Schneider Electric CM2000, Conext Gateway MODBUS registers: read online
Connect Schneider Electric to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Schneider Electric data logging and capture.
2028 Command Password, 2029 Display Setup Password, 2030 Full Access Front Panel Reset Password, 2031 Reset Access Password
Password range
0-9998
Reset access password
-32768 uses the Configuration password
Registers in the map: 334 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: smallint, word.
MODBUS offset
Description
Units
Data type
Scale
1000
Update interval
s
word
×0.001
1001
Frequency
Hz
word
formula
1002
Temperature inside CM enclosure
deg C
word
×0.01
1003
Current, phase A
A
word
formula
1004
Current, phase B
A
word
formula
1005
Current, phase C
A
word
formula
1006
Current, neutral
A
word
formula
1007
Current, ground
A
word
formula
1008
Current, 3-phase average
A
word
formula
1009
Current, apparent rms
A
word
formula
1010
Current unbalance, phase A
%
word
×0.1
1011
Current unbalance, phase B
%
word
×0.1
1012
Current unbalance, phase C
%
word
×0.1
1013
Current unbalance, worst
%
word
×0.1
1014
Voltage, phase A to B
V
word
formula
1015
Voltage, phase B to C
V
word
formula
1016
Voltage, phase C to A
V
word
formula
1017
Voltage L-L, 3-phase average
V
word
formula
1018
Voltage, phase A to neutral
V
word
formula
1019
Voltage, phase B to neutral
V
word
formula
1020
Voltage, phase C to neutral
V
word
formula
1021
Voltage L-N, 3-phase average
V
word
formula
1022
Voltage unbalance, phase A-B
%
word
×0.1
1023
Voltage unbalance, phase B-C
%
word
×0.1
1024
Voltage unbalance, phase C-A
%
word
×0.1
1025
Voltage unbalance, L-L worst
%
word
×0.1
1026
Voltage unbalance, phase A
%
word
×0.1
1027
Voltage unbalance, phase B
%
word
×0.1
1028
Voltage unbalance, phase C
%
word
×0.1
1029
Voltage unbalance, L-N worst
%
word
×0.1
1031
True power factor, phase A
word
×0.001
1032
True power factor, phase B
word
×0.001
1033
True power factor, phase C
word
×0.001
1034
True power factor, 3-phase total
word
×0.001
1035
Displacement power factor, phase A
word
×0.001
1036
Displacement power factor, phase B
word
×0.001
1037
Displacement power factor, phase C
word
×0.001
1038
Displacement power factor, 3-phase total
word
×0.001
1039
Real power, phase A
kW
word
formula
1040
Real power, phase B
kW
word
formula
1041
Real power, phase C
kW
word
formula
1042
Real power, 3-phase total
kW
word
formula
1043
Reactive power, phase A
kvar
word
formula
1044
Reactive power, phase B
kvar
word
formula
1045
Reactive power, phase C
kvar
word
formula
1046
Reactive power, 3-phase total
kvar
word
formula
1047
Apparent power, phase A
kVA
word
formula
1048
Apparent power, phase B
kVA
word
formula
1049
Apparent power, phase C
kVA
word
formula
1050
Apparent power, 3-phase total
kVA
word
formula
This is not the complete map: 50 of 334 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric (Conext Gateway) - Measurement Data
Registers in the map: 211 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
40070
AC Current
A
word
×10A_SF
40071
Phase A Current
A
word
×10A_SF
40072
Phase B Current
A
word
×10A_SF
40073
Phase C Current
A
word
×10A_SF
40074
Scale factor [A_SF]
smallint
40075
Phase Voltage AB
V
word
×10V_SF
40076
Phase Voltage BC
V
word
×10V_SF
40077
Phase Voltage CA
V
word
×10V_SF
40078
Phase Voltage AN
V
word
×10V_SF
40079
Phase Voltage BN
V
word
×10V_SF
40080
Phase Voltage CN
V
word
×10V_SF
40081
Scale factor [V_SF]
smallint
40082
AC Power
W
smallint
×10W_SF
40083
Scale factor [W_SF]
smallint
40084
Line Frequency
Hz
word
×10HZ_SF
40085
Scale factor [HZ_SF]
smallint
40086
AC Apparent Power
VA
smallint
×10VA_SF
40087
Scale factor [VA_SF]
smallint
40088
AC Reactive Power
var
smallint
×10VAR_SF
40089
Scale factor [VAR_SF]
smallint
40090
AC Power Factor
%
smallint
×10PF_SF
40091
Scale factor [PF_SF]
smallint
40092
AC Energy
Wh
dword
×10WH_SF
40094
Scale factor [WH_SF]
smallint
40095
DC Current
A
word
×10DCA_SF
40096
Scale factor [DCA_SF]
smallint
40097
DC Voltage
V
word
×10DCV_SF
40098
Scale factor [DCV_SF]
smallint
40099
DC Power
W
smallint
×10DCW_SF
40100
Scale factor [DCW_SF]
smallint
40101
Cabinet Temperature
deg C
smallint
×10TMP_SF
40102
Heat Sink Temperature
deg C
smallint
×10TMP_SF
40103
Transformer Temperature
deg C
smallint
×10TMP_SF
40104
Other Temperature
deg C
smallint
×10TMP_SF
40105
Scale factor [TMP_SF]
smallint
40106
Enumerated value. Operating state
word
40107
Vendor specific operating state code
word
40108
Bitmask value. Event fields
dword
40110
Reserved for future use
dword
40112
Vendor defined events
dword
40114
Vendor defined events
dword
40116
Vendor defined events
dword
40118
Vendor defined events
dword
40122
Type of DER device. Default value is 4 to indicate PV device.
word
40123
Continuous power output capability of the inverter.
W
word
×10WRTG_SF
40124
Scale factor
smallint
40125
Continuous capability of the inverter.
