Schneider Electric PowerLogic PowerLogic ION8300, ION8400 MODBUS registers: read online
Connect Schneider Electric PowerLogic to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Schneider Electric PowerLogic data logging and capture.
Registers in the map: 131 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
10
Vln a 1, Volts/Amps/Freq
word
×0.1
11
Vln b 1, Volts/Amps/Freq
word
×0.1
12
Vln c 1, Volts/Amps/Freq
word
×0.1
13
Vln avg 1, Volts/Amps/Freq
word
×0.1
14
Vll ab, Volts/Amps/Freq
word
×0.1
15
Vll bc, Volts/Amps/Freq
word
×0.1
16
Vll ca, Volts/Amps/Freq
word
×0.1
17
Vll avg, Volts/Amps/Freq
word
×0.1
18
I a, Volts/Amps/Freq
word
×0.1
19
I b, Volts/Amps/Freq
word
×0.1
20
I c, Volts/Amps/Freq
word
×0.1
21
I avg, Volts/Amps/Freq
word
×0.1
22
V unbal, Volts/Amps/Freq
V
word
×0.1
23
I unbal, Volts/Amps/Freq
word
×0.1
24
Freq, Volts/Amps/Freq
word
×0.1
25
I4, Volts/Amps/Freq
word
×0.1
26
kW a, Power/PF
kW
integer
×0.1
28
kW b, Power/PF
kW
integer
×0.1
30
kW c, Power/PF
kW
integer
×0.1
32
kW tot, Power/PF
kW
integer
×0.1
34
kVAR a, Power/PF
kvar
integer
×0.1
36
kVAR b, Power/PF
kvar
integer
×0.1
38
kVAR c, Power/PF
kvar
integer
×0.1
40
kVAR tot, Power/PF
kvar
integer
×0.1
42
kVA a, Power/PF
kVA
integer
×0.1
44
kVA b, Power/PF
kVA
integer
×0.1
46
kVA c, Power/PF
kVA
integer
×0.1
48
kVA tot, Power/PF
kVA
integer
×0.1
50
PF sign a, Power/PF
integer
×0.1
52
PF sign b, Power/PF
integer
×0.1
54
PF sign c, Power/PF
integer
×0.1
56
PF sign tot, Power/PF
integer
×0.1
58
Vll avg mx, Min/Max/Demand
integer
×0.1
60
I avg mx, Min/Max/Demand
integer
×0.1
62
kW tot mx, Min/Max/Demand
kW
integer
×0.1
64
kVAR tot mx, Min/Max/Demand
kvar
integer
×0.1
66
kVA tot mx, Min/Max/Demand
kVA
integer
×0.1
68
Freq mx, Min/Max/Demand
integer
×0.1
70
Vll avg mn, Min/Max/Demand
integer
×0.1
72
I avg mn, Min/Max/Demand
integer
×0.1
74
Freq mn, Min/Max/Demand
integer
×0.1
76
kW sd del-rec, Min/Max/Demand
kW
integer
×0.1
78
kVA sd del+rec, Min/Max/Demand
kVA
integer
×0.1
80
kVAR sd del-rec, Min/Max/Demand
kvar
integer
×0.1
82
kW sd mx d-r, Min/Max/Demand
kW
integer
×0.1
84
kVA sd mx d+r, Min/Max/Demand
kVA
integer
×0.1
86
kVAR sd mx d-r, Min/Max/Demand
kvar
integer
×0.1
88
Phase Rev, Min/Max/Demand
integer
×0.1
90
kWh del, Energy/THD
kWh
integer
×0.1
92
kWh rec, Energy/THD
kWh
integer
×0.1
This is not the complete map: 50 of 131 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PowerLogic ION8600 - MODBUS Registers
Registers in the map: 131 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
10
Vln a, Volts/Amps/Freq
word
×0.1
11
Vln b, Volts/Amps/Freq
word
×0.1
12
Vln c, Volts/Amps/Freq
word
×0.1
13
Vln avg, Volts/Amps/Freq
word
×0.1
14
Vll ab, Volts/Amps/Freq
word
×0.1
15
Vll bc, Volts/Amps/Freq
word
×0.1
16
Vll ca, Volts/Amps/Freq
word
×0.1
17
Vll avg, Volts/Amps/Freq
word
×0.1
18
I a, Volts/Amps/Freq
word
×0.1
19
I b, Volts/Amps/Freq
word
×0.1
20
I c, Volts/Amps/Freq
word
×0.1
21
I avg, Volts/Amps/Freq
word
×0.1
22
V unbal, Volts/Amps/Freq
V
word
×0.1
23
I unbal, Volts/Amps/Freq
word
×0.1
24
Freq, Volts/Amps/Freq
word
×0.1
25
I4, Volts/Amps/Freq
word
×0.1
26
kW a, Power/PF
kW
integer
×0.1
28
kW b, Power/PF
kW
integer
×0.1
30
kW c, Power/PF
kW
integer
×0.1
32
kW tot, Power/PF
kW
integer
×0.1
34
kVAR a, Power/PF
kvar
integer
×0.1
36
kVAR b, Power/PF
kvar
integer
×0.1
38
kVAR c, Power/PF
kvar
integer
×0.1
40
kVAR tot, Power/PF
kvar
integer
×0.1
