1 reactive power (+/- signed value)kvardword×0.01
1052Q2: phase 2 reactive power (+/- signed value)kvardword×0.01
1054Q3: phase 3 reactive power (+/- signed value)kvardword×0.01

Schneider Electric (PVSCL20E) - MODBUS Mapping

Registers in the map: 50. function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
40070AC CurrentAword×10A_SF
40071Phase A CurrentAword×10A_SF
40072Phase B CurrentAword×10A_SF
40073Phase C CurrentAword×10A_SF
40074Scale factor [A_SF] smallint 
40075Phase Voltage ABVword×10V_SF
40076Phase Voltage BCVword×10V_SF
40077Phase Voltage CAVword×10V_SF
40078Phase Voltage ANVword×10V_SF
40079Phase Voltage BNVword×10V_SF
40080Phase Voltage CNVword×10V_SF
40081Scale factor [V_SF] smallint 
40082AC PowerWsmallint×10W_SF
40083Scale factor [W_SF] smallint 
40084Line FrequencyHzword×10HZ_SF
40085Scale factor [HZ_SF] smallint 
40086AC Apparent PowerVAsmallint×10VA_SF
40087Scale factor [VA_SF] smallint 
40088AC Reactive Powervarsmallint×10VAR_SF
40089Scale factor [VAR_SF] smallint 
40090AC Power Factor%smallint×10PF_SF
40091Scale factor [PF_SF] smallint 
40092AC EnergyWhdword×10WH_SF
40094Scale factor [WH_SF] smallint 
40095DC CurrentAword×10DCA_SF
40096Scale factor [DCA_SF] smallint 
40097DC VoltageVword×10DCV_SF
40098Scale factor [DCV_SF] smallint 
40099DC PowerWsmallint×10DCW_SF
40100Scale factor [DCW_SF] smallint 
40101Cabinet Temperaturedeg Csmallint×10TMP_SF
40102Heat Sink Temperaturedeg Csmallint×10TMP_SF
40103Transformer Temperaturedeg Csmallint×10TMP_SF
40104Other Temperaturedeg Csmallint×10TMP_SF
40105Scale factor [TMP_SF] smallint 
40106Enumerated value. Operating state word 
40107Vendor specific operating state code word 
40108Bitmask value. Event fields dword 
40110Reserved for future use dword 
40112Vendor defined events dword 
40114Vendor defined events dword 
40116Vendor defined events dword 
40118Vendor defined events dword 
40122Scale factor [DCA_SF] smallint 
40123Scale factor [DCV_SF] smallint 
40124Scale factor [DCW_SF] smallint 
40125Scale factor [DCWH_SF] smallint 
40126EVT dword 
40128N  
40129TMSPER word 

Schneider Electric (Sepam 40) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Register addressing
word addresses are hexadecimal (e.g. 0113)
Function codes
3 and 4 for reads
Time-tagged values
read with function code 3
32-bit values
occupy two consecutive words (e.g. 01A8/01A9)

Registers in the map: 113 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
275Phase current I1 word×0.1
276Phase current I2 word×0.1
277Phase current I3 word×0.1
278Residual current i0 sum word×0.1
279Residual current measured word×0.1
280Average phase current IM1 word×0.1
281Average phase current IM2 word×0.1
282Average phase current IM3 word×0.1
283Peak demand phase current IM1 word×0.1
284Peak demand phase current IM2 word×0.1
285Peak demand phase current IM3 word×0.1
286Phase-to-phase voltage U21 word 
287Phase-to-phase voltage U32 word 
288Phase-to-phase voltage U13 word 
289Phase-to-neutral voltage V1 word 
290Phase-to-neutral voltage V2 word 
291Phase-to-neutral voltage V3 word 
292Residual voltage v0 word 
293Positive sequence voltage vd word 
294Negative sequence voltage vi word 
295Frequency word×0.01
296Active power P smallint 
297Reactive power Q smallint 
298Apparent power S smallint 
299Peak demand active power pm smallint 
300Peak demand reactive power qm smallint 
301Power factor cos smallint×0.01
302Positive active energy ea+ dword×100
304Negative active energy ea- dword×100
306Positive reactive energy er+ dword×100
308Negative reactive energy er- dword×100
310Phase current I1 word 
311Phase current I2 word 
312Phase current I3 word 
313Residual current i0 sum word 
314Residual current measured word 
315Average phase current IM1 word 
316Average phase current IM2 word 
317Average phase current IM3 word 
318Peak demand phase current IM1 word 
319Peak demand phase current IM2 word 
320Peak demand phase current IM3 word 
321Phase-to-phase voltage U21 word×10
322Phase-to-phase voltage U32 word×10
323Phase-to-phase voltage U13 word×10
324Phase-to-neutral voltage V1 word×10
325Phase-to-neutral voltage V2 word×10
326Phase-to-neutral voltage V3 word×10
327Residual voltage v0 word×10
328Positive sequence voltage vd word×10

