Press the [Parameters] button for parameters settings
Press the [PAGE DOWN] button and select the 'Settings 2' submode
Set the 'MODE SELECT' switch to 'MDI'
Set the 'NO PWE' parameter to 1 and press the 'Input' button. After changing parameters below, change this value to 0 again
Select the 'Settings 2' submode
Set I/O = 1
With help of 'PAGE DOWN' and 'PAGE UP' buttons change bits in the following parameters. Please, don't change bits that didn't print in the table below
#002 (stop bit and data format)
bit 0
0 (1 stop bit)
bit 2
0 (RS232)
bit 3
1 (ASCII)
#0552 (baud rate). Set this parameter = 9
Baud
Parameter value
2400
9
4800
10
9600
11
19200
12
#0038 (IO device)
bit 1
0
bit 2
1
bit 4
0
bit 5
1
bit 6
0
bit 7
1
#0051 (Parity)
bit 1
1 (Yes)
#0055 (Additional parameters)
bit 0
1 (ASCII)
bit 1
0 (CR)
bit 2
0 (Protocol A)
bit 3
0 (RS232)
Set the following parameters on the PC
Serial port tab
Machine name
Fanuc O-T
Serial port
COM2 (or any free COM port)
Baud
2400
Data bits
7
Parity
Even
Stop bits
2
Data flow control tab
Use DTR
False
Use RTS
False
Require DSR
False
Require CTS
True
Set RTS
False
Set DTR
False
Software flowcontrol
None
Xon char
#11
Xoff char
#13
Data exchange format tab
Format mode
Uniform
Format parameters
Program start: % Program end: % Line start: Line end: #0A#0D#0D Skip lines: Ignore characters: No characters for remove Remove blank lines: No Program name prefix: : Program starting characters in the file: No Program ending characters in the file: No
Press the [Parameters] button for parameters settings
Press the [PAGE DOWN] button and select the 'Settings 2' submode
Set the 'MODE SELECT' switch to 'MDI'
Set the 'NO PWE' parameter to 1 and press the 'Input' button. After changing parameters below, change this value to 0 again
Select the 'Settings 2' submode
Set I/O = 1
With help of 'PAGE DOWN' and 'PAGE UP' buttons change bits in the following parameters. Please, don't change bits that didn't print in the table below
#002 (stop bit and data format)
bit 0
0 (1 stop bit)
bit 2
0 (RS232)
bit 3
1 (ASCII)
#0552 (baud rate). Set this parameter = 9
Baud
Parameter value
2400
9
4800
10
9600
11
19200
12
#0038 (IO device)
bit 1
0
bit 2
1
bit 4
0
bit 5
1
bit 6
0
bit 7
1
#0051 (Parity)
bit 1
1 (Yes)
#0055 (Additional parameters)
bit 0
1 (ASCII)
bit 1
0 (CR)
bit 2
0 (Protocol A)
bit 3
0 (RS232)
Set the following parameters on the PC
Serial port tab
Machine name
Fanuc O-TC
Serial port
COM2 (or any free COM port)
Baud
2400
Data bits
7
Parity
Even
Stop bits
2
Data flow control tab
Use DTR
False
Use RTS
False
Require DSR
False
Require CTS
True
Set RTS
False
Set DTR
False
Software flowcontrol
None
Xon char
#11
Xoff char
#13
Data exchange format tab
Format mode
Uniform
Format parameters
Program start: % Program end: % Line start: Line end: #0A#0D#0D Skip lines: Ignore characters: No characters for remove Remove blank lines: No Program name prefix: : Program starting characters in the file: No Program ending characters in the file: No