ABB (M2M,DMTME) data logging. MODBUS registers map.


This data is being extracted with help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
40963 phase system voltageVoltdword
4098Phase voltage L1 NVoltdword
4100Phase voltage L2 NVoltdword
4102Phase voltage L3 NVoltdword
4104Line voltage L1 2Voltdword
4106Line voltage L2 3Voltdword
4108Line voltage L3 1Voltdword
41103 phase system currentmAdword
4112Line current L1mAdword
4114Line current L2mAdword
4116Line current L3mAdword
41183 phase sys. Power factor integer
4120Power factor L1 integer
4122Power factor L2 integer
4124Power factor L3 integer
41263 phase system cos integer
4128Phase cos p1 integer
4130Phase cos 2 integer
4132Phase cos 3 integer
41343 phase s. Apparent powerVAdword
4136Apparent power L1VAdword
4138Apparent power L2VAdword
4140Apparent power L3VAword
41423 phase sys. Active powerWattinteger
4144Active power L1Wattinteger
4146Active power L2Wattinteger
4148Active power L3Wattinteger
41503 phase s. Reactive powerVArinteger
4152Reactive power L1VArinteger
4154Reactive power L2VArinteger
4156Reactive power L3VArinteger
41583 phase sys. Active energyWhdword
41603 phase s. Reactive energyVArhdword
4166FrequencymHzdword
4192Max line current L1mAdword
4194Max line current L2mAdword
4196Max line current L3mAword
4198Max 3 phase sys. Active powerWattinteger
4200Max 3 phase s. Apparent powerVAword
42083 phase sys. Active power 15 averWattinteger
4512Current transform ratio (ct) dword
4514Voltage transform ratio (vt) dword
4516Pulse energy weight dword