This is not the complete map: 50 of 113 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (Sepam 60) - MODBUS Values

Connection and addressing notes

Register addressing
word addresses are hexadecimal (e.g. 0200/0201)
Function codes
3 and 4 for reads
32-bit values
occupy two consecutive words
32-bit metering and diagnosis zone
exceeds the capacity of a frame
Zone read requests
at least two requests are required to read the zone in full

Registers in the map: 104 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
512Phase current I1 dword×0.1
514Phase current I2 dword×0.1
516Phase current I3 dword×0.1
518Residual current i0 dword×0.1
520Residual current i0 dword×0.1
522Demand current IM1 dword×0.1
524Demand current IM2 dword×0.1
526Demand current IM3 dword×0.1
528Peak demand current IM1 dword×0.1
530Peak demand current IM2 dword×0.1
532Peak demand current IM3 dword×0.1
534Phase-to-phase voltage U21 dword 
536Phase-to-phase voltage U32 dword 
538Phase-to-phase voltage U13 dword 
540Phase-to-neutral voltage V1 dword 
542Phase-to-neutral voltage V2 dword 
544Phase-to-neutral voltage V3 dword 
546Residual voltage v0 dword 
548Positive sequence voltage vd dword 
550Negative-sequence voltage vi dword 
552Frequency fHzdword×0.01
554Active power PkWinteger×0.1
560Power factor cos integer×0.01
562Peak demand active power PMkWinteger×0.1
564Peak demand reactive power QMkvarinteger×0.1
566Active power P phase 1kWinteger×0.1
568Active power P phase 2kWinteger×0.1
570Active power P phase 3kWinteger×0.1
572Reactive power Q phase 1kvarinteger×0.1
574Reactive power Q phase 2kvarinteger×0.1
576Reactive power Q phase 3kvarinteger×0.1
578Apparent power S phase 1kVAinteger×0.1
580Apparent power S phase 2kVAinteger×0.1
582Apparent power S phase 3kVAinteger×0.1
584Positive active energy ea+kWdword×100
586Negative active energy ea-kWdword×100
588Positive reactive energy er+kvardword×100
590Negative reactive energy er-kvardword×100
592Ext. positive active energy ea+kWdword×100
594Ext. negative active energy ea-kWdword×100
596Ext. positive reactive energy er+kvardword×100
598Ext. negative reactive energy er-kvardword×100
600Neutral-point voltage vnt dword 
616Number of operations dword 
618Tripping current phase 1 itrip1 dword×0.1
620Tripping current phase 2 itrip2 dword×0.1
622Tripping current phase 3 itrip3 dword×0.1
624Tripping current calculated i0 itrip0 dword×0.1
636Number of operations dword 
650Impedance ZdMOhmdword 

This is not the complete map: 50 of 104 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (Sepam 80) - Measurement Data

Connection and addressing notes

Register addressing
word addresses are hexadecimal (e.g. 0200/0201)
Function codes
3 and 4 for reads
32-bit values
occupy two consecutive words
32-bit metering and diagnosis zone
exceeds the capacity of a frame
Zone read requests
at least two requests are required to read the zone in full

