Connection and addressing notes
- Protocol
- Modbus
- Function codes
- 0x03 read holding, 0x05 force single coil, 0x10 preset multiple registers for device programming
- Register addressing
- response tables use 4xxxx holding registers and 0xxxx coils
- Protocol version
- 6.0
Registers in the map: 65 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|---|---|---|---|
| 40000 | UL1 | V | dword | ×0.01 |
| 40002 | UL2 | V | dword | ×0.01 |
| 40004 | UL3 | V | dword | ×0.01 |
| 40006 | ULN | V | dword | ×0.01 |
| 40008 | UL1L2 | V | dword | ×0.01 |
| 40010 | UL2L3 | V | dword | ×0.01 |
| 40012 | UL3LI | V | dword | ×0.01 |
| 40014 | ULL | V | dword | ×0.01 |
| 40016 | I1 | A | dword | ×0.001 |
| 40018 | I2 | A | dword | ×0.001 |
| 40020 | I3 | A | dword | ×0.001 |
| 40022 | IN | A | dword | ×0.001 |
| 40024 | PL1 | kW | integer | ×0.001 |
| 40026 | PL2 | kW | integer | ×0.001 |
| 40028 | PL3 | kW | integer | ×0.001 |
| 40030 | Pges | kW | integer | ×0.001 |
| 40032 | QL1 | kvar | integer | ×0.001 |
| 40034 | QL2 | kvar | integer | ×0.001 |
| 40036 | QL3 | kvar | integer | ×0.001 |
| 40038 | Qges | kvar | integer | ×0.001 |
| 40040 | SL1 | kVA | integer | ×0.001 |
| 40042 | SL2 | kVA | integer | ×0.001 |
| 40044 | SL3 | kVA | integer | ×0.001 |
| 40046 | Sges | kVA | integer | ×0.001 |
| 40048 | PF L1 | smallint | ×0.001 | |
| 40049 | PF L2 | smallint | ×0.001 | |
| 40050 | PF L3 | smallint | ×0.001 | |
| 40051 | PF ges | smallint | ×0.001 | |
| 40052 | F | word | ×0.01 | |
| 40053 | I4 | A | dword | ×0.001 |
| 40055 | Voltage unbalance | word | ×0.001 | |
| 40056 | Current unbalance | word | ×0.001 | |
| 40057 | Displacement factor L1 | smallint | ×0.001 | |
| 40058 | Displacement factor L2 | smallint | ×0.001 | |
| 40059 | Displacement factor L3 | smallint | ×0.001 | |
| 40060 | Demand P | kW | integer | ×0.001 |
| 40062 | Demand Q | kvar | integer | ×0.001 |
| 40064 | Demand S | kVA | integer | ×0.001 |
| 40066 | Demand I1 | A | dword | ×0.001 |
| 40068 | Demand I2 | A | dword | ×0.001 |
| 40070 | Demand I3 | A | dword | ×0.001 |
| 40072 | Phase angle U1 | deg | word | ×0.01 |
| 40073 | Phase angle U2 | deg | word | ×0.01 |
| 40074 | Phase angle U3 | deg | word | ×0.01 |
| 40075 | Phase angle I1 | deg | word | ×0.01 |
| 40076 | Phase angle I2 | deg | word | ×0.01 |
| 40077 | Phase angle I3 | deg | word | ×0.01 |
| 40095 | Alarm | word | ||
| 40096 | Status digital outputs | word | ||
| 40097 | Status digital inputs | word |
This is not the complete map: 50 of 65 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.