VA
word
×10VARTG_SF
40126
Scale factor
smallint
40127
Continuous VAR capability of the inverter in Q1.
var
smallint
×10VARRTG_SF
40128
Continuous VAR capability of the inverter in Q2.
var
smallint
×10VARRTG_SF
This is not the complete map: 50 of 211 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric (EM1000,EM1100,EM1200) - MODBUS Registers Map
Registers in the map: 70 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single.
MODBUS offset
Description
Units
Data type
Scale
3056
Current average
single
3008
Current, phase 1
single
3024
Current, phase 2
single
3040
Current, phase 3
single
3058
Voltage (ll) average
single
3010
Voltage(ll), phase 1 2
single
3026
Voltage(ll), phase 2 3
single
3042
Voltage(ll), phase 3 1
single
3060
Voltage(ln) average
single
3012
Voltage(ln), phase 1
single
3028
Voltage(ln), phase 2
single
3044
Voltage(ln), phase 3
single
3062
Frequency
single
3050
Active power, total
single
3002
Active power, phase 1
single
3018
Active power, phase 2
single
3034
Active power, phase 3
single
3052
Reactive power, total
single
3004
Reactive power, phase 1
single
3020
Reactive power, phase 2
single
3036
Reactive power, phase 3
single
3048
Apparent power, total
single
3000
Apparent power, phase 1
single
3016
Apparent power, phase 2
single
3032
Apparent power, phase 3
single
3054
Power factor total
single
3006
Power factor, phase 1
single
3022
Power factor, phase 2
single
3038
Power factor, phase 3
single
3200
Forward apparent energy
single
3202
Forward active energy
single
3204
Forward reactive energy
single
3264
Forward run seconds
dword
3266
On seconds
dword
3268
Number of input voltage interruptions
dword
2506
Current average
single
2500
Current, phase 1
single
2502
Current, phase 2
single
2504
Current, phase 3
single
2514
Voltage (ll) average
single
2508
Voltage(ll), phase 1 2
single
2510
Voltage(ll), phase 2 3
single
2512
Voltage(ll), phase 3 1
single
2522
Voltage(ln) average
single
2516
Voltage(ln), phase 1
single
2518
Voltage(ln), phase 2
single
2520
Voltage(ln), phase 3
single
2530
Frequency
single
2546
Active power, total
single
2540
Active power, phase 1
single
This is not the complete map: 50 of 70 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric (EM3502,EM3550) - MODBUS Values
ULong with MSR (most significant register) and LSR
Data format
float32 available
Third output
0 = RS-485, 2 = VAR pulse
Address and baud rate setup
front panel Setup menu
Registers in the map: 101 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.
MODBUS offset
Description
Units
Data type
Scale
0
Real energy consumption (msr)
kWh
dword
2
Total instantaneous real power (3 phase total)
kW
word
3
Total instantaneous reactive power (3 phase total)
kvar
word
4
Total instantaneous apparent power (3 phase total)
kVA
word
5
Total power factor (total kw / total kva)
Ratio
word
×0.0001
6
Voltage, L l, average of 3 phases
V
word
7
Voltage, L n, average of 3 phases
V
word
8
Current, average of 3 phases
A
word
9
Real power, phase A
kW
word
10
Real power, phase B
kW
word
11
Real power, phase C
kW
word
12
Power factor, phase A
Ratio
word
×0.0001
13
Power factor, phase B
Ratio
word
×0.0001
14
Power factor, phase C
Ratio
word
×0.0001
15
Voltage, phase A B
V
word
16
Voltage, phase B C
V
word
17
Voltage, phase A C
V
word
18
Voltage, phase A N
V
word
19
Voltage, phase B N
V
word
20
Voltage, phase C N
V
word
21
Current, instantaneous, phase A
A
word
22
Current, instantaneous, phase B
A
word
23
Current, instantaneous, phase C
A
word
25
Frequency (derived from phase a)
Hz
word
×0.01
26
Apparent energy consumption (msr)
kVAh
dword
28
Reactive energy consumption (msr)
kvarh
dword
30
Apparent power, phase A
kVA
word
31
Apparent power, phase B
kVA
word
32
Apparent power, phase C
kVA
word
33
Reactive power, phase A
kvar
word
34
Reactive power, phase B
kvar
word
35
Reactive power, phase C
kvar
word
36
Total real power present demand
kW
word
37
Total reactive power present demand
kvar
word
38
Total apparent power present demand
kVA
word
39
Total real power max. demand
kW
word
40
Total reactive power max. demand
kvar
word
41
Total apparent power max. demand
kVA
word
42
Pulse counter 1 (real energy)
dword
44
Pulse counter 2 (reactive energy)
dword
46
Real energy consumption phase A
kWh
dword
48
Real energy consumption phase B
kWh
dword
50
Real energy consumption phase C
kWh
dword
129
Single phase: A + N
word
130
Ct ratio primary
A
word
131
Ct ratio secondary interface
word
132
Pt ratio
word
×100
133
System voltage
word
134
Theoretical maximum system power
kW
word
136
Display units
word
This is not the complete map: 50 of 101 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 328 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, smallint, string, word.
MODBUS offset
Description
Units
Data type
Scale
5031
Model
string
5319
Product Revision
string
5323
Hardware Revision
string
6999
Hardware Version
word
7000
Firmware version (reset system)
word
7001
Firmware version (operating system)
word
7002
Device ID
word
0
Real energy consumption
kWh
dword
2
Total instantaneous real power (3 phase total)
kW
word
3
Total instantaneous reactive power (3 phase total)
kvar
word
4
Total instantaneous apparent power (3 phase total)
kVA
word
5
Total power factor (total kw / total kva)
Ratio
word
6
Voltage, line to line, average of phases
V
word
7
Voltage, line to neutral, average of phases
V
word
8
Current, average of phases
A
word
9
Real power, L1
kW
word
10
Real power, L2
kW
word
11
Real power, L3
kW
word
12
Power factor, L1
Ratio
word
13
Power factor, L2
Ratio
word
14
Power factor, L3
Ratio
word
15
Voltage, L1 L2
V
word
16
Voltage, L2 L3
V
word
17
Voltage, L3 L1
V
word
18
Voltage, L1 N
V
word
19
Voltage, L2 N
V
word
20
Voltage, L3 N
V
word
21
Current, instantaneous, L1
A
word
22
Current, instantaneous, L2
A
word
23
Current, instantaneous, L3
A
word
24
Present demand sub interval
kW
word
25
Minimum demand
kW
word
26
Maximum demand
kW
word
27
Present demand
kW
word
28
Peak demand
kW
word
30
Ct size (100, 300, etc.)
