Connect IME to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous IME data logger and record.
Do you not know the meter address? Scan the device address online
IME (Conto D2) - MODBUS Registers Map
Connection and addressing notes
- Register addressing
- hexadecimal addresses (e.g. 0x2000)
Registers in the map: 12. function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 768 | Device identifier | | word | |
| 8192 | Voltage | V | dword | ×0.001 |
| 8194 | Current | A | dword | ×0.001 |
| 8196 | Active power | W | dword | ×0.01 |
| 8198 | Sign of active power | | word | |
| 8199 | Power factor | | word | |
| 8200 | Sector of power factor (cap or ind) | | word | |
| 8201 | Frequency | Hz | word | ×0.1 |
| 8202 | Positive active energy | kWh | dword | ×0.1 |
| 8204 | Positive partial active energy | kWh | dword | ×0.1 |
| 8206 | Operating time counter | s | dword | |
| 200 | Reset bit to bit defined | | word | |
IME (Conto D4) - MODBUS Mapping
Connection and addressing notes
- Register numbers
- 1-based
- Register addressing
- 0-based decimal and hex addresses (e.g. register number 20481 = address 20480 = 0x5000)
Registers in the map: 60 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, integer.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 20480 | Phase 1 current value (R) | A | dword | ×0.001 |
| 20482 | Phase 2 current value (S) | A | dword | ×0.001 |
| 20484 | Phase 3 current value (T) | A | dword | ×0.001 |
| 20509 | 1-N voltage | V | dword | |
| 20511 | 2-N voltage | V | dword | |
| 20513 | 3-N voltage | V | dword | |
| 20515 | 1-2 voltage | V | dword | |
| 20517 | 2-3 voltage | V | dword | |
| 20519 | 3-1 voltage | V | dword | |
| 20537 | Three-phase frequency | Hz | dword | ×0.01 |
| 20538 | Three-phase active power | kW | integer | ×0.01 |
| 20540 | Three-phase reactive power | kvar | integer | ×0.01 |
| 20544 | Threee-phase apparent power | kVA | integer | ×0.01 |
| 20548 | Three-phase power factor | PF | integer | ×0.001 |
| 20550 | Power factor sector | PF | dword | |
| 20551 | Phase 1 active power | kW | integer | ×0.01 |
| 20553 | Phase 2 active power | kW | integer | ×0.01 |
| 20555 | Phase 3 active power | kW | integer | ×0.01 |
| 20557 | Phase reactive power | kvar | integer | ×0.01 |
| 20559 | Phase 2 reactive power | kvar | integer | ×0.01 |
| 20561 | Phase 3 reactive power | kvar | integer | ×0.01 |
| 20569 | Phase 1 apparent power | kVA | dword | ×0.01 |
| 20571 | Phase 2 apparent power | kVA | dword | ×0.01 |
| 20573 | Phase 3 apparent power | kVA | dword | ×0.01 |
| 20592 | Positive three-phase active energy | kWh | dword | |
| 20594 | Negative three-phase active energy | kWh | dword | |
| 20598 | Positive three-phase reactive energy | kvarh | dword | |
| 20600 | Negative three-phase reactive energy | kvarh | dword | |
| 20604 | Positive three-phase active energy (Tariff 1) | kWh | dword | ×0.1 |
| 20606 | Negative three-phase active energy (Tariff 1) | kWh | dword | ×0.1 |
| 20608 | Positive three-phase reactive energy (Tariff 1) | kvarh | dword | ×0.1 |
| 20610 | Negative three-phase reactive energy (Tariff 1) | kvarh | dword | ×0.1 |
| 20612 | Positive three-phase active energy (Tariff 2) | kWh | dword | ×0.1 |
| 20614 | Negative three-phase active energy (Tariff 2) | kWh | dword | ×0.1 |
| 20616 | Positive three-phase reactive energy (Tariff 2) | kvarh | dword | ×0.1 |
| 20618 | Negative three-phase reactive energy (Tariff 2) | kvarh | dword | ×0.1 |
| 20638 | Positive three-phase active energy (secondary) | kWh | dword | ×0.01 |
| 20640 | Negative three-phase active energy (secondary) | kWh | dword | ×0.01 |
| 20644 | Positive three-phase reactive energy (secondary) | kvarh | dword | ×0.01 |
| 20646 | Negative three-phase reactive energy (secondary) | kvarh | dword | ×0.01 |
| 20650 | Positive three-phase active energy (Tariff 1) (secondary) | kWh | dword | ×0.01 |
