Schneider Electric PowerLogic PowerLogic ION8300, ION8400 MODBUS registers: read online

Connect Schneider Electric PowerLogic to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Schneider Electric PowerLogic data logging and capture.

Do you not know the meter address? Scan the device address online

Schneider Electric PowerLogic ION8300-ION8400-ION8500 - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Register addressing
4xxxx register notation (e.g. 40011)

Registers in the map: 131 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
10Vln a 1, Volts/Amps/Freq word×0.1
11Vln b 1, Volts/Amps/Freq word×0.1
12Vln c 1, Volts/Amps/Freq word×0.1
13Vln avg 1, Volts/Amps/Freq word×0.1
14Vll ab, Volts/Amps/Freq word×0.1
15Vll bc, Volts/Amps/Freq word×0.1
16Vll ca, Volts/Amps/Freq word×0.1
17Vll avg, Volts/Amps/Freq word×0.1
18I a, Volts/Amps/Freq word×0.1
19I b, Volts/Amps/Freq word×0.1
20I c, Volts/Amps/Freq word×0.1
21I avg, Volts/Amps/Freq word×0.1
22V unbal, Volts/Amps/FreqVword×0.1
23I unbal, Volts/Amps/Freq word×0.1
24Freq, Volts/Amps/Freq word×0.1
25I4, Volts/Amps/Freq word×0.1
26kW a, Power/PFkWinteger×0.1
28kW b, Power/PFkWinteger×0.1
30kW c, Power/PFkWinteger×0.1
32kW tot, Power/PFkWinteger×0.1
34kVAR a, Power/PFkvarinteger×0.1
36kVAR b, Power/PFkvarinteger×0.1
38kVAR c, Power/PFkvarinteger×0.1
40kVAR tot, Power/PFkvarinteger×0.1
42kVA a, Power/PFkVAinteger×0.1
44kVA b, Power/PFkVAinteger×0.1
46kVA c, Power/PFkVAinteger×0.1
48kVA tot, Power/PFkVAinteger×0.1
50PF sign a, Power/PF integer×0.1
52PF sign b, Power/PF integer×0.1
54PF sign c, Power/PF integer×0.1
56PF sign tot, Power/PF integer×0.1
58Vll avg mx, Min/Max/Demand integer×0.1
60I avg mx, Min/Max/Demand integer×0.1
62kW tot mx, Min/Max/DemandkWinteger×0.1
64kVAR tot mx, Min/Max/Demandkvarinteger×0.1
66kVA tot mx, Min/Max/DemandkVAinteger×0.1
68Freq mx, Min/Max/Demand integer×0.1
70Vll avg mn, Min/Max/Demand integer×0.1
72I avg mn, Min/Max/Demand integer×0.1
74Freq mn, Min/Max/Demand integer×0.1
76kW sd del-rec, Min/Max/DemandkWinteger×0.1
78kVA sd del+rec, Min/Max/DemandkVAinteger×0.1
80kVAR sd del-rec, Min/Max/Demandkvarinteger×0.1
82kW sd mx d-r, Min/Max/DemandkWinteger×0.1
84kVA sd mx d+r, Min/Max/DemandkVAinteger×0.1
86kVAR sd mx d-r, Min/Max/Demandkvarinteger×0.1
88Phase Rev, Min/Max/Demand integer×0.1
90kWh del, Energy/THDkWhinteger×0.1
92kWh rec, Energy/THDkWhinteger×0.1

This is not the complete map: 50 of 131 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric PowerLogic ION8600 - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Register addressing
4xxxx register notation (e.g. 40011)

