ABB DMTME multimeters DMTME MODBUS registers: read online

Connect ABB DMTME multimeters to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous ABB DMTME multimeters data logger and record.

Do you not know the meter address? Scan the device address online

ABB DMTME multimeters - MODBUS Maps

Registers in the map: 30. function 3 (holding registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
4098Phase voltage l1-nVdword 
4100Phase voltage l2-nVdword 
4102Phase voltage l3-nVdword 
4104Line voltage l1-l2Vdword 
4106Line voltage l2-l3Vdword 
4108Line voltage l1-l3Vdword 
4112Line current l1Adword×0.001
4114Line current l2Adword×0.001
4116Line current l3Adword×0.001
41183-phase sys. power factor integer×0.001
4120Power factor l1 integer×0.001
4122Power factor l2 integer×0.001
4124Power factor l3 integer×0.001
41343-phase sys. apparent powerVAdword 
4136Apparent power l1VAdword 
4138Apparent power l2VAdword 
4140Apparent power l3VAdword 
41423-phase sys. active powerWdword 
4144Active power l1Wdword 
4146Active power l2Wdword 
4148Active power l3Wdword 
41503-phase reactive powervardword 
4152Reactive power l1vardword 
4154Reactive power l2vardword 
4156Reactive power l3vardword 
41583-phase sys. active energyWhdword×0.01
41603-phase sys. reactive energyvarhdword×0.01
4166FrequencymHzdword 
4512Current transformer ratio dword 
4514Voltage transformer ratio dword 