A
word
31
Count of kwh resets
word
32
Count of peak demand resets
word
33
Count of sub intervals
word
34
Count of number readings in present sub interval
word
35
System type: see manual
word
36
Sub interval length
word
37
Number of sub intervals per demand interval
word
38
Command
Bitmask
word
256
Real energy consumption
kWh
single
258
Real energy consumption (redundant)
kWh
single
260
Total instantaneous real power
kW
single
262
Total instantaneous reactive power
kvar
single
264
Total instantaneous apparent power
kVA
single
266
Total power factor (total kw / total kva)
Ratio
single
This is not the complete map: 50 of 328 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PM1000 PM1200 - MODBUS Registers Map
Registers in the map: 137 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single.
MODBUS offset
Description
Units
Data type
Scale
3913
Current average
A
single
3929
Current, phase 1 (A1)
single
3943
Current, phase 2 (A2)
single
3957
Current, phase 3 (A3)
single
3909
Line to line average voltage (VLL)
single
3911
Line to neutral voltage (VLN)
single
3925
Voltage phase 1 to phase 2 (V12)
single
3939
Voltage phase 2 to phase 3 (V23)
single
3953
Voltage phase 3 to phase 1 (V31)
single
3927
Voltage phase 1 to neutral (V1)
single
3941
Voltage phase 2 to neutral (V2)
single
3955
Voltage phase 3 to neutral (V3)
single
3903
Active power, total
W
single
3919
Active power, phase 1 (W1)
single
3933
Active power, phase 2 (W2)
single
3947
Active power, phase 3 (W3)
single
3905
Reactive power, total
var
single
3921
Reactive power, phase 1 (VAR1)
single
3935
Reactive power, phase 2 (VAR2)
single
3949
Reactive power, phase3 (VAR3)
single
3901
Apparent power, total
VA
single
3917
Apparent power, phase 1 (VA1)
single
3931
Apparent power, phase 2 (VA2)
single
3945
Apparent power, phase 3 (VA3)
single
3907
Power factor average
PF
single
3923
Power factor, phase 1 (PF1)
single
3937
Power factor, phase 2 (PF2)
single
3951
Power factor, phase 3 (PF3)
single
3915
Frequency, hz (F)
single
3861
Voltage THD, phase 1 (%V1)
single
3863
Voltage THD, phase 2 (%V2)
single
3865
Voltage THD, phase 3 (%V3)
single
3867
Current THD, phase 1 (%A1)
single
3869
Current THD, phase 2 (%A2)
single
3871
Current THD, phase 3 (%A3)
single
3959
Forward apparent energy (FwdVAh)
single
3961
Forward active energy (FwdWh)
single
3963
Forward reactive inductive energy (FwdVARh)
single
3965
Forward reactive capacitive energy (FwdVARh)
single
3967
Reverse apparent energy (RevVAh)
single
3969
Reverse active energy (RevWh)
single
3971
Reverse reactive inductive energy (RevVARh)
single
3973
Reverse reactive capacitive energy (RevVARh)
single
3993
On hours (On hrs)
integer
3995
Forward run seconds (FwdRun secs)
integer
3997
Reverse run seconds (RevRun secs)
integer
3999
Number of power interruptions (Intr)
integer
3975
Present demand (Present demand)
single
3977
Rising demand (Rising demand)
single
3979
Maximum demand (Max MD)
single
This is not the complete map: 50 of 137 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 117 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: int64, single, smallint.
MODBUS offset
Description
Units
Data type
Scale
2675
Active energy delivered (Into load)
kWh
single
2677
Active energy received (Out of load)
kWh
single
2679
Active energy delivered + received
kWh
single
2681
Active energy delivered- received
kWh
single
2683
Reactive energy delivered
kvarh
single
2685
Reactive energy received
kvarh
single
2687
Reactive energy delivered + received
kvarh
single
2689
Reactive energy delivered - received
kvarh
single
2691
Apparent energy delivered
kVAh
single
2693
Apparent energy received
kVAh
single
2695
Apparent energy delivered + received
kVAh
single
2697
Apparent energy delivered - received
kVAh
single
2699
Active energy delivered (Into load)
kWh
single
2701
Active energy received (Out of load)
kWh
single
2703
Active energy delivered + received
kWh
single
2705
Active energy delivered- received
kWh
single
2707
Reactive energy delivered
kvarh
single
2709
Reactive energy received
kvarh
single
2711
Reactive energy delivered + received
kvarh
single
2713
Reactive energy delivered - received
kvarh
single
2715
Apparent energy delivered
kVAh
single
2717
Apparent energy received
kVAh
single
2719
Apparent energy delivered + received
kVAh
single
2721
Apparent energy delivered - received
kVAh
single
2731
Reactive energy in Q1
kvarh
single
2733
Reactive energy in Q2
kvarh
single
2737
Reactive energy in Q3
kvarh
single
2739
Reactive energy in Q4
kvarh
single
2811
Active energy delivered phase A
kWh
single
2813
Active energy delivered phase B
kWh
single
2815
Active energy delivered phase C
kWh
single
2817
Reactive energy delivered phase A
kvarh
single
2819
Reactive energy delivered phase B
kvarh
single
2821
Reactive energy delivered phase C
kvarh
single
2823
Apparent energy delivered phase A
kVAh
single
2825
Apparent energy delivered phase B
kVAh
single
2827
Apparent energy delivered phase C
kVAh
single
2999
Current A
A
single
3001
Current B
A
single
3003
Current C
A
single
3005
Current N
A
single
3007
Current G
A
single
3009
Current avg
A
single
3011
Current unbalance A
%
single
3013
Current unbalance B
%
single
3015
Current unbalance C
%
single
3017
Current unbalance worst
%
single
3019
Voltage A-B
V
single
3021
Voltage B-C
V
single
3023
Voltage C-A
V
single
This is not the complete map: 50 of 117 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric (PM5000, PM5200) - MODBUS Mapping
Registers in the map: 310 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, single, utf8(10), utf8(40), word.
