MODBUS offsetDescriptionUnitsData type
10511Hour: operating hours counterhdword
10513U12: conductor voltageVdword
10515U23: conductor voltageVdword
10517U31: conductor voltageVdword
10519V1: conductor voltage to NVdword
10521V2: conductor voltage to NVdword
10523V3: conductor voltage to NVdword
10525F: frequencyHzdword
10527I1: currentAdword
10529I2: currentAdword
10531I3: currentAdword
10533In: neutral conductor currentAdword
10535P: total active power +/-Winteger
10537Q: total reactive power +/-varinteger
10539S: total apparent powerVAdword
10541PF: total power factor -: capacitive and +: inductive1integer
10543P1: active power phase 1 +/-Winteger
10545P2: active power phase 2 +/-Winteger
10547P3: active power phase 3 +/-Winteger
10549Q1: reactive power phase 1 +/-varinteger
10551Q2: reactive power phase 2 +/-varinteger
10553Q3: reactive power phase 3 +/-varinteger
10555S1: apparent power phase 1VAdword
10557S2: apparent power phase 2VAdword
10559S3: apparent power phase 3VAdword
10561PF1; power factor, phase 1 -: capacitive and +: inductive1integer
10563PF2; power factor, phase 2 -: capacitive and +: inductive1integer
10565PF3; power factor, phase 3 -: capacitive and +: inductive1integer
10567ISYS: mean current valueAdword
10569USYS: mean value of line voltagesVdword
10571VSYS: mean value of line voltages to NVdword
10767Hour: operating hours counterhdword
10769Total active energy procurement systemkWhdword
10771Total inductive reactive energy systemkvarhdword
10773Total apparent energy systemkVAhdword
10775Total active energy supply systemkWhdword
10777Total capacitive reactive energy systemkvarhdword
10779Partial energy meter active energy pro- curement systemkWhdword
10781Partial energy meter inductive reactive energy systemkvarhdword
10783Partial energy meter apparent energy systemkVAhdword
10785Partial energy meter active energy sup- ply systemkWhdword
10787Partial energy meter capacitive reactive energy systemkvarhdword


Phoenix Contact (EEM-EM3xx,EM325,EM355,EM375,EM327,EM357,EM377) data logging