Schneider Electric PM5500 data logger. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
29Meter name utf8(40)
49Meter model utf8(40)
69Manufacturer utf8(40)
89Product ID number word
129Serial number dword
135Hardware revision utf8(10)
1636Present firmware version (DLF format) X.Y.T word
1637X major word
1638Y minor word
1639Z quality word
1641Previous firmware version (DLF format) X.Y.T word
1642X major word
1643Y minor word
1644Z quality word
1668Present firmware version (DLF format) X.Y.T word
1700Present firmware version (DLF format) X.Y.T word
1827Number of metering system restarts word
1828Number of control power failures word
1833Duration of last control power failuresecondsdword
1835Cause of last meter reset word
1836Yearyearword
1837Monthmonthword
1838Daydaysword
1839Hourhoursword
1840Minuteminutesword
1841Secondsecondsword
1842Millisecondmsecword
1844Year word
1845Month and day word
1846Hour and minute word
1847Milliseconds word
1919Revenue security switch status word
1920Revenue security status word
2001Active load timersecondsdword
2003Meter operation timersecondsdword
2013Number of phases word
2014Number of wires word
2015Power system configuration word
2016Nominal frequencyHzword
2017Nominal voltageVsingle
2019Nominal currentAsingle
2023Normal phase rotation word
2024Number VTs word
2025VT primaryVsingle
2027VT secondaryVword
2028Number CTs word
2029CT primaryAword
2030CT secondaryAword
2031CT primary NAword
2032CT secondary NAword
There are more MODBUS items for this device. Please, download the program.