MODBUS offset
Description
Units
Data type
Scale
49
Meter model
utf8(40)
29
Meter name
utf8(40)
69
Manufacturer
utf8(40)
89
Product ID number
word
129
Serial number
dword
135
Hardware revision
utf8(10)
1827
Number of metering system restarts
word
1828
Number of control power failures
word
1833
Duration of last control power failure
s
dword
1835
Cause of last meter reset
word
1836
Year
year
word
1837
Month
month
word
1838
Day
days
word
1839
Hour
h
word
1840
Minute
min
word
1841
Second
s
word
1842
Millisecond
ms
word
1844
Year
word
1845
Month and day
word
1846
Hour and minute
word
1847
Milliseconds
word
1999
Conditional energy control status
word
2001
Active load timer
s
dword
2003
Meter operation timer
s
dword
2005
Cycle count
dword
2013
Number of phases
word
2014
Number of wires
word
2015
Power system configuration
word
2016
Nominal frequency
Hz
word
2017
Nominal voltage
V
single
2019
Nominal current
A
single
2021
Nominal power factor
dword
2023
Normal phase rotation
word
2024
Number VTs
word
2025
VT primary
V
single
2027
VT secondary
V
word
2028
Number CTs
word
2029
CT primary
A
word
2030
CT secondary
A
word
2033
CT location for 1 or 2 CT metering
word
2034
VT location for 1 or 2 VT metering
word
2035
VT connection type
word
2047
Peak current demand over last year
A
single
2049
Active load timer setpoint
A
single
2125
Alarm / energy LED mode
word
2129
Energy channel
word
2131
Pulse weight
kWh, kVAh, kVAh
dword
2133
Energy channel
word
2135
Pulse weight
kWh, kVAh, kVAh
dword
2137
Energy channel
word
This is not the complete map: 50 of 310 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric (PM5100, PM5300) - MODBUS Measurements
Registers in the map: 697 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, single, utf8(40), word.
MODBUS offset
Description
Units
Data type
Scale
49
Meter model
utf8(40)
29
Meter name
utf8(40)
69
Manufacturer
utf8(40)
89
Product ID number
word
129
Serial number
dword
1827
Number of metering system restarts
word
1828
Number of control power failures
word
1833
Duration of last control power failure
s
dword
1835
Cause of last meter reset
word
1836
Year
year
word
1837
Month
month
word
1838
Day
days
word
1839
Hour
h
word
1840
Minute
min
word
1841
Second
s
word
1842
Millisecond
ms
word
1843
Day of week
word
1844
Year
word
1845
Month and day
word
1846
Hour and minute
word
1847
Milliseconds
word
1920
Revenue security status
word
1999
Conditional energy control status
word
2001
Active load timer
s
dword
2003
Meter operation timer
s
dword
2005
Cycle count
dword
2007
Heartbeat LED control
word
2013
Number of phases
word
2014
Number of wires
word
2015
Power system configuration
word
2016
Nominal frequency
Hz
word
2017
Nominal voltage
V
single
2019
Nominal current
A
single
2021
Nominal power factor
dword
2023
Normal phase rotation
word
2024
Number VTs
word
2025
VT primary
V
single
2027
VT secondary
V
word
2028
Number CTs
word
2029
CT primary
A
word
2030
CT secondary
A
word
2033
CT location for 1 or 2 CT metering
word
2034
VT location for 1 or 2 VT metering
word
2035
VT connection type
word
2047
Peak current demand over last year
A
single
2049
Active load timer setpoint
A
single
2125
Alarm / energy LED mode
word
2129
Energy channel
word
2130
Digital output association
word
2131
Pulse weight
kWh, kVAh, kVAh
dword
This is not the complete map: 50 of 697 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 1867 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (input registers). byte order big-endian. data types: dword, int64, single, utf8(10), utf8(40), word.
MODBUS offset
Description
Units
Data type
Scale
49
Meter model
utf8(40)
1636
Present firmware version (DLF format) X.Y.T
word
1641
Previous firmware version (DLF format) X.Y.T
word
1668
Present firmware version (DLF format) X.Y.T
word
1700
Present firmware version (DLF format) X.Y.T
word
2284
Present firmware version (DLF format) X.Y.T
word
2289
Previous firmware version (DLF format) X.Y.T
word
29
Meter name
utf8(40)
69
Manufacturer
utf8(40)
89
Product ID number
word
129
Serial number
dword
135
Hardware revision
utf8(10)
1637
X major
word
1638
Y minor
word
1639
Z quality
word
1642
X major
word
1643
Y minor
word
1644
Z quality
word
1827
Number of metering system restarts
word
1828
Number of control power failures
word
1833
Duration of last control power failure
s
dword
1835
Cause of last meter reset
word
1836
Year
year
word
1837
Month
month
word
1838
Day
days
word
1839
Hour
h
word
1840
Minute
min
word
1841
Second
s
word
1842
Millisecond
ms
word
1844
Year
word
1845
Month and day
word
1846
Hour and minute
word
1847
Milliseconds
word
1919
Revenue security switch status
word
1920
Revenue security status
word
2001
Active load timer
s
dword
2003
Meter operation timer
s
dword
2013
Number of phases
word
2014
Number of wires
word
2015
Power system configuration
word
2016
Nominal frequency
Hz
word
2017
Nominal voltage
V
single
2019
Nominal current
A
single
2023
Normal phase rotation
word
2024
Number VTs
word
2025
VT primary
V
single
2027
VT secondary
V
word
2028
Number CTs
word
2029
CT primary
A
word
2030
CT secondary
A
word
This is not the complete map: 50 of 1867 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
meter automatically compensates for the Modbus offset of one
Address prefixes
30,000 or 40,000 can be used, e.g. Current phase A = 31,003 or 41,003
Registers in the map: 192 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: smallint.
