Hypontech HPK, HPS, HPT, HHS MODBUS registers: read online

Connect Hypontech to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Hypontech logging and read.

Do you not know the meter address? Scan the device address online

Hypontech (HPK,HPS,HPT,HHS) - Measurement Data

Connection and addressing notes

Protocol
Modbus RTU
Interface
RS-485, 2-wire (RS485 2W cabling)
Default baud rate
9600
Data bits
8
Parity
N/A
Device address range
1-16
Frame format
Modbus RTU
Register addressing
3xxxx numbers with hex equivalent (e.g. 30000 = 0x7530)

Registers in the map: 66 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, integer, single, smallint, string(14), string(16), word.

MODBUS offsetDescriptionUnitsData typeScale
30000Firmware part string(14) 
30018Model name string(16) 
30034Device type word 
30037Hardware version dwordformula
30039Software version dwordformula
30041Protocol version dwordformula
30043Parameter version dwordformula
30010Manufacturer name string(16) 
30026Serial number string(16) 
30035Grid type word 
30036Rated power word 
30047Max. Apparent powerVAword 
30048No. MPPT word 
30100Output PWinteger 
30102Output SVAinteger 
30104Output Qvarinteger 
30106OutputPFword×0.01
30107Q/PF direction word 
30108Meter powerWinteger 
30110E-todayIKWHword 
30111E-totalkWhdword 
30113H-totalHzdword 
30115Inverter state word 
30116Waiting time word 
30119PVI voltageVword×0.1
30120PVI currentAword×0.1
30121PV2 voltageVword×0.1
30122PV2 currentAword×0.1
30123PV3 voltageVword×0.1
30124PV3 currentAword×0.1
30125PV4 voltageVword×0.1
30126PV4 currentAword×0.1
30127Reserve word 
30128Reserve integer×14
30130Reserve word 
30131Grid R voltageVword×0.1
30132Grid R currentAword×0.1
30133Grid S voltageVword×0.1
30134Grid S currentAword×0.1
30135Grid T voltageVword×0.1
30136Grid T currentAword×0.1
30139Grid line voltage TR word 
30154E-totalkWhsingle 
30156Import energy from meterkWhsingle 
30158Export energy from meterkWhsingle 
30160Substate word 
30161BatSt word 
30162WchaWinteger 
30164BatVVword×0.1
30165BatAAsmallint×0.1

This is not the complete map: 50 of 66 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.