Connect Veris to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Veris data logger and record.
two registers per value (Float Reg MSW and Float Reg LSW)
Scale register
follows each float value pair
Registers in the map: 75 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.
MODBUS offset
Description
Units
Data type
Scale
10101
Total kwh (msw)
kWh
single
10109
Total
kW
single
10113
Total
kVA
single
10115
Total pf
PF
single
10119
Average current
A
single
10121
Present kw demand
kW
single
10127
Present current demand
A
single
10129
Max kw demand
kW
single
10135
Max current demand
A
single
10137
Max
kW
single
10143
Max current
A
single
10145
Voltage, L l, average of 3 phases
V
single
10147
Voltage, L n, average of 3 phases
V
single
10149
Frequency (derived from phase a)
Hz
single
10151
Thd current, weighted average of 3 phases
single
10153
Thd voltage L l, weighted average of 3 phases
single
10155
Thd voltage L n, weighted average of 3 phases
single
10157
Snapshot kwh (msw)
kWh
single
10301
Kwh (msw)
kWh
single
10309
Kw
kW
single
10313
Kva
kVA
single
10315
Pf
PF
single
10317
Current angle
degrees-angular
single
10319
Current
A
single
10321
Present kw demand
kW
single
10327
Present current demand
A
single
10329
Max kw demand
kW
single
10335
Max current demand
A
single
10337
Max
kW
single
10343
Max current
A
single
10345
Voltage, L L
V
single
10347
Voltage, L N
V
single
10349
Frequency (derived from phase a)
Hz
single
10351
Thd current
single
10353
Thd voltage L L
single
10355
Thd voltage L N
single
10357
Kwh snapshot (msw)
kWh
single
10501
Kwh (msw)
kWh
single
10509
Kw
kW
single
10513
Kva
kVA
single
10515
Pf
PF
single
10517
Current angle
degrees-angular
single
10519
Current
A
single
10521
Present kw demand
kW
single
10527
Present current demand
A
single
10529
Max kw demand
kW
single
10535
Max current demand
A
single
10537
Max
kW
single
10543
Max current
A
single
10545
Voltage, L L
V
single
This is not the complete map: 50 of 75 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 72 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, single, word.
MODBUS offset
Description
Units
Data type
Scale
1
Real energy consumption
kWh
dword
3
Total instantaneous real power (3 phase total)
kW
word
4
Total instantaneous reactive power (3 phase total)
kvar
word
5
Total instantaneous apparent power (3 phase total)
kVA
word
6
Total power factor (total kw /total kva)
Ratio
word
×0.0001
7
Voltage, L l, average of 3 phases
V
word
8
Voltage, L ii, average of 3 phases
V
word
9
Current, average of 3 phases
A
word
10
Real power, phase A
kW
word
11
Real power, phase B
kW
word
12
Real power, phase C
kW
word
13
Power factor, phase A
Ratio
word
×0.0001
14
Power factor, phase B
Ratio
word
×0.0001
15
Power factor, phase C
Ratio
word
×0.0001
16
Voltage, phase A B
V
word
17
Voltage, phase B C
V
word
18
Voltage, phase A C
V
word
19
Voltage, phase A N
V
word
20
Voltage, phase B N
V
word
21
Voltage, phase C N
V
word
22
Current, instantaneous, phase A
A
word
23
Current, instantaneous, phase B
A
word
24
Ljrrent, instantaneous, phase C
A
word
26
Frequency (derived from phase A)
Hz
word
×0.01
31
Apparent power phase A
kVA
word
32
Apparent power phase B
kVA
word
34
Reactive power, phase A
kvar
word
35
Reactive power, phase B
kvar
word
36
Reactive power, phase C
kvar
word
37
Total real power present demand
kW
word
38
Total reactive power present demand
kvar
word
39
Total apparent power present demand
kVA
word
40
Total real power max demand
kW
word
41
Total reactive power max demand
kvar
word
42
Total apparent power max demand
kVA
word
257
Real energy consumption (clear via reset register)
kWh
single
259
Real energy consumption (clear via reset register)
kWh
single
261
Total instantaneous real power
kW
single
263
Total instantaneous reactive power
kVAk
single
265
Total instantaneous apparent power
kVA
single
267
Total power factor (total kw / total kva)
Ratio
single
273
Current, average of 3 phases
A
single
275
Real power phase A
kW
single
277
Real power phase B
kW
single
279
Real power phase C
kW
single
281
Power factor phase A
Ratio
single
283
Power factor phase B
Ratio
single
285
Power factor phase C
Ratio
single
287
Voltage, phase A B
V
single
289
Voltage, phase B C
V
single
This is not the complete map: 50 of 72 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 147 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, integer, single, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
1
Real energy (diet import-export)
kWh
dword
3
Real energy (Q1-4 import)
kWh
dword
5
Real energy (Q2-3 import)
kWh
dword
7
Reactive energy Q1
kvarh
dword
9
Reactive energy Q2
kvarh
dword
11
Reactive energy Q3
kvarh
dword
13
Reactive energy Q4
kvarh
dword
15
Apparent energy: net (import export)
kVAh
integer
17
Apparent: Q1-4 import
kVAh
dword
19
Apparent: Q2-3 import
kVAh
dword
21
Total instantaneous real power
kW
smallint
22
Total instantaneous reactive power
kvar
smallint
23
Total instantaneous apparent power
kVA
word
24
Total power factor (total kw /total kva)
Ratio
smallint
×0.0001
25
Voltage L-L, average of active phases
V
word
27
Current, average of active phases
A
word
28
Frequency
Hz
word
×0.01
29
Total real power present demand
kW
smallint
30
Total reactive power present demand
kvar
smallint
31
Total apparent power present demand
kVA
smallint
32
Total real power max. demand
kW
smallint
33
Total reactive power max. demand
kvar
smallint
34
Total apparent power max. demand
kVA
smallint
35
Total real power max. demand
kW
smallint
36
Total reactive power max. demand
kvar
smallint
37
Total apparent power max. demand
kVA
smallint
39
Pulse counter 1 (import real energy)
dword
41
Pulse counter 2 (export real energy)
dword
43
Accumulated real energy, phase A
kWh
dword
45
Accumulated real energy, phase B
kWh
dword
47
Accumulated real energy, phase C
kWh
dword
49
Accumulated real energy, phase A
kWh
dword
51
Accumulated real energy, phase B
kWh
dword
53
Accumulated real energy, phase C
kWh
dword
55
Accumulated Q1 reactive energy phase A
kvarh
dword
57
Accumulated Q1 reactive energy phase B
kvarh
dword
59
Accumulated Q1 reactive energy phase C
kvarh
dword
61
Accumulated Q2 reactive energy phase A
kvarh
dword
63
Accumulated Q2 reactive energy phase B
kvarh
dword
65
Accumulated Q2 reactive energy phase C
kvarh
dword
67
Accumulated Q3 reactive energy phase A
kvarh
dword
69
Accumulated Q3 reactive energy phase B
kvarh
dword
71
Accumulated Q3 reactive energy phase C
kvarh
dword
73
Accumulated Q4 reactive energy phase A
kvarh
dword
75
Accumulated Q4 reactive energy phase B
kvarh
dword
77
Accumulated Q4 reactive energy phase C
kvarh
dword
79
Accumulated apparent energy, phase A
kVAh
dword
81
Accumulated apparent energy, phase B
kVAh
dword
83
Accumulated apparent energy, phase C
kVAh
dword
85
Accumulated apparent energy, phase A
kVAh
dword
This is not the complete map: 50 of 147 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.