Veris (E50) data logger. MODBUS registers map.


This data is being extracted with help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
1Real energy consumptionkWhdword
3Total instantaneous real power (3 phase total)kWword
4Total instantaneous reactive power (3 phase total)kVARword
5Total instantaneous apparent power (3 phase total)KVAword
6Total power factor (total kw /total kva)Ratioword
7Voltage, L l, average of 3 phasesVoltword
8Voltage, L ii, average of 3 phasesVoltword
9Current, average of 3 phasesAmpword
10Real power, phase AkWword
11Real power, phase BkWword
12Real power, phase CkWword
13Power factor, phase ARatioword
14Power factor, phase BRatioword
15Power factor, phase CRatioword
16Voltage, phase A BVoltword
17Voltage, phase B CVoltword
18Voltage, phase A CVoltword
19Voltage, phase A NVoltword
20Voltage, phase B NVoltword
21Voltage, phase C NVoltword
22Current, instantaneous, phase AAmpword
23Current, instantaneous, phase BAmpword
24Ljrrent, instantaneous, phase CAmpword
26Frequency (derived from phase A)Hzword
31Apparent power phase AKVAword
32Apparent power phase BKVAword
34Reactive power, phase AkVARword
35Reactive power, phase BkVARword
36Reactive power, phase CkVARword
37Total real power present demandkWword
38Total reactive power present demandkVARword
39Total apparent power present demandKVAword
40Total real power max demandkWword
41Total reactive power max demandkVARword
42Total apparent power max demandKVAword
257Real energy consumption (clear via reset register)kWhsingle
259Real energy consumption (clear via reset register)kWhsingle
261Total instantaneous real powerkWsingle
263Total instantaneous reactive powerkVAksingle
265Total instantaneous apparent powerkVAsingle
267Total power factor (total kw / total kva)Ratiosingle
273Current, average of 3 phasesAmpsingle
275Real power phase AkWsingle
277Real power phase BkWsingle
279Real power phase CkWsingle
281Power factor phase ARatiosingle
283Power factor phase BRatiosingle
285Power factor phase CRatiosingle
287Voltage, phase A BVoltsingle
289Voltage, phase B CVoltsingle
291Voltage, phase A CVoltsingle
293Voltage, phase A NVoltsingle
295Voltage, phase B NVoltsingle
297Voltage, phase C NVoltsingle
299Current, instantaneous, phase AAmpsingle
301Current, instantaneous, phase BAIIIpsingle
303Current, instantaneous, phase CAmpsingle
307Frequency (derived from phase a)Hzsingle
309Apparent energy consumptionkYAhsingle
311Reactive energy consumptionkYARhsingle
313Apparent power, phase AkYAsingle
315Apparent power, phase BkYAsingle
317Apparent power, phase CkYAsingle
319Reactive power, phase AkYARsingle
321Reactive power, phase BkYARsingle
323Reactive power, phase CkYARsingle
325Total real (power present demand)kWsingle
327Total reactive (power present demand)kYARsingle
329Total apparent (power present demand)kYAsingle
331Total real (power max demand)kWsingle
333Total reactive (power max demand)kYARsingle
335Total apparent (power max demand)kYAsingle