Janitza UMG604, UMG605, UMG96 MODBUS registers: read online

Connect Janitza to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Janitza data logger and record.

Do you not know the meter address? Scan the device address online

Janitza (UMG604) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus RTU
Interface
RS485 and RS232
Device address register
10180
Protocol register
10182, Modbus RTU slave or master
RS485 baud rate register
10184
RS232 baud rate register
10186
RS232 protocol register
10188, Modbus RTU slave
Ethernet Modbus
can be disabled by register 14183
Register addressing
bus register numbers used directly as map offsets

Registers in the map: 375 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single, string(128), string(16), string(64).

MODBUS offsetDescriptionUnitsData typeScale
13437Firmware release string(16) 
19000Voltage L1 NVsingle 
19002Voltage L2 NVsingle 
19004Voltage L3 NVsingle 
19006Voltage L1 L2Vsingle 
19008Voltage L2 L3Vsingle 
19010Voltage L3 L1Vsingle 
19012Apparent current, L1 NAsingle 
19014Apparent current, L2 NAsingle 
19016Apparent current, L3 NAsingle 
19018Vector sum; in=i1+i2+i3Asingle 
19020Real power L1 NWsingle 
19022Real power L2 NWsingle 
19024Real power L3 NWsingle 
19026Psum3=p1+p2+p3Wsingle 
19028Apparent power L1 NVAsingle 
19030Apparent power L2 NVAsingle 
19032Apparent power L3 NVAsingle 
19034Sum; ssum3=s1+s2+s3VAsingle 
19036Reactive power L1 (fundamental comp.)varsingle 
19038Reactive power L2 (fundamental comp.)varsingle 
19040Reactive power L3 (fundamental comp.)varsingle 
19042Qsum3=Q1+Q2+Q3 (fundamental comp.)varsingle 
19044Cosphi; UL1 IL1 (fundamental comp.) single 
19046Cosphi; UL2 IL2 (fundamental comp.) single 
19048Cosphi; UL3 IL3 (fundamental comp.) single 
19050Measured frequencyHzsingle 
19052Rotation field single 
19054Real energy L1Whsingle 
19056Real energy L2Whsingle 
19058Real energy L3Whsingle 
19060Real energy l1..l3Whsingle 
19062Real energy l1, consumedWhsingle 
19064Real energy l2, consumedWhsingle 
19066Real energy l3, consumedWhsingle 
19068Real energy l1..l3, consumed, rate 1Whsingle 
19070Real energy l1, deliveredWhsingle 
19072Real energy l2, deliveredWhsingle 
19074Real energy l3, deliveredWhsingle 
19076Real energy l1..l3, deliveredWhsingle 
19078Apparent energy L1VAhsingle 
19080Apparent energy L2VAhsingle 
19082Apparent energy L3VAhsingle 
19084Apparent energy l1..l3VAhsingle 
19086Reaktive energy L1 (fundamental comp.)varhsingle 
19088Reaktive energy L2 (fundamental comp.)varhsingle 
19090Reaktive energy L3 (fundamental comp.)varhsingle 
19092Reaktive energy l1..l3 (fundamental comp.)varhsingle 
19094Reactive energy, inductive, L1 (fundamental comp.)varhsingle 
19096Reactive energy, inductive, L2 (fundamental comp.)varhsingle 

This is not the complete map: 50 of 375 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Janitza (UMG605) - MODBUS Registers Map

