Rayleigh Instruments RI-D140, RI-D35, RI-F100 MODBUS registers: read online

Connect Rayleigh Instruments to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Rayleigh Instruments data logger and record.

Do you not know the meter address? Scan the device address online

Rayleigh Instruments (RI-D140) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Byte order (4-byte data)
LSB on the lower address, MSB on the higher address
Data format
2 registers per value
Register addressing
3xxxx with a hex offset column (30000 = 0x00)

Registers in the map: 15. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage 1st phaseVsingle 
2Voltage 2nd phaseVsingle 
4Voltage 3rd phaseVsingle 
6Average voltage lnVsingle 
8Voltage V12Vsingle 
10Voltage V23Vsingle 
12Voltage V31Vsingle 
14Average voltage llVsingle 
16Current I1Asingle 
18Current I2Asingle 
20Current I3Asingle 
22Average currentAsingle 
24kW1 single 
26kW2 single 
28kW3 single 

Rayleigh Instruments (RI-D35) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Data format
2 registers per value, float data structure
Register addressing
3xxxx with a hex offset column (30001 = 0x01)

Registers in the map: 24. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Total active energy single 
2Import active energy single 
4Export active energy single 
6Total reactive energy single 
8Import reactive energy single 
10Export reactive energy single 
12Apparent energy single 
14Active power single 
16Reactive power single 
18Apparent power single 
20Voltage L NVsingle 
22CurrentAsingle 
24Power factor single 
26FrequencyHzsingle 
28Max demand active power single 
30Max demand reactive power single 
32Max demand apparent power single 
149TotalkWhsingle 
150ImportkWhsingle 
151ExportkWhsingle 
152Totalkvarhsingle 
153Importkvarhsingle 
154Exportkvarhsingle 
155KvahKvahsingle 

Rayleigh Instruments (RI-F100) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Register addressing
input registers 30000-30xxx and 31000-31xxx
Data format
2 registers per parameter (float)
Byte order (3-register hex values)
LSB at the lower address, MSB at the higher address

Registers in the map: 70 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
1Voltage v2n single 
3Voltage v3n single 
5Average voltage ln single 
7Voltage V12 single 
9Voltage V23 single 
11Voltage V31 single 
13Average voltage ll single 
15Current I1 single 
17Current I2 single 
19Current I3 single 
21Average current single 
23kW1 single 
25kW2 single 
27kW3 single 
29Kva1 single 
31Kva2 single 
33Kva3 single 
35Kvar1 single 
37Kvar2 single 
39Kvar3 single 
41TotalkWsingle 
43TotalkVAsingle 
45Totalkvarsingle 
47PF1 single 
49PF2 single 
51PF3 single 
53Average pf single 
55Frequency single 
57Total netkWhsingle 
59Total netkVAhsingle 
61Total netkvarhsingle 
63Kw max active power single 
65Kw min active power single 
67Kvar max reactive power single 
69Kvar min reactive power single 
71Kva max apparent power single 
73Max I1 demand single 
75Max I2 demand single 
77Max I3 demand single 
79Max avg demand single 
81Run hour single 
83Kwh1 (imp) single 
85Kwh2 (imp) single 
87Kwh3 (imp) single 
89Kwh1 (exp) single 
91Kwh2 (exp) single 
93Kwh3 (exp) single 
95Total kwh (imp)kWhsingle 
97Total kwh (exp)kWhsingle 
99Kvarh1 (imp) single 

This is not the complete map: 50 of 70 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Rayleigh Instruments (RI-F200) - Measurement Data

Registers in the map: 62 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single, string(4).

MODBUS offsetDescriptionUnitsData typeScale
684Serial number of unit string(4) 
0Voltage v1nVsingle 
2Voltage v2nVsingle 
4Voltage v3nVsingle 
6Average voltage lnVsingle 
8Voltage V12Vsingle 
10Voltage V23Vsingle 
12Voltage V31Vsingle 
14Average voltage llVsingle 
16Current l1Asingle 
18Current I2Asingle 
20Current I3Asingle 
22Average currentAsingle 
24kW1 single 
26kW2 single 
28kW3 single 
30Kva1 single 
32Kva2 single 
34Kva3 single 
36Kvar1 single 
38Kvar2 single 
40Kvar3 single 
42TotalkWsingle 
44TotalkVAsingle 
46Totalkvarsingle 
48PF1 single 
50PF2 single 
52PF3 single 
54Average pf single 
56FrequencyHzsingle 
58Kwh single 
60Kvah single 
62Kvarh single 
64Kw max active power single 
66Kw min active power single 
68Kvar max reactive power single 
70Kvar min reactive power single 
72Kva max apparent power single 
122Neutral current single 
124Thd of voltage v1n single 
126Thd of voltage v2n single 
128Thd of voltage v3n single 
130Thd of voltage V12 single 
132Thd of voltage V23 single 
134Thd of voltage V31 single 
136Thd of current I1 single 
138Thd of current l2 single 
140Thd of current l3 single 
692Max l1 demand single 
694Max l2 demand single 

This is not the complete map: 50 of 62 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Rayleigh Instruments (RI-F220) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Register addressing
input registers 30000-30xxx with hex addresses
Data format
2 registers per parameter (float)

Registers in the map: 78 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single, string(4).

MODBUS offsetDescriptionUnitsData typeScale
684Serial no. string(4) 
0Voltage v1nVsingle 
2Voltage v2nVsingle 
4Voltage v3nVsingle 
6Average voltage lnVsingle 
8Voltage V12Vsingle 
10Voltage V23Vsingle 
12Voltage V31Vsingle 
14Average voltage llVsingle 
16Current I1Asingle 
18Current I2Asingle 
20Current I3Asingle 
22Average currentAsingle 
24kW1 single 
26kW2 single 
28kW3 single 
30Kva1 single 
32Kva2 single 
34Kva3 single 
36Kvar1 single 
38Kvar2 single 
40Kvar3 single 
42TotalkWsingle 
44TotalkVAsingle 
46Totalkvarsingle 
48Pf1 single 
50Pf2 single 
52Pf3 single 
54Average pf single 
56FrequencyHzsingle 
58TotalkWhsingle 
60TotalkVAhsingle 
62Totalkvarhsingle 
64Kw max active power single 
66Kw min active power single 
68Kvarh max reactive power single 
70Kvarh min reactive power single 
72Kva max apparent power single 
74Max I1 demand single 
76Max I2 demand single 
78Max I3 demand single 
80Max avg. I demand single 
82Run hour single 
84Imp kwh1 single 
86Imp kwh2 single 
88Imp kwh3 single 
90Exp kwh1 single 
92Exp kwh2 single 
94Exp kwh3 single 
96Total impkWhsingle 

This is not the complete map: 50 of 78 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.