Connect IME to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous IME data logger and record.
Do you not know the meter address? Scan the device address online
IME (Nemo D4-LE) - MODBUS Measurements
Connection and addressing notes
- Protocol
- Modbus
- Register addressing
- hexadecimal addresses (e.g. 0x1000)
Registers in the map: 193 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 4612 | Device identifier | | word | |
| 4096 | Phase 1 : phase voltage | V | dword | ×0.001 |
| 4098 | Phase 2 : phase voltage | V | dword | ×0.001 |
| 4100 | Phase 3 : phase voltage | V | dword | ×0.001 |
| 4102 | Phase 1 : current | A | dword | ×0.001 |
| 4104 | Phase 2 : current | A | dword | ×0.001 |
| 4106 | Phase 3 : current | A | dword | ×0.001 |
| 4108 | Neutral current | A | dword | ×0.001 |
| 4110 | Chained voltage : L1 L2 | V | dword | ×0.001 |
| 4112 | Chained voltage : L2 L3 | V | dword | ×0.001 |
| 4114 | Chained voltage : L3 L1 | V | dword | ×0.001 |
| 4116 | 3 phase : active power | W/var/VA | dword | |
| 4118 | 3 phase : reactive power | W/var/VA | dword | |
| 4120 | 3 phase : apparent power | W/var/VA | dword | |
| 4122 | 3 phase : sign of active power | | word | |
| 4123 | 3 phase : sign of reactive power | | word | |
| 4124 | 3 phase : positive active energy | Wh | dword | |
| 4126 | 3 phase : positive reactive energy | Wh | dword | |
| 4128 | 3 phase : negative active energy | Wh | dword | |
| 4130 | 3 phase : negative reactive energy | Wh | dword | |
| 4132 | 3 phase : power factor | s | smallint | ×0.01 |
| 4133 | 3 phase : sector of power factor (cap or ind) | a | word | |
| 4134 | Frequency | Hz | word | ×0.1 |
| 4135 | 3 phase : average power | W/var/VA | dword | |
| 4137 | 3 phase : peak maximum demand | W/var/VA | dword | |
| 4139 | Time counter for average power | min | word | |
| 4140 | Phase 1 : active power | W/var/VA | dword | |
| 4142 | Phase 2 : active power | W/var/VA | dword | |
| 4144 | Phase 3 : active power | W/var/VA | dword | |
| 4146 | Phase 1 : sign of active power | | word | |
| 4147 | Phase 2 : sign of active power | | word | |
| 4148 | Phase 3 : sign of active power | | word | |
| 4149 | Phase 1 : reactive power | W/var/VA | dword | |
| 4151 | Phase 2 : reactive power | W/var/VA | dword | |
| 4153 | Phase 3 : reactive power | W/var/VA | dword | |
| 4155 | Phase 1 : sign of reactive power | | word | |
| 4156 | Phase 2 : sign of reactive power | | word | |
| 4157 | Phase 3 : sign of reactive power | | word | |
| 4158 | Phase 1 : apparent power | W/var/VA | dword | |
| 4160 | Phase 2 : apparent power | W/var/VA | dword | |
| 4162 | Phase 3 : apparent power | W/var/VA | dword | |
| 4164 | Phase 1 : power factor | s | smallint | ×0.01 |
| 4165 | Phase 2 : power factor | s | smallint | ×0.01 |
| 4166 | Phase 3 : power factor | s | smallint | ×0.01 |
| 4167 | Phase 1 : power factor sector | a | word | |
| 4168 | Phase 2 : power factor sector | a | word | |
| 4169 | Phase 3 : power factor sector | a | word | |
| 4170 | Phase 1 : thd V1 | % | word | |
| 4171 | Phase 2 : thd V2 | % | word | |
| 4172 | Phase 3 : thd V3 | % | word | |
This is not the complete map: 50 of 193 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
IME (Nemo D4-LP) - MODBUS Measurements
Connection and addressing notes
- Register addressing
- hexadecimal addresses (e.g. 0x1000)
- Second address table
- starts at 0x1000, available at any time
Registers in the map: 105 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 768 | Device identifier | | word | |
| 4614 | Device identifier | | word | |
| 769 | Phase 1 : phase voltage | V | dword | ×0.001 |
| 773 | Phase 2 : phase voltage | V | dword | ×0.001 |
| 777 | Phase 3 : phase voltage | V | dword | ×0.001 |
| 781 | Phase 1 : current | A | dword | ×0.001 |
| 785 | Phase 2 : current | A | dword | ×0.001 |
| 789 | Phase 3 : current | A | dword | ×0.001 |
| 793 | 3 phase : active power | W/var/VA | dword | |
| 797 | 3 phase : reactive power | W/var/VA | dword | |
| 801 | 3 phase : apparent power | W/var/VA | dword | |
| 805 | 3 phase : positive active energy | Wh | dword | |
| 809 | Chained voltage : L1 L2 | V | dword | ×0.001 |
| 813 | Chained voltage : L2 L3 | V | dword | ×0.001 |
| 817 | Chained voltage : L3 L1 | V | dword | ×0.001 |
| 821 | 3 phase : partial positive active energy | Wh | dword | |
| 825 | Frequency | Hz | word | |
| 829 | 3 phase : power factor | | word | |
| 831 | 3 phase : sector of power factor (cap or ind) | | word | |
| 835 | 3 phase : positive reactive energy | Wh | dword | |
| 839 | 3 phase : sign of active power | | word | |
| 840 | Time counter | s | dword | |
| 844 | 3 phase : sign of reactive power | | word | |
| 848 | 3 phase : average power | W/var/VA | dword | |
| 852 | 3 phase : peak maximum demand | W/var/VA | dword | |
| 856 | Time counter for average power | min | word | |
| 857 | Neutro current | A | dword | ×0.001 |
| 861 | Phase 1 : active power | W/var/VA | dword | |
| 865 | Phase 2 : active power | W/var/VA | dword | |
| 869 | Phase 3 : active power | W/var/VA | dword | |
| 873 | Phase 1 : sign of active power | | word | |
| 874 | Phase 2 : sign of active power | | word | |
| 875 | Phase 3 : sign of active power | | word | |
| 876 | Phase 1 : reactive power | W/var/VA | dword | |
| 880 | Phase 2 : reactive power | W/var/VA | dword | |
| 884 | Phase 3 : reactive power | W/var/VA | dword | |
| 888 | Phase 1 : sign of reactive power | | word | |
| 889 | Phase 2 : sign of reactive power | | word | |
| 890 | Phase 3 : sign of reactive power | | word | |
| 891 | Phase 1 : average current | A | dword | ×0.001 |
| 895 | Phase 2 : average current | A | dword | ×0.001 |
| 899 | Phase 3 : average current | A | dword | ×0.001 |
| 903 | Phase 1 : current maximum demand | A | dword | ×0.001 |
| 907 | Phase 2 : current maximum demand | A | dword | ×0.001 |
| 911 | Phase 3 : current maximum demand | A | dword | ×0.001 |
| 915 | Phase 1 : thd voltage | % | word | |
| 917 | Phase 2 : thd voltage | % | word | |
| 919 | Phase 3 : thd voltage | % | word | |
| 921 | Phase 1 : thd current | % | word | |
| 922 | Phase 2 : thd current | % | word | |
This is not the complete map: 50 of 105 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Related MODBUS registers maps
MODBUS Maps Index
IME (Nemo D4-DC)
I-Real (WS0101)
Inepro Metering (PRO1)
Integra Ci1
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.