ABB (UNO DM PLUS) data logging. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
40070 | AC Current | A | word |
40071 | Phase A Current | A | word |
40072 | Phase B Current | A | word |
40073 | Phase C Current | A | word |
40074 | Scale factor [A_SF] | | smallint |
40075 | Phase Voltage AB | V | word |
40076 | Phase Voltage BC | V | word |
40077 | Phase Voltage CA | V | word |
40078 | Phase Voltage AN | V | word |
40079 | Phase Voltage BN | V | word |
40080 | Phase Voltage CN | V | word |
40081 | Scale factor [V_SF] | | smallint |
40082 | AC Power | W | smallint |
40083 | Scale factor [W_SF] | | smallint |
40084 | Line Frequency | Hz | word |
40085 | Scale factor [HZ_SF] | | smallint |
40086 | AC Apparent Power | VA | smallint |
40087 | Scale factor [VA_SF] | | smallint |
40088 | AC Reactive Power | var | smallint |
40089 | Scale factor [VAR_SF] | | smallint |
40090 | AC Power Factor | Pct | smallint |
40091 | Scale factor [PF_SF] | | smallint |
40092 | AC Energy | Wh | dword |
40094 | Scale factor [WH_SF] | | smallint |
40095 | DC Current | A | word |
40096 | Scale factor [DCA_SF] | | smallint |
40097 | DC Voltage | V | word |
40098 | Scale factor [DCV_SF] | | smallint |
40099 | DC Power | W | smallint |
40100 | Scale factor [DCW_SF] | | smallint |
40101 | Cabinet Temperature | C | smallint |
40102 | Heat Sink Temperature | C | smallint |
40103 | Transformer Temperature | C | smallint |
40104 | Other Temperature | C | smallint |
40105 | Scale factor [TMP_SF] | | smallint |
40106 | Enumerated value. Operating state | | word |
40107 | Vendor specific operating state code | | word |
40108 | Bitmask value. Event fields | | dword |
40110 | Reserved for future use | | dword |
40112 | Vendor defined events | | dword |
40114 | Vendor defined events | | dword |
40116 | Vendor defined events | | dword |
40118 | Vendor defined events | | dword |
40122 | Type of DER device. Default value is 4 to indicate PV device. | | word |
40123 | Continuous power output capability of the inverter. | W | word |
40124 | Scale factor | | smallint |
40125 | Continuous Volt-Ampere capability of the inverter. | VA | word |
40126 | Scale factor | | smallint |
40127 | Continuous VAR capability of the inverter in quadrant 1. | var | smallint |
40128 | Continuous VAR capability of the inverter in quadrant 2. | var | smallint |
There are more MODBUS items for this device. Please, download the program. |
ABB (-3P81-) data logging
ABB (3P86) data logging
ABB (3P88) data logging
ABB (3Q4200) data logging
ABB (B21) data logging
ABB (B23,B24) data logging
ABB (M2M,DMTME) data logging
ABB (M4M) data logging
ABB (Trio 50,Trio 60) data logging
ABB (UNO DM PLUS) data logging
ABB A41-A42 data logging
ABB A43-A44 data logging
ABB DMTME multimeters data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.