MODBUS offset | Description | Units | Data type |
1 | Alarm/Status register | | word |
2 | Alarm/Status register | | word |
3 | Alarm/Status register | | word |
4 | Alarm/Status register | | word |
5 | Alarm/Status register | | word |
6 | Line quality 00FF=acceptable utility line quality 0000=unacceptable utility line quality | | word |
7 | % battery capacity remaining battery capacity as a percent of the fully charged condition (0-100) | % | word |
8 | Runtime remaining | minutes | word |
9 | Battery voltage present UPS battery voltage | V | word |
10 | UPS internal temperature (0-209) 00XX=valid reading FFXX=invalid reading XX=sensor reading | DC | word |
11 | Amps drawn by load | A | word |
12 | Number of battery packs with bad batteries | each | word |
13 | Number of battery packs | each | word |
14 | UPS output load as a percentage of full rated load in watts | % | word |
15 | Maximum input voltage since last reading | V | word |
16 | Minimum input voltage since last reading | V | word |
17 | Nominal battery voltage | V | word |
18 | Actual battery voltage | V | word |
19 | Utility input frequency | Hz | word |
20 | Phase A utility input voltage | V | word |
21 | Phase A utility input current | A | word |
22 | Phase A bypass input voltage | V | word |
23 | Phase A percent of maximum output VA @ N + 0 | % | word |
24 | Phase A percent of maximum output VA @ N + x | % | word |
25 | Phase A output | kVA | word |
26 | Phase A output voltage | V | word |
27 | Phase A output current | A | word |
28 | Phase A peak output current | A | word |
29 | Phase B utility input voltage | V | word |
30 | Phase B utility input current | A | word |
31 | Phase B bypass input voltage | V | word |
32 | Phase B percent of maximum output VA @ N + 0 | % | word |
33 | Phase B percent of maximum output VA @ N + x | % | word |
34 | Phase B output | kVA | word |
35 | Phase B output voltage | V | word |
36 | Phase B output current | A | word |
37 | Phase B peak output current | A | word |
38 | Phase C utility input voltage | V | word |
39 | Phase C utility input current | A | word |
40 | Phase C bypass input voltage | V | word |
41 | Phase C percent of maximum output VA @ N + 0 | % | word |
42 | Phase C percent of maximum output VA @ N + x | % | word |
43 | Phase C output | kVA | word |
44 | Phase C output voltage | V | word |
45 | Phase C output current | A | word |
46 | Phase C peak output current | A | word |
47 | Environmental monitoring card temperature reading (Sensor 1) | DC | word |
48 | Environmental monitoring card humidity reading (Sensor 1) | %RH | word |
49 | Environmental monitoring card temperature reading (Sensor 2) | DC | word |
50 | Environmental monitoring card humidity reading (Sensor 2) | %RH | word |
There are more MODBUS items for this device. Please, download the program. |