IME Conto D2, Conto D4, Nemo 72 MODBUS registers: read online

Connect IME to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous IME data logger and record.

Do you not know the meter address? Scan the device address online

IME (Conto D2) - MODBUS Registers Map

Connection and addressing notes

Register addressing
hexadecimal addresses (e.g. 0x2000)

Registers in the map: 12. function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
768Device identifier word 
8192VoltageVdword×0.001
8194CurrentAdword×0.001
8196Active powerWdword×0.01
8198Sign of active power word 
8199Power factor word 
8200Sector of power factor (cap or ind) word 
8201FrequencyHzword×0.1
8202Positive active energykWhdword×0.1
8204Positive partial active energykWhdword×0.1
8206Operating time countersdword 
200Reset bit to bit defined word 

IME (Conto D4) - MODBUS Mapping

Connection and addressing notes

Register numbers
1-based
Register addressing
0-based decimal and hex addresses (e.g. register number 20481 = address 20480 = 0x5000)

Registers in the map: 60 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
20480Phase 1 current value (R)Adword×0.001
20482Phase 2 current value (S)Adword×0.001
20484Phase 3 current value (T)Adword×0.001
205091-N voltageVdword 
205112-N voltageVdword 
205133-N voltageVdword 
205151-2 voltageVdword 
205172-3 voltageVdword 
205193-1 voltageVdword 
20537Three-phase frequencyHzdword×0.01
20538Three-phase active powerkWinteger×0.01
20540Three-phase reactive powerkvarinteger×0.01
20544Threee-phase apparent powerkVAinteger×0.01
20548Three-phase power factorPFinteger×0.001
20550Power factor sectorPFdword 
20551Phase 1 active powerkWinteger×0.01
20553Phase 2 active powerkWinteger×0.01
20555Phase 3 active powerkWinteger×0.01
20557Phase reactive powerkvarinteger×0.01
20559Phase 2 reactive powerkvarinteger×0.01
20561Phase 3 reactive powerkvarinteger×0.01
20569Phase 1 apparent powerkVAdword×0.01
20571Phase 2 apparent powerkVAdword×0.01
20573Phase 3 apparent powerkVAdword×0.01
20592Positive three-phase active energykWhdword 
20594Negative three-phase active energykWhdword 
20598Positive three-phase reactive energykvarhdword 
20600Negative three-phase reactive energykvarhdword 
20604Positive three-phase active energy (Tariff 1)kWhdword×0.1
20606Negative three-phase active energy (Tariff 1)kWhdword×0.1
20608Positive three-phase reactive energy (Tariff 1)kvarhdword×0.1
20610Negative three-phase reactive energy (Tariff 1)kvarhdword×0.1
20612Positive three-phase active energy (Tariff 2)kWhdword×0.1
20614Negative three-phase active energy (Tariff 2)kWhdword×0.1
20616Positive three-phase reactive energy (Tariff 2)kvarhdword×0.1
20618Negative three-phase reactive energy (Tariff 2)kvarhdword×0.1
20638Positive three-phase active energy (secondary)kWhdword×0.01
20640Negative three-phase active energy (secondary)kWhdword×0.01
20644Positive three-phase reactive energy (secondary)kvarhdword×0.01
20646Negative three-phase reactive energy (secondary)kvarhdword×0.01
20650Positive three-phase active energy (Tariff 1) (secondary)kWhdword×0.01
20652Negative three-phase active energy (Tariff 1) (secondary)kWhdword×0.01
20654Positive three-phase reactive energy (Tariff 1) (secondary)kvarhdword×0.01
20656Negative three-phase reactive energy (Tariff 1) (secondary)kvarhdword×0.01
20658Positive three-phase active energy (Tariff 2) (secondary)kWhdword×0.01
20660Negative three-phase active energy (Tariff 2) (secondary)kWhdword×0.01
20662Positive three-phase reactive energy (Tariff 2) (secondary)kvarhdword×0.01
20664Negative three-phase reactive energy (Tariff 2) (secondary)kvarhdword×0.01
20725Phase shift between V1 V2 dword×0.1
20726Phase shift between V2 - V3 dword×0.1

This is not the complete map: 50 of 60 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

IME (Nemo 72) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Register addressing
hexadecimal addresses (e.g. 0x1000)