MODBUS offset
Description
Units
Data type
Scale
2019
Scale Factor A
smallint
2022
Scale Factor D
smallint
2023
Scale Factor E
smallint
999
Update interval
smallint
1000
Frequency
Hz
smallint
1002
Current, phase A
A
smallint
×10SCALE_A
1003
Current, phase B
A
smallint
×10SCALE_A
1004
Current, phase C
A
smallint
×10SCALE_A
1005
Current, calculated neutral
A
smallint
×10SCALE_A
1009
Current unbalance, phase A
%
smallint
×0.1
1010
Current unbalance, phase B
%
smallint
×0.1
1011
Current unbalance, phase C
%
smallint
×0.1
1012
Current unbalance, worst
%
smallint
×0.1
1013
Voltage, phase A to B
V
smallint
×10SCALE_D
1014
Voltage, phase B to C
V
smallint
×10SCALE_D
1015
Voltage, phase C to A
V
smallint
×10SCALE_D
1017
Voltage, phase A to neutral
V
smallint
×10SCALE_D
1018
Voltage, phase B to neutral
V
smallint
×10SCALE_D
1019
Voltage, phase C to neutral
V
smallint
×10SCALE_D
1021
Voltage unbalance, phase A B
%
smallint
×0.1
1022
Voltage unbalance, phase B C
%
smallint
×0.1
1023
Voltage unbalance, phase C A
%
smallint
×0.1
1024
Voltage unbalance, L L worst
%
smallint
×0.1
1025
Voltage unbalance, phase A
%
smallint
×0.1
1026
Voltage unbalance, phase B
%
smallint
×0.1
1027
Voltage unbalance, phase C
%
smallint
×0.1
1028
Voltage unbalance, L N worst
%
smallint
×0.1
1030
True power factor, phase A
smallint
×0.001
1031
True power factor, phase B
smallint
×0.001
1032
True power factor, phase C
smallint
×0.001
1033
True power factor, 3 phase total
smallint
×0.001
1038
Real power, phase A
kW
smallint
×10SCALE_E
1039
Real power, phase B
kW
smallint
×10SCALE_E
1040
Real power, phase C
kW
smallint
×10SCALE_E
1041
Real power, 3 phase total
kW
smallint
×10SCALE_E
1042
Reactive power, phase A
kvar
smallint
×10SCALE_E
1043
Reactive power, phase B
kvar
smallint
×10SCALE_E
1044
Reactive power, phase C
kvar
smallint
×10SCALE_E
1045
Reactive power, 3 phase total
kvar
smallint
×10SCALE_E
1046
Apparent power, phase A
kVA
smallint
×10SCALE_E
1047
Apparent power, phase B
kVA
smallint
×10SCALE_E
1048
Apparent power, phase C
kVA
smallint
×10SCALE_E
1049
Apparent power, 3 phase total
kVA
smallint
×10SCALE_E
1050
Thd/thd A current
smallint
×0.1
1051
Thd/thd B current
smallint
×0.1
1052
Thd/thd C current
smallint
×0.1
1054
Thd/thd A voltage
smallint
×0.1
1055
Thd/thd B voltage
smallint
×0.1
1056
Thd/thd C voltage
smallint
×0.1
1077
A current fundamental rms magnitude
A
smallint
×10SCALE_A
This is not the complete map: 50 of 192 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 97 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.
MODBUS offset
Description
Units
Data type
Scale
1000
Real energy, total
kWh
single
1002
Apparent energy, total
kVAh
single
1004
Reactive energy, total
kvarh
single
1006
Real power, total
kW
single
1008
Apparent power, total
kVA
single
1010
Reactive power, total
kvar
single
1012
Power factor, total
single
1014
Voltage, L-L, 3P average
V
single
1016
Voltage, L-N, 3P average
V
single
1018
Current, 3P average
A
single
1020
Frequency
Hz
single
1034
Current, A
A
single
1036
Current, B
A
single
1038
Current, C
A
single
1040
Current, N
A
single
1054
Voltage, A-B
V
single
1056
Voltage, B-C
V
single
1058
Voltage, C-A
V
single
1060
Voltage, A-N
V
single
1062
Voltage, B-N
V
single
1064
Voltage, C-N
V
single
1066
Real power, A
kW
single
1068
Real power, B
kW
single
1070
Real power, C
kW
single
1072
Apparent power, A
kVA
single
1074
Apparent power, B
kVA
single
1076
Apparent power, C
kVA
single
1078
Reactive power, A
kvar
single
1080
Reactive power, B
kvar
single
1082
Reactive power, C
kvar
single
1084
Current, A, THD
%
single
1086
Current, B, THD
%
single
1088
Current, C, THD
%
single
1092
Voltage, A-N, THD
%
single
1094
Voltage, B-N, THD
%
single
1096
Voltage, C-N, THD
%
single
1098
Voltage, A-B, THD
%
single
1100
Voltage, B-C, THD
%
single
1102
Voltage, C-A, THD
%
single
1022
Real power, total demand present
kW
single
1024
Apparent power, total demand present
kVA
single
1026
Reactive power, total demand present
kvar
single
1028
Real power, total demand peak
kW
single
1030
Apparent power, total demand peak
kVA
single
1032
Reactive power, total demand peak
kvar
single
1042
Current, A, demand present
A
single
1044
Current, B, demand present
A
single
1046
Current, C, demand present
A
single
1048
Current, A, demand peak
A
single
1050
Current, B, demand peak
A
single
This is not the complete map: 50 of 97 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Modbus TCP and Modbus RTU over TCP can be enabled in the Ethernet settings
Registers in the map: 2871 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, single, utf8(12), utf8(40), word.
