Registers in the map: 30. function 3 (holding registers). byte order big-endian. data types: dword, integer.
| MODBUS offset | Description | Units | Data type | Scale |
|---|---|---|---|---|
| 4098 | Phase voltage l1-n | V | dword | |
| 4100 | Phase voltage l2-n | V | dword | |
| 4102 | Phase voltage l3-n | V | dword | |
| 4104 | Line voltage l1-l2 | V | dword | |
| 4106 | Line voltage l2-l3 | V | dword | |
| 4108 | Line voltage l1-l3 | V | dword | |
| 4112 | Line current l1 | A | dword | ×0.001 |
| 4114 | Line current l2 | A | dword | ×0.001 |
| 4116 | Line current l3 | A | dword | ×0.001 |
| 4118 | 3-phase sys. power factor | integer | ×0.001 | |
| 4120 | Power factor l1 | integer | ×0.001 | |
| 4122 | Power factor l2 | integer | ×0.001 | |
| 4124 | Power factor l3 | integer | ×0.001 | |
| 4134 | 3-phase sys. apparent power | VA | dword | |
| 4136 | Apparent power l1 | VA | dword | |
| 4138 | Apparent power l2 | VA | dword | |
| 4140 | Apparent power l3 | VA | dword | |
| 4142 | 3-phase sys. active power | W | dword | |
| 4144 | Active power l1 | W | dword | |
| 4146 | Active power l2 | W | dword | |
| 4148 | Active power l3 | W | dword | |
| 4150 | 3-phase reactive power | var | dword | |
| 4152 | Reactive power l1 | var | dword | |
| 4154 | Reactive power l2 | var | dword | |
| 4156 | Reactive power l3 | var | dword | |
| 4158 | 3-phase sys. active energy | Wh | dword | ×0.01 |
| 4160 | 3-phase sys. reactive energy | varh | dword | ×0.01 |
| 4166 | Frequency | mHz | dword | |
| 4512 | Current transformer ratio | dword | ||
| 4514 | Voltage transformer ratio | dword |