Veris (E50) data logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
1 | Real energy consumption | kWh | dword |
3 | Total instantaneous real power (3 phase total) | kW | word |
4 | Total instantaneous reactive power (3 phase total) | kVAR | word |
5 | Total instantaneous apparent power (3 phase total) | KVA | word |
6 | Total power factor (total kw /total kva) | Ratio | word |
7 | Voltage, L l, average of 3 phases | Volt | word |
8 | Voltage, L ii, average of 3 phases | Volt | word |
9 | Current, average of 3 phases | Amp | word |
10 | Real power, phase A | kW | word |
11 | Real power, phase B | kW | word |
12 | Real power, phase C | kW | word |
13 | Power factor, phase A | Ratio | word |
14 | Power factor, phase B | Ratio | word |
15 | Power factor, phase C | Ratio | word |
16 | Voltage, phase A B | Volt | word |
17 | Voltage, phase B C | Volt | word |
18 | Voltage, phase A C | Volt | word |
19 | Voltage, phase A N | Volt | word |
20 | Voltage, phase B N | Volt | word |
21 | Voltage, phase C N | Volt | word |
22 | Current, instantaneous, phase A | Amp | word |
23 | Current, instantaneous, phase B | Amp | word |
24 | Ljrrent, instantaneous, phase C | Amp | word |
26 | Frequency (derived from phase A) | Hz | word |
31 | Apparent power phase A | KVA | word |
32 | Apparent power phase B | KVA | word |
34 | Reactive power, phase A | kVAR | word |
35 | Reactive power, phase B | kVAR | word |
36 | Reactive power, phase C | kVAR | word |
37 | Total real power present demand | kW | word |
38 | Total reactive power present demand | kVAR | word |
39 | Total apparent power present demand | KVA | word |
40 | Total real power max demand | kW | word |
41 | Total reactive power max demand | kVAR | word |
42 | Total apparent power max demand | KVA | word |
257 | Real energy consumption (clear via reset register) | kWh | single |
259 | Real energy consumption (clear via reset register) | kWh | single |
261 | Total instantaneous real power | kW | single |
263 | Total instantaneous reactive power | kVAk | single |
265 | Total instantaneous apparent power | kVA | single |
267 | Total power factor (total kw / total kva) | Ratio | single |
273 | Current, average of 3 phases | Amp | single |
275 | Real power phase A | kW | single |
277 | Real power phase B | kW | single |
279 | Real power phase C | kW | single |
281 | Power factor phase A | Ratio | single |
283 | Power factor phase B | Ratio | single |
285 | Power factor phase C | Ratio | single |
287 | Voltage, phase A B | Volt | single |
289 | Voltage, phase B C | Volt | single |
There are more MODBUS items for this device. Please, download the program. |