Registers in the map: 568 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
19000Voltage L1 NVsingle 
19002Voltage L2 NVsingle 
19004Voltage L3 NVsingle 
19006Voltage L1 L2Vsingle 
19008Voltage L2 L3Vsingle 
19010Voltage L3 L1Vsingle 
19012Apparent current, L1 NAsingle 
19014Apparent current, L2 NAsingle 
19016Apparent current, L3 NAsingle 
19018Vector sum; in=i1+i2+i3Asingle 
19020Real power L1 NWsingle 
19022Real power L2 NWsingle 
19024Real power L3 NWsingle 
19026Psum3=p1+p2+p3Wsingle 
19028Apparent power L1 NVAsingle 
19030Apparent power L2 NVAsingle 
19032Apparent power L3 NVAsingle 
19034Sum; ssum3=s1+s2+s3VAsingle 
19036Reactive power L1 (fundamental comp.)varsingle 
19038Reactive power L2 (fundamental comp.)varsingle 
19040Reactive power L3 (fundamental comp.)varsingle 
19042Qsum3=Q1+Q2+Q3 (fundamental comp.)varsingle 
19044Cosphi; UL1 IL1 (fundamental comp.) single 
19046Cosphi; UL2 IL2 (fundamental comp.) single 
19048Cosphi; UL3 IL3 (fundamental comp.) single 
19050Measured frequencyHzsingle 
19052Rotation field single 
19054Real energy L1Whsingle 
19056Real energy L2Whsingle 
19058Real energy L3Whsingle 
19060Real energy l1..l3Whsingle 
19062Real energy l1, consumedWhsingle 
19064Real energy l2, consumedWhsingle 
19066Real energy l3, consumedWhsingle 
19068Real energy l1..l3, consumed, rate 1Whsingle 
19070Real energy l1, deliveredWhsingle 
19072Real energy l2, deliveredWhsingle 
19074Real energy l3, deliveredWhsingle 
19076Real energy l1..l3, deliveredWhsingle 
19078Apparent energy L1VAhsingle 
19080Apparent energy L2VAhsingle 
19082Apparent energy L3VAhsingle 
19084Apparent energy l1..l3VAhsingle 
19086Reaktive energy L1 (fundamental comp.)varhsingle 
19088Reaktive energy L2 (fundamental comp.)varhsingle 
19090Reaktive energy L3 (fundamental comp.)varhsingle 
19092Reaktive energy l1..l3 (fundamental comp.)varhsingle 
19094Reactive energy, inductive, L1 (fundamental comp.)varhsingle 
19096Reactive energy, inductive, L2 (fundamental comp.)varhsingle 
19098Reactive energy, inductive, L3 (fundamental comp.)varhsingle 

This is not the complete map: 50 of 568 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Janitza (UMG96) - MODBUS Registers Map

Registers in the map: 512 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
19000Voltage L1 NVsingle 
19002Voltage L2 NVsingle 
19004Voltage L3 NVsingle 
19006Voltage L1 L2Vsingle 
19008Voltage L2 L3Vsingle 
19010Voltage L1 L3Vsingle 
19012Current I L1Asingle 
19014Current I L2Asingle 
19016Current I L3Asingle 
19018Vector sum; in=i1+i2+i3Asingle 
19020Real power P1 l1nWsingle 
19022Real power P2 l2nWsingle 
19024Real power P3 l3nWsingle 
19026Sum; psum3=p1+p2+p3Wsingle 
19028Apparent power S1 l1nVAsingle 
19030Apparent power S2 l2nVAsingle 
19032Apparent power S3 l3nVAsingle 
19034Sum; ssum3=s1+s2+s3VAsingle 
19036Fund. reactive power Q1 l1nvarsingle 
19038Fund. reactive power Q2 l2nvarsingle 
19040Fund. reactive power Q3 l3nvarsingle 
19042Sum; qsum3=Q1+Q2+Q3varsingle 
19044Cosphi; UL1 IL1 (fundamental comp.) single 
19046Cosphi; UL2 IL2 (fundamental comp.) single 
19048Cosphi; UL3 IL3 (fundamental comp.) single 
19050Measured frequencyHzsingle 
19052Rotation field single 
19054Real energy L1Whsingle 
19056Real energy L2Whsingle 
19058Real energy L3Whsingle 
19060Real energy l1..l3Whsingle 
19062Real energy l1, consumedWhsingle 
19064Real energy l2, consumedWhsingle 
19066Real energy l3, consumedWhsingle 
19068Real energy l1..l3, consumed, rate 1Whsingle 
19070Real energy l1, deliveredWhsingle 
19072Real energy l2, deliveredWhsingle 
19074Real energy l3, deliveredWhsingle 
19076Real energy l1..l3, deliveredWhsingle 
19078Apparent energy L1VAhsingle 
19080Apparent energy L2VAhsingle 
19082Apparent energy L3VAhsingle 
19084Apparent energy l1..l3VAhsingle 
19086Reactive energy L1varhsingle 
19088Reactive energy L2varhsingle 
19090Reactive energy L3varhsingle 
19092Reactive energy l1..l3varhsingle 
19094Reactive energy ind. L1varhsingle 
19096Reactive energy ind. L2varhsingle 
19098Reactive energy ind. L3varhsingle 

This is not the complete map: 50 of 512 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.