Registers in the map: 141 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
512Phase current I1 dword×0.1
514Phase current I2 dword×0.1
516Phase current I3 dword×0.1
518Residual current i0 dword×0.1
520Residual current i0 dword×0.1
522Demand current Im1 dword×0.1
524Demand current Im2 dword×0.1
526Demand current Im3 dword×0.1
528Peak demand current IM1 dword×0.1
530Peak demand current IM2 dword×0.1
532Peak demand current IM3 dword×0.1
534Phase to phase voltage U21 dword 
536Phase to phase voltage U32 dword 
538Phase to phase voltage U13 dword 
540Phase to neutral voltage V1 dword 
542Phase to neutral voltage V2 dword 
544Phase to neutral voltage V3 dword 
546Residual voltage v0 dword 
548Positive sequence voltage vd dword 
550Negative sequence voltage vi dword 
552Frequency fHzdword×0.01
554Active power PkWinteger×0.1
556Reactive power Qkvarinteger×0.1
558Apparent power SkVAinteger×0.1
560Power factor cos integer×0.01
562Peak demand active power pmkWinteger×0.1
564Peak demand reactive power qmkvarinteger×0.1
566Active power P phase 1kWinteger×0.1
568Active power P phase 2kWinteger×0.1
570Active power P phase 3kWinteger×0.1
572Reactive power Q phase 1kvarinteger×0.1
574Reactive power Q phase 2kvarinteger×0.1
576Reactive power Q phase 3kvarinteger×0.1
578Apparent power S phase 1kVAinteger×0.1
580Apparent power S phase 2kVAinteger×0.1
582Apparent power S phase 3kVAinteger×0.1
584Positive active energy ea+kWdword×100
586Negative active energy eakWdword×100
588Positive reactive energy er+kvardword×100
590Negative reactive energy erkvardword×100
592Ext. positive active energy ea+kWdword×100
594Ext. negative active energy eakWdword×100
596Ext. positive reactive energy ea+kvardword×100
598Ext. negative reactive energy eakvardword×100
600Neutral point voltage vnt dword 
602H3 neutral point voltage v3nt dword 
604H3 residual voltage v3r dword 
606Phase current i-1 dword×0.1
608Phase current i-2 dword×0.1
610Phase current i-3 dword×0.1

This is not the complete map: 50 of 141 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (Symmetra PX) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus TCP and Modbus RTU
Interface
Ethernet (Modbus TCP) or serial (Modbus RTU)
Function codes
3 and 4
Byte order
16-bit registers transmitted MSB first (big-endian)
32-bit byte order
UINT32 values most-significant word first
Register addressing
absolute starting register address 0 equals Modicon register 40001 (wire address zero)
Status bits
atomic within a single register only
Maximum frame size
26 words

Registers in the map: 71 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: word.

