Connect Veris to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Veris data logger and record.

Do you not know the meter address? Scan the device address online

Veris (E23) - MODBUS Registers

Registers in the map: 50. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
1537Real energy (ph) consumptionkWhsingle 
1539Reactive energy (qh) consumptionkvarhsingle 
1541Apparent energy (sh) consumptionkVAhsingle 
1543Total instantaneous real power (p)kWsingle 
1545Total instantaneous reactive power (q)kvarsingle 
1547Total instantaneous apparent power (s)kVAsingle 
1549Average power factor (pf: total kw / total kva)Ratiosingle 
1551Voltage line to line (u), average of active phasesVsingle 
1553Voltageline to neutral (v), average of active phasesVsingle 
1555Current, average of active phasesAsingle 
1557Frequency (derived from phase a, b, or C in that order)Hzsingle 
1559Total real power present demandkWsingle 
1561Total reactive power present demandkvarsingle 
1563Total apparent power present demandkVAsingle 
1565Total real power max demandkWsingle 
1567Total reactive power max demandkvarsingle 
1569Total apparent power max demandkVAsingle 
1577Pulse counter 1 (real energy) single 
1579Pulse counter 2 (reactive energy) single 
1589Real energy consumption, L1kWhsingle 
1591Real energy consumption, L2kWhsingle 
1593Real energy consumption, L3kWhsingle 
1595Reactive energy consumption, L1kWhsingle 
1597Reactive energy consumption, L2kWhsingle 
1599Reactive energy consumption, L3kWhsingle 
1601Apparent energy consumption, L1kWhsingle 
1603Apparent energy consumption, L2kWhsingle 
1605Apparent energy consumption, L3kWhsingle 
1607Real power, L1kWsingle 
1609Real power, L2kWsingle 
1611Real power, L3kWsingle 
1613Reactive power, L1kvarsingle 
1615Reactive power, L2kvarsingle 
1617Reactive power, L3kvarsingle 
1619Apparent power, L1kVAsingle 
1621Apparent power, L2kVAsingle 
1623Apparent power, L3kVAsingle 
1625Power factor, L1Ratiosingle 
1627Power factor, L2Ratiosingle 
1629Power factor, L3Ratiosingle 
1631Voltage, L1 L2Vsingle 
1633Voltage, L2 L3Vsingle 
1635Voltage, L3 L1Vsingle 
1637Voltage, L1 NVsingle 
1639Voltage, L2 NVsingle 
1641Voltage, L3 NVsingle 
1643Current, phase AAsingle 
1645Current, phase BAsingle 
1647Current, phase CAsingle 
1649Current, neutralAsingle 

Veris (E34) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Data format
32-bit float
Register layout
two registers per value (Float Reg MSW and Float Reg LSW)
Scale register
follows each float value pair

Registers in the map: 75 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
10101Total kwh (msw)kWhsingle 
10109TotalkWsingle 
10113TotalkVAsingle 
10115Total pfPFsingle 
10119Average currentAsingle 
10121Present kw demandkWsingle 
10127Present current demandAsingle 
10129Max kw demandkWsingle 
10135Max current demandAsingle 
10137MaxkWsingle 
10143Max currentAsingle 
10145Voltage, L l, average of 3 phasesVsingle 
10147Voltage, L n, average of 3 phasesVsingle 
10149Frequency (derived from phase a)Hzsingle 
10151Thd current, weighted average of 3 phases single 
10153Thd voltage L l, weighted average of 3 phases single 
10155Thd voltage L n, weighted average of 3 phases single 
10157Snapshot kwh (msw)kWhsingle 
10301Kwh (msw)kWhsingle 
10309KwkWsingle 
10313KvakVAsingle 
10315PfPFsingle 
10317Current angledegrees-angularsingle 
10319CurrentAsingle 
10321Present kw demandkWsingle 
10327Present current demandAsingle 
10329Max kw demandkWsingle 
10335Max current demandAsingle 
10337MaxkWsingle 
10343Max currentAsingle 
10345Voltage, L LVsingle 
10347Voltage, L NVsingle 
10349Frequency (derived from phase a)Hzsingle 
10351Thd current single 
10353Thd voltage L L single 
10355Thd voltage L N single 
10357Kwh snapshot (msw)kWhsingle 
10501Kwh (msw)kWhsingle 
10509KwkWsingle 
10513KvakVAsingle 
10515PfPFsingle 
10517Current angledegrees-angularsingle 
10519CurrentAsingle 
10521Present kw demandkWsingle 
10527Present current demandAsingle 
10529Max kw demandkWsingle 
10535Max current demandAsingle 
10537MaxkWsingle 
10543Max currentAsingle 
10545Voltage, L LVsingle 

This is not the complete map: 50 of 75 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Veris (E50) - MODBUS Values