Registers in the map: 176 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
4612Device identifier word 
4096Phase 1 : phase voltageVdword×0.001
4098Phase 2 : phase voltageVdword×0.001
4100Phase 3 : phase voltageVdword×0.001
4102Phase 1 : currentAdword×0.001
4104Phase 2 : currentAdword×0.001
4106Phase 3 : currentAdword×0.001
4108Neutral currentAdword×0.001
4110Chained voltage : L1 L2Vdword×0.001
4112Chained voltage : L2 L3Vdword×0.001
4114Chained voltage : L3 L1Vdword×0.001
41163 phase : active powerW/var/VAdword 
41183 phase : reactive powerW/var/VAdword 
41203 phase : apparent powerW/var/VAdword 
41223 phase : sign of active power word 
41233 phase : sign of reactive power word 
41243 phase : positive active energyWhdword 
41263 phase : positive reactive energyWhdword 
41283 phase : negative active energyWhdword 
41303 phase : negative reactive energyWhdword 
41323 phase : power factorssmallint×0.01
41333 phase : sector of power factor (cap or ind)aword 
4134FrequencyHzword×0.1
41353 phase : average powerW/var/VAdword 
41373 phase : peak maximum demandW/var/VAdword 
4139Time counter for average powerminword 
4140Phase 1 : active powerW/var/VAdword 
4142Phase 2 : active powerW/var/VAdword 
4144Phase 3 : active powerW/var/VAdword 
4146Phase 1 : sign of active power word 
4147Phase 2 : sign of active power word 
4148Phase 3 : sign of active power word 
4149Phase 1 : reactive powerW/var/VAdword 
4151Phase 2 : reactive powerW/var/VAdword 
4153Phase 3 : reactive powerW/var/VAdword 
4155Phase 1 : sign of reactive power word 
4156Phase 2 : sign of reactive power word 
4157Phase 3 : sign of reactive power word 
4158Phase 1 : apparent powerW/var/VAdword 
4160Phase 2 : apparent powerW/var/VAdword 
4162Phase 3 : apparent powerW/var/VAdword 
4164Phase 1 : power factorssmallint×0.01
4165Phase 2 : power factorssmallint×0.01
4166Phase 3 : power factorssmallint×0.01
4167Phase 1 : power factor sectoraword 
4168Phase 2 : power factor sectoraword 
4169Phase 3 : power factor sectoraword 
4170Phase 1 : thd V1%word 
4171Phase 2 : thd V2%word 
4172Phase 3 : thd V3%word 

This is not the complete map: 50 of 176 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

IME (Nemo 96) - MODBUS Maps

Connection and addressing notes

Register addressing
hexadecimal addresses (e.g. 0x379)
Second address table
starts at 0x1000, implemented in the software
Address table usage
one or both tables may be used freely

Registers in the map: 184 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
768Device identifier word 
4612Device identifier word 
769Phase 1 : phase voltageVdword×0.001
773Phase 2 : phase voltageVdword×0.001
777Phase 3 : phase voltageVdword×0.001
781Phase 1 : currentAdword×0.001
785Phase 2 : currentAdword×0.001
789Phase 3 : currentAdword×0.001
7933 phase : active powerW/var/VAdword 
7973 phase : reactive powerW/var/VAdword 
8013 phase : apparent powerW/var/VAdword 
8053 phase : positive active energyWhdword 
809Chained voltage : L1 L2Vdword×0.001
813Chained voltage : L2 L3Vdword×0.001
817Chained voltage : L3 L1Vdword×0.001
8213 phase : negative active energyWhdword 
825FrequencyHzword 
827Operating timer counter word 
8293 phase : power factor word 
8313 phase : sector of power factor (cap or ind)aword 
832Voltages sequence diagnostic word 
833Output relay status word 
8353 phase : positive reactive energyWhdword 
8393 phase : sign of active power word 
8403 phase : negative reactive energyWhdword 
8443 phase : sign of reactive power word 
8483 phase : average powerW/var/VAdword 
8523 phase : peak maximum demandW/var/VAdword 
856Time counter for average powerminword 
857Neutral currentAdword×0.001
861Phase 1 : active powerW/var/VAdword 
865Phase 2 : active powerW/var/VAdword 
869Phase 3 : active powerW/var/VAdword 
873Phase 1 : sign of active power word 
874Phase 2 : sign of active power word 
875Phase 3 : sign of active power word 
876Phase 1 : reactive powerW/var/VAdword 
880Phase 2 : reactive powerW/var/VAdword 
884Phase 3 : reactive powerW/var/VAdword 
888Phase 1 : sign of reactive power word 
889Phase 2 : sign of reactive power word 
890Phase 3 : sign of reactive power word 
891Phase 1 : apparent powerW/var/VAdword 
895Phase 2 : apparent powerW/var/VAdword 
899Phase 3 : apparent powerW/var/VAdword 
903Phase 1 : power factor word 
905Phase 2 : power factor word 
907Phase 3 : power factor word 
909Phase 1 : power factor sectoraword 
910Phase 2 : power factor sectoraword 

This is not the complete map: 50 of 184 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

IME (Nemo D4-DC) - MODBUS Registers Map

Connection and addressing notes

Register addressing
hexadecimal addresses (e.g. 0x1000)
Data block size
variables or groups of variables may require up to 32 bytes

Registers in the map: 14. function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
4611Device identifier word 
4096VoltageVdword×0.001
4098CurrentAdword×0.001
4100Signed power dword 
4102Positive energy dword 
4104Negative energy dword 
4106Timesdword 
4108Average power dword 
4110Maximum power demand dword 
4112Minutes elapsed durino the average calculation word 
4114Positive amperehoursAhdword 
4116Negative amperehoursAhdword 
4609Current transformer ratio (kta) word 
4610Voltage transformer ratio (ktv) word×0.1