MODBUS offset
Description
Units
Data type
Scale
50
Meter model
utf8(40)
1717
Current version
utf8(12)
30
Meter name
utf8(40)
1837
Year
year
word
1838
Month
month
word
1839
Day
days
word
1840
Hour
h
word
1841
Minute
min
word
1842
Second
s
word
1844
Day of week
word
2400
Digital input status validity base unit
word
2402
Digital output status validity base unit
word
2420
Setpoint status validity
word
2550
Digital input status validity option slot A
word
2552
Digital input status validity option slot B
word
2554
Digital input status validity option slot C
word
2556
Digital input status validity option slot D
word
2566
Digital output status validity option slot A
word
2568
Digital output status validity option slot B
word
2570
Digital output status validity option slot C
word
2572
Digital output status validity option slot D
word
2700
Active energy delivered (into load)
kWh
single
2702
Active energy received (out of load)
kWh
single
2704
Active energy delivered + received
kWh
single
2706
Active energy delivered received
kWh
single
2708
Reactive energy delivered
kvarh
single
2710
Reactive energy received
kvarh
single
2712
Reactive energy delivered + received
kvarh
single
2714
Reactive energy delivered received
kvarh
single
2716
Apparent energy delivered
kVAh
single
2718
Apparent energy received
kVAh
single
2720
Apparent energy delivered + received
kVAh
single
2722
Apparent energy delivered received
kVAh
single
2724
Active energy in Q1
kWh
single
2726
Active energy in Q2
kWh
single
2728
Active energy in Q3
kWh
single
2730
Active energy in Q4
kWh
single
2732
Reactive energy in Q1
kvarh
single
2734
Reactive energy in Q2
kvarh
single
2736
Reactive energy in Q3
kvarh
single
2738
Reactive energy in Q4
kvarh
single
2740
Apparent energy in Q1
kVAh
single
2742
Apparent energy in Q2
kVAh
single
2744
Apparent energy in Q3
kVAh
single
2746
Apparent energy in Q4
kVAh
single
2748
Conditional active energy delivered (into load)
kWh
single
2750
Conditional active energy received (out of load)
kWh
single
2754
Active energy delivered received, conditional
kWh
single
2756
Conditional reactive energy in (delivered)
kvarh
single
2758
Conditional reactive energy out (received)
kvarh
single
This is not the complete map: 50 of 2871 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 953 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, string(16).
MODBUS offset
Description
Units
Data type
Scale
3059
Present FW module
integer
3086
Model ID
integer
628
Ethernet physical connection
integer
631
Wire mode
integer
632
Port protocol mode
integer
633
PM8ECC reset counter
integer
634
Frame type
integer
1100
Current, phase A
A/Scale
integer
1101
Current, phase B
A/Scale
integer
1102
Current, phase C
A/Scale
integer
1103
Current, neutral
A/Scale
integer
1104
Current, ground
A/Scale
integer
1105
Current, 3-phase average
A/Scale
integer
1107
Current, unbalance, phase A
%
integer
×0.1
1108
Current, unbalance, phase B
%
integer
×0.1
1109
Current, unbalance, phase C
%
integer
×0.1
1110
Current, unbalance, max
%
integer
×0.1
1120
Voltage, A-B
V/Scale
integer
1121
Voltage, B-C
V/Scale
integer
1122
Voltage, C-A
V/Scale
integer
1123
Voltage, L-L average
V/Scale
integer
1124
Voltage, A-N
V/Scale
integer
1125
Voltage, B-N
V/Scale
integer
1126
Voltage, C-N
V/Scale
integer
1127
Voltage, N-R
V/Scale
integer
1128
Voltage, L-N average
V/Scale
integer
1129
Voltage, unbalance, A-B
%
integer
×0.1
1130
Voltage, unbalance, B-C
%
integer
×0.1
1131
Voltage, unbalance, C-A
%
integer
×0.1
1132
Voltage, unbalance, max L-L
%
integer
×0.1
1133
Voltage, unbalance, A-N
%
integer
×0.1
1134
Voltage, unbalance, B-N
%
integer
×0.1
1135
Voltage, unbalance, C-N
%
integer
×0.1
1136
Voltage, unbalance, max L-N
%
integer
×0.1
1140
Real power, phase A
kW/Scale
integer
1141
Real power, phase B
kW/Scale
integer
1142
Real power, phase C
kW/Scale
integer
1143
Real power, total
kW/Scale
integer
1144
Reactive power, phase A
kvar/Scale
integer
1145
Reactive power, phase B
kvar/Scale
integer
1146
Reactive power, phase C
kvar/Scale
integer
1147
Reactive power, total
kvar/Scale
integer
1148
Apparent power, phase A
kVA/Scale
integer
1149
Apparent power, phase B
kVA/Scale
integer
1150
Apparent power, phase C
kVA/Scale
integer
1151
Apparent power, total
kVA/Scale
integer
1160
True power factor, phase A
integer
×0.001
1161
True power factor, phase B
integer
×0.001
1162
True power factor, phase C
integer
×0.001
1163
True power factor, total
integer
×0.001
This is not the complete map: 50 of 953 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 113 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
275
Phase current I1
word
×0.1
276
Phase current I2
word
×0.1
277
Phase current I3
word
×0.1
278
Residual current i0 sum
word
×0.1
279
Residual current measured
word
×0.1
280
Average phase current IM1
word
×0.1
281
Average phase current IM2
word
×0.1
282
Average phase current IM3
word
×0.1
283
Peak demand phase current IM1
word
×0.1
284
Peak demand phase current IM2
word
×0.1
285
Peak demand phase current IM3
word
×0.1
286
Phase-to-phase voltage U21
word
287
Phase-to-phase voltage U32
word
288
Phase-to-phase voltage U13
word
289
Phase-to-neutral voltage V1
word
290
Phase-to-neutral voltage V2
word
291
Phase-to-neutral voltage V3
word
292
Residual voltage v0
word
293
Positive sequence voltage vd
word
294
Negative sequence voltage vi
word
295
Frequency
word
×0.01
296
Active power P
smallint
297
Reactive power Q
smallint
298
Apparent power S
smallint
299
Peak demand active power pm
smallint
300
Peak demand reactive power qm
smallint
301
