Connect IME to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous IME data logger and record.

Do you not know the meter address? Scan the device address online

IME (Nemo D4-LE) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Register addressing
hexadecimal addresses (e.g. 0x1000)

Registers in the map: 193 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
4612Device identifier word 
4096Phase 1 : phase voltageVdword×0.001
4098Phase 2 : phase voltageVdword×0.001
4100Phase 3 : phase voltageVdword×0.001
4102Phase 1 : currentAdword×0.001
4104Phase 2 : currentAdword×0.001
4106Phase 3 : currentAdword×0.001
4108Neutral currentAdword×0.001
4110Chained voltage : L1 L2Vdword×0.001
4112Chained voltage : L2 L3Vdword×0.001
4114Chained voltage : L3 L1Vdword×0.001
41163 phase : active powerW/var/VAdword 
41183 phase : reactive powerW/var/VAdword 
41203 phase : apparent powerW/var/VAdword 
41223 phase : sign of active power word 
41233 phase : sign of reactive power word 
41243 phase : positive active energyWhdword 
41263 phase : positive reactive energyWhdword 
41283 phase : negative active energyWhdword 
41303 phase : negative reactive energyWhdword 
41323 phase : power factorssmallint×0.01
41333 phase : sector of power factor (cap or ind)aword 
4134FrequencyHzword×0.1
41353 phase : average powerW/var/VAdword 
41373 phase : peak maximum demandW/var/VAdword 
4139Time counter for average powerminword 
4140Phase 1 : active powerW/var/VAdword 
4142Phase 2 : active powerW/var/VAdword 
4144Phase 3 : active powerW/var/VAdword 
4146Phase 1 : sign of active power word 
4147Phase 2 : sign of active power word 
4148Phase 3 : sign of active power word 
4149Phase 1 : reactive powerW/var/VAdword 
4151Phase 2 : reactive powerW/var/VAdword 
4153Phase 3 : reactive powerW/var/VAdword 
4155Phase 1 : sign of reactive power word 
4156Phase 2 : sign of reactive power word 
4157Phase 3 : sign of reactive power word 
4158Phase 1 : apparent powerW/var/VAdword 
4160Phase 2 : apparent powerW/var/VAdword 
4162Phase 3 : apparent powerW/var/VAdword 
4164Phase 1 : power factorssmallint×0.01
4165Phase 2 : power factorssmallint×0.01
4166Phase 3 : power factorssmallint×0.01
4167Phase 1 : power factor sectoraword 
4168Phase 2 : power factor sectoraword 
4169Phase 3 : power factor sectoraword 
4170Phase 1 : thd V1%word 
4171Phase 2 : thd V2%word 
4172Phase 3 : thd V3%word 

This is not the complete map: 50 of 193 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

IME (Nemo D4-LP) - MODBUS Measurements

Connection and addressing notes

Register addressing
hexadecimal addresses (e.g. 0x1000)
Second address table
starts at 0x1000, available at any time

Registers in the map: 105 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
768Device identifier word 
4614Device identifier word 
769Phase 1 : phase voltageVdword×0.001
773Phase 2 : phase voltageVdword×0.001
777Phase 3 : phase voltageVdword×0.001
781Phase 1 : currentAdword×0.001
785Phase 2 : currentAdword×0.001
789Phase 3 : currentAdword×0.001
7933 phase : active powerW/var/VAdword 
7973 phase : reactive powerW/var/VAdword 
8013 phase : apparent powerW/var/VAdword 
8053 phase : positive active energyWhdword 
809Chained voltage : L1 L2Vdword×0.001
813Chained voltage : L2 L3Vdword×0.001
817Chained voltage : L3 L1Vdword×0.001
8213 phase : partial positive active energyWhdword 
825FrequencyHzword 
8293 phase : power factor word 
8313 phase : sector of power factor (cap or ind) word 
8353 phase : positive reactive energyWhdword 
8393 phase : sign of active power word 
840Time countersdword 
8443 phase : sign of reactive power word 
8483 phase : average powerW/var/VAdword 
8523 phase : peak maximum demandW/var/VAdword 
856Time counter for average powerminword 
857Neutro currentAdword×0.001
861Phase 1 : active powerW/var/VAdword 
865Phase 2 : active powerW/var/VAdword 
869Phase 3 : active powerW/var/VAdword 
873Phase 1 : sign of active power word 
874Phase 2 : sign of active power word 
875Phase 3 : sign of active power word 
876Phase 1 : reactive powerW/var/VAdword 
880Phase 2 : reactive powerW/var/VAdword 
884Phase 3 : reactive powerW/var/VAdword 
888Phase 1 : sign of reactive power word 
889Phase 2 : sign of reactive power word 
890Phase 3 : sign of reactive power word 
891Phase 1 : average currentAdword×0.001
895Phase 2 : average currentAdword×0.001
899Phase 3 : average currentAdword×0.001
903Phase 1 : current maximum demandAdword×0.001
907Phase 2 : current maximum demandAdword×0.001
911Phase 3 : current maximum demandAdword×0.001
915Phase 1 : thd voltage%word 
917Phase 2 : thd voltage%word 
919Phase 3 : thd voltage%word 
921Phase 1 : thd current%word 
922Phase 2 : thd current%word 

This is not the complete map: 50 of 105 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.