Registers in the map: 131 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
10Vln a, Volts/Amps/Freq word×0.1
11Vln b, Volts/Amps/Freq word×0.1
12Vln c, Volts/Amps/Freq word×0.1
13Vln avg, Volts/Amps/Freq word×0.1
14Vll ab, Volts/Amps/Freq word×0.1
15Vll bc, Volts/Amps/Freq word×0.1
16Vll ca, Volts/Amps/Freq word×0.1
17Vll avg, Volts/Amps/Freq word×0.1
18I a, Volts/Amps/Freq word×0.1
19I b, Volts/Amps/Freq word×0.1
20I c, Volts/Amps/Freq word×0.1
21I avg, Volts/Amps/Freq word×0.1
22V unbal, Volts/Amps/FreqVword×0.1
23I unbal, Volts/Amps/Freq word×0.1
24Freq, Volts/Amps/Freq word×0.1
25I4, Volts/Amps/Freq word×0.1
26kW a, Power/PFkWinteger×0.1
28kW b, Power/PFkWinteger×0.1
30kW c, Power/PFkWinteger×0.1
32kW tot, Power/PFkWinteger×0.1
34kVAR a, Power/PFkvarinteger×0.1
36kVAR b, Power/PFkvarinteger×0.1
38kVAR c, Power/PFkvarinteger×0.1
40kVAR tot, Power/PFkvarinteger×0.1
42kVA a, Power/PFkVAinteger×0.1
44kVA b, Power/PFkVAinteger×0.1
46kVA c, Power/PFkVAinteger×0.1
48kVA tot, Power/PFkVAinteger×0.1
50PF sign a, Power/PF integer×0.1
52PF sign b, Power/PF integer×0.1
54PF sign c, Power/PF integer×0.1
56PF sign tot, Power/PF integer×0.1
58Vll avg mx, Min/Max/Demand integer×0.1
60I avg mx, Min/Max/Demand integer×0.1
62kW tot mx, Min/Max/DemandkWinteger×0.1
64kVAR tot mx, Min/Max/Demandkvarinteger×0.1
66kVA tot mx, Min/Max/DemandkVAinteger×0.1
68Freq mx, Min/Max/Demand integer×0.1
70Vll avg mn, Min/Max/Demand integer×0.1
72I avg mn, Min/Max/Demand integer×0.1
74Freq mn, Min/Max/Demand integer×0.1
76kW sd del-rec, Min/Max/DemandkWinteger×0.1
78kVA sd del+rec, Min/Max/DemandkVAinteger×0.1
80kVAR sd del-rec, Min/Max/Demandkvarinteger×0.1
82kW sd mx d-r, Min/Max/DemandkWinteger×0.1
84kVA sd mx d+r, Min/Max/DemandkVAinteger×0.1
86kVAR sd mx d-r, Min/Max/Demandkvarinteger×0.1
88Phase Rev, Min/Max/Demand integer×0.1
90kWh del, Energy/THDkWhinteger×0.1
92kWh rec, Energy/THDkWhinteger×0.1

This is not the complete map: 50 of 131 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric PowerLogic ION8800 - Measurement Data

Connection and addressing notes

Protocol
Modbus
Register addressing
4xxxx register notation (e.g. 40011)

Registers in the map: 289 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
10Uln 1, Volts/Amps/Freq word×0.1
11Uln 2, Volts/Amps/Freq word×0.1
12Uln 3, Volts/Amps/Freq word×0.1
13Uln avg, Volts/Amps/Freq word×0.1
14Ull 12, Volts/Amps/Freq word×0.1
15Ull 23, Volts/Amps/Freq word×0.1
16Ull 31, Volts/Amps/Freq word×0.1
17Ull avg, Volts/Amps/Freq word×0.1
18I 1, Volts/Amps/Freq word×0.1
19I 2, Volts/Amps/Freq word×0.1
20I 3, Volts/Amps/Freq word×0.1
21I avg, Volts/Amps/Freq word×0.1
22U unbal, Volts/Amps/Freq word×0.1
23I unbal, Volts/Amps/Freq word×0.1
24Freq, Volts/Amps/Freq word×0.1
25I4, Volts/Amps/Freq word×0.1
26kW 1, Power/PFkWinteger×0.1
28kW 2, Power/PFkWinteger×0.1
30kW 3, Power/PFkWinteger×0.1
32kW tot, Power/PFkWinteger×0.1
34kVAR 1, Power/PFkvarinteger×0.1
36kVAR 2, Power/PFkvarinteger×0.1
38kVAR 3, Power/PFkvarinteger×0.1
40kVAR tot, Power/PFkvarinteger×0.1
42kVA 1, Power/PFkVAinteger×0.1
44kVA 2, Power/PFkVAinteger×0.1
46kVA 3, Power/PFkVAinteger×0.1
48kVA tot, Power/PFkVAinteger×0.1
50PF sign 1, Power/PF integer×0.1
52PF sign 2, Power/PF integer×0.1
54PF sign 3, Power/PF integer×0.1
56PF sign tot, Power/PF integer×0.1
58Ull avg mx, Min/Max/Demand integer×0.1
60I avg mx, Min/Max/Demand integer×0.1
62kW tot mx, Min/Max/DemandkWinteger×0.1
64kVAR tot mx, Min/Max/Demandkvarinteger×0.1
66kVA tot mx, Min/Max/DemandkVAinteger×0.1
68Freq mx, Min/Max/Demand integer×0.1
70Ull avg mn, Min/Max/Demand integer×0.1
72I avg mn, Min/Max/Demand integer×0.1
74Freq mn, Min/Max/Demand integer×0.1
76kW sd del-rec, Min/Max/DemandkWinteger×0.1
78kVA sd del+rec, Min/Max/DemandkVAinteger×0.1
80kVAR sd del-rec, Min/Max/Demandkvarinteger×0.1
82kW sd mx d-r, Min/Max/DemandkWinteger×0.1
84kVA sd mx d+r, Min/Max/DemandkVAinteger×0.1
86kVAR sd mx d-r, Min/Max/Demandkvarinteger×0.1
88Phase Rev, Min/Max/Demand integer×0.1
90kWh del, Energy/THDkWhinteger×0.1
92kWh rec, Energy/THDkWhinteger×0.1

This is not the complete map: 50 of 289 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.