42
kVA a, Power/PF
kVA
integer
×0.1
44
kVA b, Power/PF
kVA
integer
×0.1
46
kVA c, Power/PF
kVA
integer
×0.1
48
kVA tot, Power/PF
kVA
integer
×0.1
50
PF sign a, Power/PF
integer
×0.1
52
PF sign b, Power/PF
integer
×0.1
54
PF sign c, Power/PF
integer
×0.1
56
PF sign tot, Power/PF
integer
×0.1
58
Vll avg mx, Min/Max/Demand
integer
×0.1
60
I avg mx, Min/Max/Demand
integer
×0.1
62
kW tot mx, Min/Max/Demand
kW
integer
×0.1
64
kVAR tot mx, Min/Max/Demand
kvar
integer
×0.1
66
kVA tot mx, Min/Max/Demand
kVA
integer
×0.1
68
Freq mx, Min/Max/Demand
integer
×0.1
70
Vll avg mn, Min/Max/Demand
integer
×0.1
72
I avg mn, Min/Max/Demand
integer
×0.1
74
Freq mn, Min/Max/Demand
integer
×0.1
76
kW sd del-rec, Min/Max/Demand
kW
integer
×0.1
78
kVA sd del+rec, Min/Max/Demand
kVA
integer
×0.1
80
kVAR sd del-rec, Min/Max/Demand
kvar
integer
×0.1
82
kW sd mx d-r, Min/Max/Demand
kW
integer
×0.1
84
kVA sd mx d+r, Min/Max/Demand
kVA
integer
×0.1
86
kVAR sd mx d-r, Min/Max/Demand
kvar
integer
×0.1
88
Phase Rev, Min/Max/Demand
integer
×0.1
90
kWh del, Energy/THD
kWh
integer
×0.1
92
kWh rec, Energy/THD
kWh
integer
×0.1
This is not the complete map: 50 of 131 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PowerLogic ION8800 - Measurement Data
Registers in the map: 289 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
10
Uln 1, Volts/Amps/Freq
word
×0.1
11
Uln 2, Volts/Amps/Freq
word
×0.1
12
Uln 3, Volts/Amps/Freq
word
×0.1
13
Uln avg, Volts/Amps/Freq
word
×0.1
14
Ull 12, Volts/Amps/Freq
word
×0.1
15
Ull 23, Volts/Amps/Freq
word
×0.1
16
Ull 31, Volts/Amps/Freq
word
×0.1
17
Ull avg, Volts/Amps/Freq
word
×0.1
18
I 1, Volts/Amps/Freq
word
×0.1
19
I 2, Volts/Amps/Freq
word
×0.1
20
I 3, Volts/Amps/Freq
word
×0.1
21
I avg, Volts/Amps/Freq
word
×0.1
22
U unbal, Volts/Amps/Freq
word
×0.1
23
I unbal, Volts/Amps/Freq
word
×0.1
24
Freq, Volts/Amps/Freq
word
×0.1
25
I4, Volts/Amps/Freq
word
×0.1
26
kW 1, Power/PF
kW
integer
×0.1
28
kW 2, Power/PF
kW
integer
×0.1
30
kW 3, Power/PF
kW
integer
×0.1
32
kW tot, Power/PF
kW
integer
×0.1
34
kVAR 1, Power/PF
kvar
integer
×0.1
36
kVAR 2, Power/PF
kvar
integer
×0.1
38
kVAR 3, Power/PF
kvar
integer
×0.1
40
kVAR tot, Power/PF
kvar
integer
×0.1
42
kVA 1, Power/PF
kVA
integer
×0.1
44
kVA 2, Power/PF
kVA
integer
×0.1
46
kVA 3, Power/PF
kVA
integer
×0.1
48
kVA tot, Power/PF
kVA
integer
×0.1
50
PF sign 1, Power/PF
integer
×0.1
52
PF sign 2, Power/PF
integer
×0.1
54
PF sign 3, Power/PF
integer
×0.1
56
PF sign tot, Power/PF
integer
×0.1
58
Ull avg mx, Min/Max/Demand
integer
×0.1
60
I avg mx, Min/Max/Demand
integer
×0.1
62
kW tot mx, Min/Max/Demand
kW
integer
×0.1
64
kVAR tot mx, Min/Max/Demand
kvar
integer
×0.1
66
kVA tot mx, Min/Max/Demand
kVA
integer
×0.1
68
Freq mx, Min/Max/Demand
integer
×0.1
70
Ull avg mn, Min/Max/Demand
integer
×0.1
72
I avg mn, Min/Max/Demand
integer
×0.1
74
Freq mn, Min/Max/Demand
integer
×0.1
76
kW sd del-rec, Min/Max/Demand
kW
integer
×0.1
78
kVA sd del+rec, Min/Max/Demand
kVA
integer
×0.1
80
kVAR sd del-rec, Min/Max/Demand
kvar
integer
×0.1
82
kW sd mx d-r, Min/Max/Demand
kW
integer
×0.1
84
kVA sd mx d+r, Min/Max/Demand
kVA
integer
×0.1
86
kVAR sd mx d-r, Min/Max/Demand
kvar
integer
×0.1
88
Phase Rev, Min/Max/Demand
integer
×0.1
90
kWh del, Energy/THD
kWh
integer
×0.1
92
kWh rec, Energy/THD
kWh
integer
×0.1
This is not the complete map: 50 of 289 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.