Power factor cos
smallint
×0.01
302
Positive active energy ea+
dword
×100
304
Negative active energy ea-
dword
×100
306
Positive reactive energy er+
dword
×100
308
Negative reactive energy er-
dword
×100
310
Phase current I1
word
311
Phase current I2
word
312
Phase current I3
word
313
Residual current i0 sum
word
314
Residual current measured
word
315
Average phase current IM1
word
316
Average phase current IM2
word
317
Average phase current IM3
word
318
Peak demand phase current IM1
word
319
Peak demand phase current IM2
word
320
Peak demand phase current IM3
word
321
Phase-to-phase voltage U21
word
×10
322
Phase-to-phase voltage U32
word
×10
323
Phase-to-phase voltage U13
word
×10
324
Phase-to-neutral voltage V1
word
×10
325
Phase-to-neutral voltage V2
word
×10
326
Phase-to-neutral voltage V3
word
×10
327
Residual voltage v0
word
×10
328
Positive sequence voltage vd
word
×10
This is not the complete map: 50 of 113 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
at least two requests are required to read the zone in full
Registers in the map: 104 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
512
Phase current I1
dword
×0.1
514
Phase current I2
dword
×0.1
516
Phase current I3
dword
×0.1
518
Residual current i0
dword
×0.1
520
Residual current i0
dword
×0.1
522
Demand current IM1
dword
×0.1
524
Demand current IM2
dword
×0.1
526
Demand current IM3
dword
×0.1
528
Peak demand current IM1
dword
×0.1
530
Peak demand current IM2
dword
×0.1
532
Peak demand current IM3
dword
×0.1
534
Phase-to-phase voltage U21
dword
536
Phase-to-phase voltage U32
dword
538
Phase-to-phase voltage U13
dword
540
Phase-to-neutral voltage V1
dword
542
Phase-to-neutral voltage V2
dword
544
Phase-to-neutral voltage V3
dword
546
Residual voltage v0
dword
548
Positive sequence voltage vd
dword
550
Negative-sequence voltage vi
dword
552
Frequency f
Hz
dword
×0.01
554
Active power P
kW
integer
×0.1
560
Power factor cos
integer
×0.01
562
Peak demand active power PM
kW
integer
×0.1
564
Peak demand reactive power QM
kvar
integer
×0.1
566
Active power P phase 1
kW
integer
×0.1
568
Active power P phase 2
kW
integer
×0.1
570
Active power P phase 3
kW
integer
×0.1
572
Reactive power Q phase 1
kvar
integer
×0.1
574
Reactive power Q phase 2
kvar
integer
×0.1
576
Reactive power Q phase 3
kvar
integer
×0.1
578
Apparent power S phase 1
kVA
integer
×0.1
580
Apparent power S phase 2
kVA
integer
×0.1
582
Apparent power S phase 3
kVA
integer
×0.1
584
Positive active energy ea+
kW
dword
×100
586
Negative active energy ea-
kW
dword
×100
588
Positive reactive energy er+
kvar
dword
×100
590
Negative reactive energy er-
kvar
dword
×100
592
Ext. positive active energy ea+
kW
dword
×100
594
Ext. negative active energy ea-
kW
dword
×100
596
Ext. positive reactive energy er+
kvar
dword
×100
598
Ext. negative reactive energy er-
kvar
dword
×100
600
Neutral-point voltage vnt
dword
616
Number of operations
dword
618
Tripping current phase 1 itrip1
dword
×0.1
620
Tripping current phase 2 itrip2
dword
×0.1
622
Tripping current phase 3 itrip3
dword
×0.1
624
Tripping current calculated i0 itrip0
dword
×0.1
636
Number of operations
dword
650
Impedance Zd
MOhm
dword
This is not the complete map: 50 of 104 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
at least two requests are required to read the zone in full
Registers in the map: 141 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
512
Phase current I1
dword
×0.1
514
Phase current I2
dword
×0.1
516
Phase current I3
dword
×0.1
518
Residual current i0
dword
×0.1
520
Residual current i0
dword
×0.1
522
Demand current Im1
dword
×0.1
524
Demand current Im2
dword
×0.1
526
Demand current Im3
dword
×0.1
528
Peak demand current IM1
dword
×0.1
530
Peak demand current IM2
dword
×0.1
532
Peak demand current IM3
dword
×0.1
534
Phase to phase voltage U21
dword
536
Phase to phase voltage U32
dword
538
Phase to phase voltage U13
dword
540
Phase to neutral voltage V1
dword
542
Phase to neutral voltage V2
dword
544
Phase to neutral voltage V3
dword
546
Residual voltage v0
dword
548
Positive sequence voltage vd
dword
550
Negative sequence voltage vi
dword
552
Frequency f
Hz
dword
×0.01
554
Active power P
kW
integer
×0.1
556
Reactive power Q
kvar
integer
×0.1
558
Apparent power S
kVA
integer
×0.1
560
Power factor cos
integer
×0.01
562
Peak demand active power pm
kW
integer
×0.1
564
Peak demand reactive power qm
kvar
integer
×0.1
566
Active power P phase 1
kW
integer
×0.1
568
Active power P phase 2
kW
integer
×0.1
570
Active power P phase 3
kW
integer
×0.1
572
Reactive power Q phase 1
kvar
integer
×0.1
574
Reactive power Q phase 2
kvar
integer
×0.1
576
Reactive power Q phase 3
kvar
integer
×0.1
578
Apparent power S phase 1
kVA
integer
×0.1
580
Apparent power S phase 2
kVA
integer
×0.1
582
Apparent power S phase 3
kVA
integer
×0.1
584
Positive active energy ea+
kW
dword
×100
586
Negative active energy ea
kW
dword
×100
588
Positive reactive energy er+
kvar
dword
×100
590
Negative reactive energy er
kvar
dword
×100
592
Ext. positive active energy ea+
kW
dword
×100
594
Ext. negative active energy ea
kW
dword
×100
596
Ext. positive reactive energy ea+
kvar
dword
×100
598
Ext. negative reactive energy ea
kvar
dword
×100
600
Neutral point voltage vnt
dword
602
H3 neutral point voltage v3nt
dword
604
H3 residual voltage v3r
dword
606
Phase current i-1
dword
×0.1
608
Phase current i-2
dword
×0.1
610
Phase current i-3
dword
×0.1
This is not the complete map: 50 of 141 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 71 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: word.