| 20652 | Negative three-phase active energy (Tariff 1) (secondary) | kWh | dword | ×0.01 |
| 20654 | Positive three-phase reactive energy (Tariff 1) (secondary) | kvarh | dword | ×0.01 |
| 20656 | Negative three-phase reactive energy (Tariff 1) (secondary) | kvarh | dword | ×0.01 |
| 20658 | Positive three-phase active energy (Tariff 2) (secondary) | kWh | dword | ×0.01 |
| 20660 | Negative three-phase active energy (Tariff 2) (secondary) | kWh | dword | ×0.01 |
| 20662 | Positive three-phase reactive energy (Tariff 2) (secondary) | kvarh | dword | ×0.01 |
| 20664 | Negative three-phase reactive energy (Tariff 2) (secondary) | kvarh | dword | ×0.01 |
| 20725 | Phase shift between V1 V2 | | dword | ×0.1 |
| 20726 | Phase shift between V2 - V3 | | dword | ×0.1 |
This is not the complete map: 50 of 60 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
IME (Nemo 72) - MODBUS Registers Map
Connection and addressing notes
- Protocol
- Modbus
- Register addressing
- hexadecimal addresses (e.g. 0x1000)
Registers in the map: 176 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 4612 | Device identifier | | word | |
| 4096 | Phase 1 : phase voltage | V | dword | ×0.001 |
| 4098 | Phase 2 : phase voltage | V | dword | ×0.001 |
| 4100 | Phase 3 : phase voltage | V | dword | ×0.001 |
| 4102 | Phase 1 : current | A | dword | ×0.001 |
| 4104 | Phase 2 : current | A | dword | ×0.001 |
| 4106 | Phase 3 : current | A | dword | ×0.001 |
| 4108 | Neutral current | A | dword | ×0.001 |
| 4110 | Chained voltage : L1 L2 | V | dword | ×0.001 |
| 4112 | Chained voltage : L2 L3 | V | dword | ×0.001 |
| 4114 | Chained voltage : L3 L1 | V | dword | ×0.001 |
| 4116 | 3 phase : active power | W/var/VA | dword | |
| 4118 | 3 phase : reactive power | W/var/VA | dword | |
| 4120 | 3 phase : apparent power | W/var/VA | dword | |
| 4122 | 3 phase : sign of active power | | word | |
| 4123 | 3 phase : sign of reactive power | | word | |
| 4124 | 3 phase : positive active energy | Wh | dword | |
| 4126 | 3 phase : positive reactive energy | Wh | dword | |
| 4128 | 3 phase : negative active energy | Wh | dword | |
| 4130 | 3 phase : negative reactive energy | Wh | dword | |
| 4132 | 3 phase : power factor | s | smallint | ×0.01 |
| 4133 | 3 phase : sector of power factor (cap or ind) | a | word | |
| 4134 | Frequency | Hz | word | ×0.1 |
| 4135 | 3 phase : average power | W/var/VA | dword | |
| 4137 | 3 phase : peak maximum demand | W/var/VA | dword | |
| 4139 | Time counter for average power | min | word | |
| 4140 | Phase 1 : active power | W/var/VA | dword | |
| 4142 | Phase 2 : active power | W/var/VA | dword | |
| 4144 | Phase 3 : active power | W/var/VA | dword | |
| 4146 | Phase 1 : sign of active power | | word | |
| 4147 | Phase 2 : sign of active power | | word | |
| 4148 | Phase 3 : sign of active power | | word | |
| 4149 | Phase 1 : reactive power | W/var/VA | dword | |
| 4151 | Phase 2 : reactive power | W/var/VA | dword | |
| 4153 | Phase 3 : reactive power | W/var/VA | dword | |
| 4155 | Phase 1 : sign of reactive power | | word | |
| 4156 | Phase 2 : sign of reactive power | | word | |
| 4157 | Phase 3 : sign of reactive power | | word | |
| 4158 | Phase 1 : apparent power | W/var/VA | dword | |
| 4160 | Phase 2 : apparent power | W/var/VA | dword | |
| 4162 | Phase 3 : apparent power | W/var/VA | dword | |
| 4164 | Phase 1 : power factor | s | smallint | ×0.01 |
| 4165 | Phase 2 : power factor | s | smallint | ×0.01 |
| 4166 | Phase 3 : power factor | s | smallint | ×0.01 |
| 4167 | Phase 1 : power factor sector | a | word | |
| 4168 | Phase 2 : power factor sector | a | word | |
| 4169 | Phase 3 : power factor sector | a | word | |
| 4170 | Phase 1 : thd V1 | % | word | |
| 4171 | Phase 2 : thd V2 | % | word | |
| 4172 | Phase 3 : thd V3 | % | word | |
This is not the complete map: 50 of 176 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
IME (Nemo 96) - MODBUS Maps
Connection and addressing notes
- Register addressing
- hexadecimal addresses (e.g. 0x379)
- Second address table
- starts at 0x1000, implemented in the software
- Address table usage
- one or both tables may be used freely
Registers in the map: 184 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 768 | Device identifier | | word | |
| 4612 | Device identifier | | word | |
| 769 | Phase 1 : phase voltage | V | dword | ×0.001 |
| 773 | Phase 2 : phase voltage | V | dword | ×0.001 |
| 777 | Phase 3 : phase voltage | V | dword | ×0.001 |
| 781 | Phase 1 : current | A | dword | ×0.001 |
| 785 | Phase 2 : current | A | dword | ×0.001 |
| 789 | Phase 3 : current | A | dword | ×0.001 |
| 793 | 3 phase : active power | W/var/VA | dword | |
| 797 | 3 phase : reactive power | W/var/VA | dword | |
| 801 | 3 phase : apparent power | W/var/VA | dword | |
| 805 | 3 phase : positive active energy | Wh | dword | |
| 809 | Chained voltage : L1 L2 | V | dword | ×0.001 |
| 813 | Chained voltage : L2 L3 | V | dword | ×0.001 |
| 817 | Chained voltage : L3 L1 | V | dword | ×0.001 |
| 821 | 3 phase : negative active energy | Wh | dword | |
| 825 | Frequency | Hz | word | |
| 827 | Operating timer counter | | word | |
| 829 | 3 phase : power factor | | word | |
| 831 | 3 phase : sector of power factor (cap or ind) | a | word | |
| 832 | Voltages sequence diagnostic | | word | |
| 833 | Output relay status | | word | |
| 835 | 3 phase : positive reactive energy | Wh | dword | |
| 839 | 3 phase : sign of active power | | word | |
| 840 | 3 phase : negative reactive energy | Wh | dword | |
| 844 | 3 phase : sign of reactive power | | word | |
| 848 | 3 phase : average power | W/var/VA | dword | |
| 852 | 3 phase : peak maximum demand | W/var/VA | dword | |
| 856 | Time counter for average power | min | word | |
| 857 | Neutral current | A | dword | ×0.001 |
| 861 | Phase 1 : active power | W/var/VA | dword | |
| 865 | Phase 2 : active power | W/var/VA | dword | |
| 869 | Phase 3 : active power | W/var/VA | dword | |
| 873 | Phase 1 : sign of active power | | word | |
| 874 | Phase 2 : sign of active power | | word | |
| 875 | Phase 3 : sign of active power | | word | |
| 876 | Phase 1 : reactive power | W/var/VA | dword | |
| 880 | Phase 2 : reactive power | W/var/VA | dword | |
| 884 | Phase 3 : reactive power | W/var/VA | dword | |
| 888 | Phase 1 : sign of reactive power | | word | |
| 889 | Phase 2 : sign of reactive power | | word | |
| 890 | Phase 3 : sign of reactive power | | word | |
| 891 | Phase 1 : apparent power | W/var/VA | dword | |
| 895 | Phase 2 : apparent power | W/var/VA | dword | |
| 899 | Phase 3 : apparent power | W/var/VA | dword | |
| 903 | Phase 1 : power factor | | word | |
| 905 | Phase 2 : power factor | | word | |
| 907 | Phase 3 : power factor | | word | |
| 909 | Phase 1 : power factor sector | a | word | |
| 910 | Phase 2 : power factor sector | a | word | |
This is not the complete map: 50 of 184 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
IME (Nemo D4-DC) - MODBUS Registers Map
Connection and addressing notes
- Register addressing
- hexadecimal addresses (e.g. 0x1000)
- Data block size
- variables or groups of variables may require up to 32 bytes
Registers in the map: 14. function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 4611 | Device identifier | | word | |
| 4096 | Voltage | V | dword | ×0.001 |
| 4098 | Current | A | dword | ×0.001 |
| 4100 | Signed power | | dword | |
| 4102 | Positive energy | | dword | |
| 4104 | Negative energy | | dword | |
| 4106 | Time | s | dword | |
| 4108 | Average power | | dword | |
| 4110 | Maximum power demand | | dword | |
| 4112 | Minutes elapsed durino the average calculation | | word | |
| 4114 | Positive amperehours | Ah | dword | |
| 4116 | Negative amperehours | Ah | dword | |
| 4609 | Current transformer ratio (kta) | | word | |
| 4610 | Voltage transformer ratio (ktv) | | word | ×0.1 |