Registers in the map: 72 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
1Real energy consumptionkWhdword 
3Total instantaneous real power (3 phase total)kWword 
4Total instantaneous reactive power (3 phase total)kvarword 
5Total instantaneous apparent power (3 phase total)kVAword 
6Total power factor (total kw /total kva)Ratioword×0.0001
7Voltage, L l, average of 3 phasesVword 
8Voltage, L ii, average of 3 phasesVword 
9Current, average of 3 phasesAword 
10Real power, phase AkWword 
11Real power, phase BkWword 
12Real power, phase CkWword 
13Power factor, phase ARatioword×0.0001
14Power factor, phase BRatioword×0.0001
15Power factor, phase CRatioword×0.0001
16Voltage, phase A BVword 
17Voltage, phase B CVword 
18Voltage, phase A CVword 
19Voltage, phase A NVword 
20Voltage, phase B NVword 
21Voltage, phase C NVword 
22Current, instantaneous, phase AAword 
23Current, instantaneous, phase BAword 
24Ljrrent, instantaneous, phase CAword 
26Frequency (derived from phase A)Hzword×0.01
31Apparent power phase AkVAword 
32Apparent power phase BkVAword 
34Reactive power, phase Akvarword 
35Reactive power, phase Bkvarword 
36Reactive power, phase Ckvarword 
37Total real power present demandkWword 
38Total reactive power present demandkvarword 
39Total apparent power present demandkVAword 
40Total real power max demandkWword 
41Total reactive power max demandkvarword 
42Total apparent power max demandkVAword 
257Real energy consumption (clear via reset register)kWhsingle 
259Real energy consumption (clear via reset register)kWhsingle 
261Total instantaneous real powerkWsingle 
263Total instantaneous reactive powerkVAksingle 
265Total instantaneous apparent powerkVAsingle 
267Total power factor (total kw / total kva)Ratiosingle 
273Current, average of 3 phasesAsingle 
275Real power phase AkWsingle 
277Real power phase BkWsingle 
279Real power phase CkWsingle 
281Power factor phase ARatiosingle 
283Power factor phase BRatiosingle 
285Power factor phase CRatiosingle 
287Voltage, phase A BVsingle 
289Voltage, phase B CVsingle 

This is not the complete map: 50 of 72 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Veris (E51) - Measurement Data

Registers in the map: 147 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, integer, single, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
1Real energy (diet import-export)kWhdword 
3Real energy (Q1-4 import)kWhdword 
5Real energy (Q2-3 import)kWhdword 
7Reactive energy Q1kvarhdword 
9Reactive energy Q2kvarhdword 
11Reactive energy Q3kvarhdword 
13Reactive energy Q4kvarhdword 
15Apparent energy: net (import export)kVAhinteger 
17Apparent: Q1-4 importkVAhdword 
19Apparent: Q2-3 importkVAhdword 
21Total instantaneous real powerkWsmallint 
22Total instantaneous reactive powerkvarsmallint 
23Total instantaneous apparent powerkVAword 
24Total power factor (total kw /total kva)Ratiosmallint×0.0001
25Voltage L-L, average of active phasesVword 
27Current, average of active phasesAword 
28FrequencyHzword×0.01
29Total real power present demandkWsmallint 
30Total reactive power present demandkvarsmallint 
31Total apparent power present demandkVAsmallint 
32Total real power max. demandkWsmallint 
33Total reactive power max. demandkvarsmallint 
34Total apparent power max. demandkVAsmallint 
35Total real power max. demandkWsmallint 
36Total reactive power max. demandkvarsmallint 
37Total apparent power max. demandkVAsmallint 
39Pulse counter 1 (import real energy) dword 
41Pulse counter 2 (export real energy) dword 
43Accumulated real energy, phase AkWhdword 
45Accumulated real energy, phase BkWhdword 
47Accumulated real energy, phase CkWhdword 
49Accumulated real energy, phase AkWhdword 
51Accumulated real energy, phase BkWhdword 
53Accumulated real energy, phase CkWhdword 
55Accumulated Q1 reactive energy phase Akvarhdword 
57Accumulated Q1 reactive energy phase Bkvarhdword 
59Accumulated Q1 reactive energy phase Ckvarhdword 
61Accumulated Q2 reactive energy phase Akvarhdword 
63Accumulated Q2 reactive energy phase Bkvarhdword 
65Accumulated Q2 reactive energy phase Ckvarhdword 
67Accumulated Q3 reactive energy phase Akvarhdword 
69Accumulated Q3 reactive energy phase Bkvarhdword 
71Accumulated Q3 reactive energy phase Ckvarhdword 
73Accumulated Q4 reactive energy phase Akvarhdword 
75Accumulated Q4 reactive energy phase Bkvarhdword 
77Accumulated Q4 reactive energy phase Ckvarhdword 
79Accumulated apparent energy, phase AkVAhdword 
81Accumulated apparent energy, phase BkVAhdword 
83Accumulated apparent energy, phase CkVAhdword 
85Accumulated apparent energy, phase AkVAhdword 

This is not the complete map: 50 of 147 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Veris (H8035,H8036) - MODBUS Values

Connection and addressing notes

Protocol
Modbus RTU
Function codes
03 read holding registers, 06 preset single register, 17 report slave ID
Data format
32-bit IEEE 754 float
Float register layout
MSW in the lower address of the pair, LSW in the upper
Byte order
MSB first
Register addressing
4xxxx Modicon convention, sent address is the shown value minus 40001 (40001 is sent as 0)
Block read
single block of all data, integers from 40001, floats from 40259

Registers in the map: 27. function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
256Energy consumptionkWhsingle 
258Energy onsumption (same 40257)kWhsingle 
260Real powerkWsingle 
262Reactive powervarsingle 
264Apparent powerYAsingle 
266Power fator single 
268Voltage, line to lineVsingle 
270Voltage, line to neutralVsingle 
272CurrentAsingle 
274Real power, phase AkWsingle 
276Real power, phase BkWsingle 
278Deal power, phase CkWsingle 
280Power factor, phase A single 
282Power factor, phase B single 
284Power factor, phase C single 
286Voltage, phase A BVsingle 
288Voltage, phase B CVsingle 
290Voltage, phase A CVsingle 
292Yoltage, phase A NVsingle 
294Voltage, phase B NVsingle 
296Voltage, phase C NVsingle 
298Current, phase AAsingle 
300Current, phase BAsingle 
302Current, phase CAsingle 
304Average real powerkWsingle 
306Minimum real powerkWsingle 
308Maximum real powerkWsingle 