MODBUS offset
Description
Units
Data type
Scale
0
Alarm/Status register
word
1
Alarm/Status register
word
2
Alarm/Status register
word
3
Alarm/Status register
word
4
Alarm/Status register
word
5
Alarm/Status register
word
6
Line quality 00FF=acceptable utility line quality 0000=unacceptable utility line quality
word
7
% battery capacity remaining battery capacity as a percent of the fully charged condition (0-100)
%
word
8
Runtime remaining
min
word
9
Battery voltage present UPS battery voltage
V
word
10
UPS internal temperature (0-209) 00XX=valid reading FFXX=invalid reading XX=sensor reading
word
11
Amps drawn by load
A
word
12
Number of battery packs with bad batteries
each
word
13
Number of battery packs
each
word
14
UPS output load as a percentage of full rated load in watts
%
word
15
Maximum input voltage since last reading
V
word
16
Minimum input voltage since last reading
V
word
17
Nominal battery voltage
V
word
18
Actual battery voltage
V
word
19
Utility input frequency
Hz
word
20
Phase A utility input voltage
V
word
21
Phase A utility input current
A
word
22
Phase A bypass input voltage
V
word
23
Phase A percent of maximum output VA @ N + 0
%
word
24
Phase A percent of maximum output VA @ N + x
%
word
25
Phase A output
kVA
word
26
Phase A output voltage
V
word
27
Phase A output current
A
word
28
Phase A peak output current
A
word
29
Phase B utility input voltage
V
word
30
Phase B utility input current
A
word
31
Phase B bypass input voltage
V
word
32
Phase B percent of maximum output VA @ N + 0
%
word
33
Phase B percent of maximum output VA @ N + x
%
word
34
Phase B output
kVA
word
35
Phase B output voltage
V
word
36
Phase B output current
A
word
37
Phase B peak output current
A
word
38
Phase C utility input voltage
V
word
39
Phase C utility input current
A
word
40
Phase C bypass input voltage
V
word
41
Phase C percent of maximum output VA @ N + 0
%
word
42
Phase C percent of maximum output VA @ N + x
%
word
43
Phase C output
kVA
word
44
Phase C output voltage
V
word
45
Phase C output current
A
word
46
Phase C peak output current
A
word
47
Environmental monitoring card temperature reading (Sensor 1)
Environmental monitoring card temperature reading (Sensor 2)
word
This is not the complete map: 50 of 71 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric (XW Hybrid Inverter) - MODBUS Registers Map
Registers in the map: 147 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
40070
AC Current
A
word
×10A_SF
40071
Phase A Current
A
word
×10A_SF
40072
Phase B Current
A
word
×10A_SF
40073
Phase C Current
A
word
×10A_SF
40074
Scale factor [A_SF]
smallint
40075
Phase Voltage AB
V
word
×10V_SF
40076
Phase Voltage BC
V
word
×10V_SF
40077
Phase Voltage CA
V
word
×10V_SF
40078
Phase Voltage AN
V
word
×10V_SF
40079
Phase Voltage BN
V
word
×10V_SF
40080
Phase Voltage CN
V
word
×10V_SF
40081
Scale factor [V_SF]
smallint
40082
AC Power
W
smallint
×10W_SF
40083
Scale factor [W_SF]
smallint
40084
Line Frequency
Hz
word
×10HZ_SF
40085
Scale factor [HZ_SF]
smallint
40086
AC Apparent Power
VA
smallint
×10VA_SF
40087
Scale factor [VA_SF]
smallint
40088
AC Reactive Power
var
smallint
×10VAR_SF
40089
Scale factor [VAR_SF]
smallint
40090
AC Power Factor
%
smallint
×10PF_SF
40091
Scale factor [PF_SF]
smallint
40092
AC Energy
Wh
dword
×10WH_SF
40094
Scale factor [WH_SF]
smallint
40095
DC Current
A
word
×10DCA_SF
40096
Scale factor [DCA_SF]
smallint
40097
DC Voltage
V
word
×10DCV_SF
40098
Scale factor [DCV_SF]
smallint
40099
DC Power
W
smallint
×10DCW_SF
40100
Scale factor [DCW_SF]
smallint
40101
Cabinet Temperature
deg C
smallint
×10TMP_SF
40102
Heat Sink Temperature
deg C
smallint
×10TMP_SF
40103
Transformer Temperature
deg C
smallint
×10TMP_SF
40104
Other Temperature
deg C
smallint
×10TMP_SF
40105
Scale factor [TMP_SF]
smallint
40106
Enumerated value. Operating state
word
40107
Vendor specific operating state code
word
40108
Bitmask value. Event fields
dword
40110
Reserved for future use
dword
40112
Vendor defined events
dword
40114
Vendor defined events
dword
40116
Vendor defined events
dword
40118
Vendor defined events
dword
40122
Type of DER device. Default value is 4 to indicate PV device.
word
40123
Continuous power output capability of the inverter.
W
word
×10WRTG_SF
40124
Scale factor
smallint
40125
Continuous capability of the inverter.
VA
word
×10VARTG_SF
40126
Scale factor
smallint
40127
Continuous VAR capability of the inverter in Q1.
var
smallint
×10VARRTG_SF
40128
Continuous VAR capability of the inverter in Q2.
var
smallint
×10VARRTG_SF
This is not the complete map: 50 of 147 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.
Your current browser does not support the Web Serial API required to access local COM ports. Please use a Chromium-based browser like Google Chrome, Microsoft Edge, or Opera.