bg

Finder Series 7E, 7E64, 7E68, 7E78 MODBUS registers: read online

Connect Finder to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Finder modbus logging and log.

Do you not know the meter address? Scan the device address online

Finder (Series 7E,7E64,7E68,7E78,7E86) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Function codes
03 and 04 read registers
Register blocks
separate blocks for the three-phase, single-phase and tariff-counter model variants

Registers in the map: 165 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
4096Ph 1 N voltageVsingle 
4098Ph 2 N voltageVsingle 
4100Ph 3 N voltageVsingle 
4102L 1 2 voltageVsingle 
4104L 2 3 voltageVsingle 
4106L 3 1 voltageVsingle 
4108System voltageVsingle 
4110Ph1 currentAsingle 
4112Ph2 currentAsingle 
4114Ph3 currentAsingle 
4116Neutral currentAsingle 
4118System currentAsingle 
4120Ph1 power factor single 
4122Ph2 power factor single 
4124Ph3 power factor single 
4126Sys power factor single 
4128Ph1 active powerWsingle 
4130Ph2 active powerWsingle 
4132Ph3 active powerWsingle 
4134Sys active powerWsingle 
4136Ph1 appare nt powerVAsingle 
4138Ph2 apparent powerVAsingle 
4140Ph3 apparent powerVAsingle 
4142Sys apparent powerVAsingle 
4144Ph1 reactive powervarsingle 
4146Ph2 reactive powervarsingle 
4148Ph3 reactive powervarsingle 
4150Sys reactive powervarsingle 
4152FrequencyHzsingle 
4154Phase seque nce single 
4352Ph1 imp. Active enWhsingle 
4354Ph2 imp. Active enWhsingle 
4356Ph3 imp. Active enWhsingle 
4358Sys imp. Active enWhsingle 
4360Ph1 exp. Active enWhsingle 
4362Ph2 exp. Active enWhsingle 
4364Ph3 exp. Active enWhsingle 
4366Sys exp. Active enWhsingle 
4368Ph1 imp. Lag. Apparent enVAhsingle 
4370Ph2 imp. Lag. Apparent enVAhsingle 
4372Ph3 imp. Lag. Apparent enVAhsingle 
4374Sys imp. Lag. Apparent enVAhsingle 
4376Ph1 exp. Lag. Apparent enVAhsingle 
4378Ph2 exp. Lag. Apparent enVAhsingle 
4380Ph3 exp. Lag. Apparent enVAhsingle 
4382Sys exp. Lag. Apparent enVAhsingle 
4384Ph1 imp. Lead. Apparent enVAhsingle 
4386Ph2 imp. Lead. Apparent enVAhsingle 
4388Ph3 imp. Lead. Apparent enVAhsingle 
4390Sys imp. Lead. Apparent enVAhsingle 

This is not the complete map: 50 of 165 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection