Pilot (SPM93) logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
1 | Vb | V | word |
2 | Vc | V | word |
3 | Ia | A | dword |
5 | Ib | A | dword |
7 | Ic | A | dword |
9 | Frequency | Hz, | word |
10 | Total power factor | | smallint |
11 | Total apparent | | dword |
13 | Total active energy | | dword |
15 | Total reactive energy | kvarh, | dword |
17 | Phase A active power | W | integer |
19 | Phase B active power | W | integer |
21 | Phase C active power | W | integer |
23 | Total active power | W | integer |
25 | Phase A reactive power | | integer |
27 | Phase B reactive power | | integer |
29 | Phase C reactive | | integer |
31 | Total reactive power | | integer |
100 | Va (ph n) | V | word |
101 | Vb (ph n) | V | word |
102 | Vc (ph n) | V | word |
103 | Vab (ph ph) | V | word |
104 | Vbc (ph ph) | V | word |
105 | Vca (ph ph) | V | word |
106 | Ia | | dword |
108 | Ib | | dword |
110 | Ic | | dword |
112 | Average current | | dword |
114 | Phase A active power | W | integer |
116 | Phase B active power | W | integer |
118 | Phase C active power | W | integer |
120 | Total active power | W | integer |
122 | Phase A reactive power | | integer |
124 | Phase B reactive power | | integer |
126 | Phase C reactive power | | integer |
128 | Total reactive power | | integer |
130 | Phase A apparent power | | dword |
132 | Phase B apparent power | | dword |
134 | Phase C apparent power | | dword |
136 | Total apparent power | | dword |
138 | Phase A power factor | | smallint |
139 | Phase B power factor | | smallint |
140 | Phase C power factor | | smallint |
141 | Total power factor | | smallint |
142 | Frequency | | word |
143 | Loaded timing | | dword |
145 | Over voltage timing under voltage timing | | dword |
1000 | Imp. kwh | | dword |
1002 | Exp. kwh | | dword |
1004 | Total kwh | | dword |
There are more MODBUS items for this device. Please, download the program. |
Pilot (PMAC735) data logging
Pilot (SPM32) data logging
Pilot (SPM33) data logging
Pilot (SPM91) data logging
Pilot (SPM93) data logging
Pilot PMAC770 data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.