MODBUS offsetDescriptionUnitsData type
543Compliance name (EN 50160 or any other compliance standard)Stringstring
563Compliance descriptionStringstring
603OK / fail / NA status of the compliance currently runningUINT16word
621Percentage from the entire time (including off time) in which this compliance parameters was okfloatsingle
623Percentage from the entire time (including off time) in which this the compliance parameter was not okfloatsingle
625Percentage from the entire time (including off time) in which this compliance parameter was not evaluated (due to device off time)floatsingle
627Number of compliance parameters under checkUINT32dword
537Power supply temperature (read every second)floatsingle
999The measured frequency , calculated every 200 msec (10/12 cycles)floatsingle
1025Line 1 active power (W), calculate every cyclefloatsingle
1027Line 2 active power (W), calculate every cyclefloatsingle
1029Line 3 active power (W), calculate every cyclefloatsingle
1037Total active power (W), calculate every cyclefloatsingle
1041Line 1 reactive power (VAr) calculate every cyclefloatsingle
1043Line 2 reactive power (VAr) calculate every cyclefloatsingle
1045Line 3 reactive power (VAr) calculate every cyclefloatsingle
1053Reactive power - total (VAr) calculate every cyclefloatsingle
1057Line 1 apparent power (VA) calculate every cyclefloatsingle
1059Line 2 apparent power (VA) calculate every cyclefloatsingle
1061Line 3 apparent power (VA) calculate every cyclefloatsingle
1069Apparent power total (VA) calculate every cyclefloatsingle
1103RMS voltage V1, calculate every cyclefloatsingle
1105RMS voltage V2, calculate every cyclefloatsingle
1107RMS voltage V3, calculate every cyclefloatsingle
1109RMS voltage V12, calculate every cyclefloatsingle
1111RMS voltage V23, calculate every cyclefloatsingle
1113RMS voltage V31, calculate every cyclefloatsingle
1117RMS voltage I1, calculate every cyclefloatsingle
1119RMS voltage I2, calculate every cyclefloatsingle
1121RMS current I3, calculate every cyclefloatsingle
1123Cycle by cycle average RMS voltagefloatsingle
1125Cycle by cycle average RMS phase to phase voltagefloatsingle
1127Cycle by cycle average RMS currentfloatsingle
1159Internal DSP temperature, read every cyclefloatsingle
1161External DSP temperature (PT100 READING) , read every cyclefloatsingle
1659PST (short term flicker) - L1 - calculated over 2 secondsfloatsingle
1661PST (short term flicker) - L1 - calculated over 2 secondsfloatsingle
1663PST (short term flicker) - L1 - calculated over 2 secondsfloatsingle
1665PST (short term flicker)- L12 - calculated over 2 secondsfloatsingle
1667PST (short term flicker)- L23 -calculated over 2 secondsfloatsingle
1669PST (short term flicker)- L31 - calculated over 2 secondsfloatsingle
1671PST (short term flicker) - L1 - calculated over 10 secondsfloatsingle
1673PST (short term flicker)- L2 - calculated over 10 secondsfloatsingle
1675PST (short term flicker)- L3 - calculated over 10 secondsfloatsingle
1677PST (short term flicker)- L12 - calculated over 10 secondsfloatsingle
1679PST (short term flicker)- L23 - calculated over 10 secondsfloatsingle
1681PST (short term flicker)- L31 - calculated over 10 secondsfloatsingle
1683PST (short term flicker)- L1 - calculated over 10 minutesfloatsingle
1685PST (short term flicker)- L2 - calculated over 10 minutesfloatsingle
1687PST (short term flicker)- L3 - calculated over 10 minutesfloatsingle