MODBUS offsetDescriptionUnitsData typeScale
0Alarm/Status register word 
1Alarm/Status register word 
2Alarm/Status register word 
3Alarm/Status register word 
4Alarm/Status register word 
5Alarm/Status register word 
6Line quality 00FF=acceptable utility line quality 0000=unacceptable utility line quality word 
7% battery capacity remaining battery capacity as a percent of the fully charged condition (0-100)%word 
8Runtime remainingminword 
9Battery voltage present UPS battery voltageVword 
10UPS internal temperature (0-209) 00XX=valid reading FFXX=invalid reading XX=sensor reading word 
11Amps drawn by loadAword 
12Number of battery packs with bad batterieseachword 
13Number of battery packseachword 
14UPS output load as a percentage of full rated load in watts%word 
15Maximum input voltage since last readingVword 
16Minimum input voltage since last readingVword 
17Nominal battery voltageVword 
18Actual battery voltageVword 
19Utility input frequencyHzword 
20Phase A utility input voltageVword 
21Phase A utility input currentAword 
22Phase A bypass input voltageVword 
23Phase A percent of maximum output VA @ N + 0%word 
24Phase A percent of maximum output VA @ N + x%word 
25Phase A outputkVAword 
26Phase A output voltageVword 
27Phase A output currentAword 
28Phase A peak output currentAword 
29Phase B utility input voltageVword 
30Phase B utility input currentAword 
31Phase B bypass input voltageVword 
32Phase B percent of maximum output VA @ N + 0%word 
33Phase B percent of maximum output VA @ N + x%word 
34Phase B outputkVAword 
35Phase B output voltageVword 
36Phase B output currentAword 
37Phase B peak output currentAword 
38Phase C utility input voltageVword 
39Phase C utility input currentAword 
40Phase C bypass input voltageVword 
41Phase C percent of maximum output VA @ N + 0%word 
42Phase C percent of maximum output VA @ N + x%word 
43Phase C outputkVAword 
44Phase C output voltageVword 
45Phase C output currentAword 
46Phase C peak output currentAword 
47Environmental monitoring card temperature reading (Sensor 1) word 
48Environmental monitoring card humidity reading (Sensor 1)%RHword 
49Environmental monitoring card temperature reading (Sensor 2) word 

This is not the complete map: 50 of 71 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (XW Hybrid Inverter) - MODBUS Registers Map

Registers in the map: 147 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
40070AC CurrentAword×10A_SF
40071Phase A CurrentAword×10A_SF
40072Phase B CurrentAword×10A_SF
40073Phase C CurrentAword×10A_SF
40074Scale factor [A_SF] smallint 
40075Phase Voltage ABVword×10V_SF
40076Phase Voltage BCVword×10V_SF
40077Phase Voltage CAVword×10V_SF
40078Phase Voltage ANVword×10V_SF
40079Phase Voltage BNVword×10V_SF
40080Phase Voltage CNVword×10V_SF
40081Scale factor [V_SF] smallint 
40082AC PowerWsmallint×10W_SF
40083Scale factor [W_SF] smallint 
40084Line FrequencyHzword×10HZ_SF
40085Scale factor [HZ_SF] smallint 
40086AC Apparent PowerVAsmallint×10VA_SF
40087Scale factor [VA_SF] smallint 
40088AC Reactive Powervarsmallint×10VAR_SF
40089Scale factor [VAR_SF] smallint 
40090AC Power Factor%smallint×10PF_SF
40091Scale factor [PF_SF] smallint 
40092AC EnergyWhdword×10WH_SF
40094Scale factor [WH_SF] smallint 
40095DC CurrentAword×10DCA_SF
40096Scale factor [DCA_SF] smallint 
40097DC VoltageVword×10DCV_SF
40098Scale factor [DCV_SF] smallint 
40099DC PowerWsmallint×10DCW_SF
40100Scale factor [DCW_SF] smallint 
40101Cabinet Temperaturedeg Csmallint×10TMP_SF
40102Heat Sink Temperaturedeg Csmallint×10TMP_SF
40103Transformer Temperaturedeg Csmallint×10TMP_SF
40104Other Temperaturedeg Csmallint×10TMP_SF
40105Scale factor [TMP_SF] smallint 
40106Enumerated value. Operating state word 
40107Vendor specific operating state code word 
40108Bitmask value. Event fields dword 
40110Reserved for future use dword 
40112Vendor defined events dword 
40114Vendor defined events dword 
40116Vendor defined events dword 
40118Vendor defined events dword 
40122Type of DER device. Default value is 4 to indicate PV device. word 
40123Continuous power output capability of the inverter.Wword×10WRTG_SF
40124Scale factor smallint 
40125Continuous capability of the inverter.VAword×10VARTG_SF
40126Scale factor smallint 
40127Continuous VAR capability of the inverter in Q1.varsmallint×10VARRTG_SF
40128Continuous VAR capability of the inverter in Q2.varsmallint×10VARRTG_SF

This is not the complete map: 50 of 147 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection