Connect Janitza to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Janitza logger and poll.

Do you not know the meter address? Scan the device address online

Janitza (B21,B23,B24) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Register set
standard register set compatible with UMG devices
Register addressing
addresses expressed exactly as sent on the bus
Address adjustment
none, do not subtract 40000 or reduce by 1
Start Reg
decimal (DEZ)
Size
16-bit Modbus registers
Data format
FLOAT (IEEE754)

Registers in the map: 53 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
19000Voltage L1-NVsingle 
19002Voltage L2-NVsingle 
19004Voltage L3-NVsingle 
19006Voltage L1-L2Vsingle 
19008Voltage L2-L3Vsingle 
19010Voltage L3-L1Vsingle 
19012Apparent current, L1-NAsingle 
19014Apparent current, L2-NAsingle 
19016Apparent current, L3-NAsingle 
19020Real power L1-NWsingle 
19022Real power L2-NWsingle 
19024Real power L3-NWsingle 
19026Real power L1+L2+L3Wsingle 
19028Apparent power L1-NVAsingle 
19030Apparent power L2-NVAsingle 
19032Apparent power L3-NVAsingle 
19034Apparent power L1+L2+L3VAsingle 
19036Reactive power L1varsingle 
19038Reactive power L2varsingle 
19040Reactive power L3varsingle 
19042Reactive power L1+L2+L3varsingle 
19044Power factor L1 single 
19046Power factor L2 single 
19048Power factor L3 single 
19050Measured frequencyHzsingle 
19054Real energy L1Whsingle 
19056Real energy L2Whsingle 
19058Real energy L3Whsingle 
19060Real energy L1+L2+L3Whsingle 
19062Real energy L1, consumedWhsingle 
19064Real energy L2, consumedWhsingle 
19066Real energy L3, consumedWhsingle 
19068Real energy L1+L2+L3, consumedWhsingle 
19070Real energy L1, deliveredWhsingle 
19072Real energy L2, deliveredWhsingle 
19074Real energy L3, deliveredWhsingle 
19076Real energy L1+L2+L3, deliveredWhsingle 
19078Apparent energy L1VAhsingle 
19080Apparent energy L2VAhsingle 
19082Apparent energy L3VAhsingle 
19084Apparent energy L1+L2+L3VAhsingle 
19086Reactive energy L1varhsingle 
19088Reactive energy L2varhsingle 
19090Reactive energy L3varhsingle 
19092Reactive energy L1+L2+L3varhsingle 
19094Reactive energy L1, inductivevarhsingle 
19096Reactive energy L2, inductivevarhsingle 
19098Reactive energy L3, inductivevarhsingle 
19100Reactive energy L1+L2+L3, inductivevarhsingle 
19102Reactive energy L1, capacitivevarhsingle 

This is not the complete map: 50 of 53 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Janitza (ECS) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Interface variants
Basic and Full
Interface and counter type columns
TA, TE, SA, SE
Register addressing
register addresses used directly as map offsets
Speed register
4112
Parity register
4113
Stop bits register
4114
Device address register
4115
Value format register
4117
Unsupported quantities
returned as 0

Registers in the map: 69 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, word.

MODBUS offsetDescriptionUnitsData typeScale
4099Device type word 
4100Firmware version word 
4101Range overflow alarm word 
4102Running tariff dword 
4104PID bytes 1 and 2 word 
4105PID bytes 3 and 4 word 
4106PID bytes 5 and 6 word 
4107PID bytes 7 and 8 word 
4108PID bytes 9 and 10 word 
4109PID bytes 11 and 12 word 
4110PID bytes 13 and 14 word 
4119Active energy 1st phase T1, impkWhint64formula
4123Active energy 2nd phase T1, impkWhint64formula
4127Active energy 3rd phase T1, impkWhint64formula
4131Active energy sum T1, impkWhint64formula
4135Active energy 1st phase T2, impkWhint64formula
4139Active energy 2nd phase T2, impkWhint64formula
4143Active energy 3rd phase T2, impkWhint64formula
4147Active energy sum T2, impkWhint64formula
4151Active power 1st phase dword 
4153Active power 2nd phase dword 
4155Active power 3rd phase dword 
4157Active power sum int64formula
4161Active energy 1st phase T1, expkWhint64formula
4165Active energy 2nd phase T1, expkWhint64formula
4169Active energy 3rd phase T1, expkWhint64formula
4173Active energy sum T1, expkWhint64formula
4177Active energy 1st phase T2, expkWhint64formula
4181Active energy 2nd phase T2, expkWhint64formula
4185Active energy 3rd phase T2, expkWhint64formula
4189Active energy sum T2, expkWhint64formula
4193Reactive energy 1st phase T1, impkvarhint64formula
4197Reactive energy 2nd phase T1, impkvarhint64formula
4201Reactive energy 3rd phase T1, impkvarhint64formula
4205Reactive energy sum T1, impkvarhint64formula
4209Reactive energy 1st phase T2, impkvarhint64formula
4213Reactive energy 2nd phase T2, impkvarhint64formula
4217Reactive energy 3rd phase T2, impkvarhint64formula
4221Reactive energy sum T2, impkvarhint64formula
4225Reactive energy 1st phase T1, expkvarhint64formula
4229Reactive energy 2nd phase T1, expkvarhint64formula
4233Reactive energy 3rd phase T1, expkvarhint64formula
4237Reactive energy sum T1, expkvarhint64formula
4241Reactive energy 1st phase T2, expkvarhint64formula
4245Reactive energy 2nd phase T2, expkvarhint64formula
4249Reactive energy 3rd phase T2, expkvarhint64formula
4253Reactive energy sum T2, expkvarhint64formula
4257Reactive power 1st phasekvardword 
4259Reactive power 2nd phasekvardword 
4261Reactive power 3rd phasekvardword 

This is not the complete map: 50 of 69 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Janitza (UMG103) - MODBUS Registers Map

Registers in the map: 1274 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
911Serial number integer 
913Firmware release smallint 
914Hardware expansion smallint 
19000Voltage L1 NVsingle 
19002Voltage L2 NVsingle 
19004Voltage L3 NVsingle 
19006Voltage L1 L2Vsingle 
19008Voltage L2 L3Vsingle 
19010Voltage L3 L1Vsingle 
19012Apparent current, L1Asingle 
19014Apparent current, L2Asingle 
19016Apparent current, L3Asingle 
19018Vector sum; in=i1+i2+i3Asingle 
19020Real power L1Wsingle 
19022Real power L2Wsingle 
19024Real power L3Wsingle 
19026Sum; psum3=p1+p2+p3Wsingle 
19028Apparent power L1VAsingle 
19030Apparent power L2VAsingle 
19032Apparent power L3VAsingle 
19034Sum; ssum3=s1+s2+s3VAsingle 
19036Reactive power (mains frequ.) L1varsingle 
19038Reactive power (mains frequ.) L2varsingle 
19040Reactive power (mains frequ.) L3varsingle 
19042Sum; qsum3=Q1+Q2+Q3varsingle 
19044Fund.power factor, cosphi; UL1 IL1 single 
19046Fund.power factor, cosphi; UL2 IL2 single 
19048Fund.power factor, cosphi; UL3 IL3 single 
19050Measured frequencyHzsingle 
19052Rotation field single 
19060Real energy l1..l3Whsingle 
19062Real energy l1, consumedWhsingle 
19064Real energy l2, consumedWhsingle 
19066Real energy l3, consumedWhsingle 
19068Real energy l1..l3, consumed, rate 1Whsingle 
19070Real energy l1, deliveredWhsingle 
19072Real energy l2, deliveredWhsingle 
19074Real energy l3, deliveredWhsingle 
19076Real energy l1..l3, deliveredWhsingle 
19078Apparent energy L1VAhsingle 
19080Apparent energy L2VAhsingle 
19082Apparent energy L3VAhsingle 
19084Apparent energy l1..l3VAhsingle 
19092Reactive energy l1..l3varhsingle 
19094Reactive energy, inductive, L1varhsingle 
19096Reactive energy, inductive, L2varhsingle 
19098Reactive energy, inductive, L3varhsingle 
19100Reactive energy l1..l3, indvarhsingle 
19102Reactive energy, capacitive, L1varhsingle 
19104Reactive energy, capacitive, L2varhsingle 

This is not the complete map: 50 of 1274 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Janitza (UMG104) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Interface
RS485 and RS232
Register addressing
bus register numbers used directly as map offsets
Device address register
10180
RS485 mode register
10182
RS485 baud rate register
10184
RS232 baud rate register
10186
RS232 mode register
10188
Data format
float, int, short, word, string

Registers in the map: 2895 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, smallint, string(16).

MODBUS offsetDescriptionUnitsData typeScale
10176Serial number dword 
13437Software release string(16) 
19000Voltage L1 NVsingle 
19002Voltage L2 NVsingle 
19004Voltage L3 NVsingle 
19006Voltage L1 L2Vsingle 
19008Voltage L2 L3Vsingle 
19010Voltage L3 L1Vsingle 
19012Apparent current, L1Asingle 
19014Apparent current, L2Asingle 
19016Apparent current, L3Asingle 
19018Vector sum; in=i1+i2+i3Asingle 
19020Real power L1Wsingle 
19022Real power L2Wsingle 
19024Real power L3Wsingle 
19026Sum; psum3=p1+p2+p3Wsingle 
19028Apparent power L1VAsingle 
19030Apparent power L2VAsingle 
19032Apparent power L3VAsingle 
19034Sum; ssum3=s1+s2+s3VAsingle 
19036Reactive power (mains frequ.) L1varsingle 
19038Reactive power (mains frequ.) L2varsingle 
19040Reactive power (mains frequ.) L3varsingle 
19042Sum; qsum3=Q1+Q2+Q3varsingle 
19044Fund.power factor, cosphi; UL1 IL1 single 
19046Fund.power factor, cosphi; UL2 IL2 single 
19048Fund.power factor, cosphi; UL3 IL3 single 
19050Measured frequencyHzsingle 
19052Rotation field single 
19054Real energy L1Whsingle 
19056Real energy L2Whsingle 
19058Real energy L3Whsingle 
19060Real energy l1..l3Whsingle 
19062Real energy l1, consumedWhsingle 
19064Real energy l2, consumedWhsingle 
19066Real energy l3, consumedWhsingle 
19068Real energy l1..l3, consumed, rate 1Whsingle 
19070Real energy l1, deliveredWhsingle 
19072Real energy l2, deliveredWhsingle 
19074Real energy l3, deliveredWhsingle 
19076Real energy l1..l3, deliveredWhsingle 
19078Apparent energy L1VAhsingle 
19080Apparent energy L2VAhsingle 
19082Apparent energy L3VAhsingle 
19084Apparent energy l1..l3VAhsingle 
19086Reaktive energy L1varhsingle 
19088Reaktive energy L2varhsingle 
19090Reaktive energy L3varhsingle 
19092Reaktive energy l1..l3varhsingle 
19094Reactive energy, inductive, L1varhsingle 

This is not the complete map: 50 of 2895 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Janitza (UMG511) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Register addressing
19000 series addresses used directly as map offsets

Registers in the map: 61 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
19000Voltage L1 NVsingle 
19002Voltage L2 NVsingle 
19004Voltage L3 NVsingle 
19006Voltage L1 L2Vsingle 
19008Voltage L2 L3Vsingle 
19010Voltage L3 L1Vsingle 
19012Apparent current, L1 NAsingle 
19014Apparent current, L2 NAsingle 
19016Apparent current, L3 NAsingle 
19018Vector sum; in=i1+i2+i3Asingle 
19020Real power L1 NWsingle 
19022Real power L2 NWsingle 
19024Real power L3 NWsingle 
19026Psum3=p1+p2+p3Wsingle 
19028Apparent power L1 NVAsingle 
19030Apparent power L2 NVAsingle 
19032Apparent power L3 NVAsingle 
19034Sum; ssum3=s1+s2+s3VAsingle 
19036Reactive power L1 (fundamental comp.)varsingle 
19038Reactive power L2 (fundamental comp.)varsingle 
19040Reactive power L3 (fundamental comp.)varsingle 
19042Qsum3=Q1+Q2+Q3 (fundamental comp.)varsingle 
19044Cosphi; UL1 IL1 (fundamental comp.) single 
19046Cosphi; UL2 IL2 (fundamental comp.) single 
19048Cosphi; UL3 IL3 (fundamental comp.) single 
19050Measured frequencyHzsingle 
19052Rotation field single 
19054Real energy L1Whsingle 
19056Real energy L2Whsingle 
19058Real energy L3Whsingle 
19060Real energy l1..l3Whsingle 
19062Real energy l1, consumedWhsingle 
19064Real energy l2, consumedWhsingle 
19066Real energy l3, consumedWhsingle 
19068Real energy l1..l3, consumed, rate 1Whsingle 
19070Real energy l1, deliveredWhsingle 
19072Real energy l2, deliveredWhsingle 
19074Real energy l3, deliveredWhsingle 
19076Real energy l1..l3, deliveredWhsingle 
19078Apparent energy L1VAhsingle 
19080Apparent energy L2VAhsingle 
19082Apparent energy L3VAhsingle 
19084Apparent energy l1..l3VAhsingle 
19086Reaktive energy L1 (fundamental comp.)varhsingle 
19088Reaktive energy L2 (fundamental comp.)varhsingle 
19090Reaktive energy L3 (fundamental comp.)varhsingle 
19092Reaktive energy l1..l3 (fundamental comp.)varhsingle 
19094Reactive energy, inductive, L1 (fundamental comp.)varhsingle 
19096Reactive energy, inductive, L2 (fundamental comp.)varhsingle 
19098Reactive energy, inductive, L3 (fundamental comp.)varhsingle 