Selec EM2M-1P, MFM374, MFM383A MODBUS registers: read online

Connect Selec to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Selec modbus logging and log.

Do you not know the meter address? Scan the device address online

Selec (EM2M-1P) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Interface
RS-485
Default baud rate
9600 bps
Baud rate options
9600 or 19200 selectable
Stop bits
1
Parity
None
Default device address
1
Default password
1000
Device address range
1 to 255
Measured values
3xxxx input registers (30001 and up, 0-based offset = 3xxxx minus 30001)
32-bit float values
two registers per value
Configuration password range
0000 to 9998

Registers in the map: 24. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Total active energyWsingle 
2Import active energy single 
4Export active energy single 
6Total reactive energy single 
8Import reactive energy single 
10Export reactive energy single 
12Apparent energy single 
14Active power single 
16Reactive power single 
18Apparent power single 
20Voltage L-NBsingle 
22CurrentAsingle 
24Power factor single 
26FrequencyHzsingle 
28Max demand active powerWsingle 
30Max demand reactive power single 
32Max demand apparent power single 
149TotalkWhsingle 
150ImportkWhsingle 
151ExportkWhsingle 
152Totalkvarhsingle 
153Importkvarhsingle 
154Exportkvarhsingle 
155kVAhkVAhsingle 

Selec (MFM374) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Measured values
3xxxx input registers (30000 and up, 0-based offset = address minus 30000)
32-bit float values
two registers per value
Settings
4xxxx holding registers
Password register
40000

Registers in the map: 35. function 4 (input registers). function 3 (input registers). byte order big-endian. data types: single, word.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage v1n single 
2Voltage v2n single 
4Voltage v3n single 
6Average voltage ln single 
8Voltage V12 single 
10Voltage V23 single 
12Voltage V31 single 
14Average voltage ll single 
16Current I1 single 
18Current I2 single 
20Current I3 single 
22Average current single 
24kW1 single 
26kW2 single 
28kW3 single 
30Kva1 single 
32Kva2 single 
34Kva3 single 
36Kvar1 single 
38Kvar2 single 
40Kvar3 single 
42TotalkWsingle 
44TotalkVAsingle 
46Totalkvarsingle 
48PF1 single 
50PF2 single 
52PF3 single 
54Average pf single 
56Frequency single 
58Kwh single 
60Kvah single 
62Kvarh single 
1Nm selection word 
3Ct primary (ct secondary = 5) word 
5Pt primary word 

Selec (MFM383A) - MODBUS Registers Map

Connection and addressing notes

Measured values
3xxxx input registers (30000 and up, 0-based offset = address minus 30000)
32-bit float values
two registers per value
Access
read only

Registers in the map: 27. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage v1n single 
2Voltage v2n single 
6Average voltage ln single 
8Voltage V12 single 
14Average voltage ll single 
16Current 11 single 
18Current 12 single 
20Current I3 single 
22Average current single 
24kW1 single 
26kW2 single 
28kW3 single 
30Kva1 single 
32Kva2 single 
34Kva3 single 
36Kvar1 single 
38Kvar2 single 
40Kvar3 single 
42TotalkWsingle 
44TotalkVAsingle 
46Totalkvarsingle 
48PF1 single 
50PF2 single 
52PF3 single 
54Average pf single 
56Frequency single 
58Kwh single 

Selec (MFM384) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Measured values
3xxxx input registers (30000 and up, 0-based offset = address minus 30000)
32-bit float values
two registers per value
Settings
4xxxx holding registers
Password register
40000, range 0 to 9998
Slave ID register
40007, range 1 to 255
Baud rate register
40008, 0 = 300, 1 = 600, 2 = 1200, 3 = 2400, 4 = 4800, 5 = 9600, 6 = 19200
Parity register
40009, 0 = none, 1 = odd, 2 = even
Stop bits register
40010, 0 = 1, 1 = 2

Registers in the map: 40. function 4 (input registers). function 3 (holding registers). byte order big-endian. data types: single, word.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage v1n single 
2Voltage v2n single 
4Voltage v3n single 
6Average voltage ln single 
8Voltage V12 single 
10Voltage V23 single 
12Voltage V31 single 
14Average voltage ll single 
16Current I1 single 
18Current I2 single 
20Current I3 single 
22Average current single 
24kW1 single 
26kW2 single 
28kW3 single 
30Kva1 single 
32Kva2 single 
34Kva3 single 
36Kvar1 single 
38Kvar2 single 
40Kvar3 single 
42TotalkWsingle 
44TotalkVAsingle 
46Totalkvarsingle 
48PF1 single 
50PF2 single 
52PF3 single 
54Average pf single 
56Frequency single 
58Kwh single 
60Kvah single 
62Kvarh single 
64Kw max active power single 
66Kw min active power single 
68Kvar max reactive power single 
70Kvar min reactive power single 
72Kva max apparent power single 
1Nm selection word 
3Ct primary (ct secondary = 5) word 
5Pt primary word 

Selec (MRJ4M) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Measured values
3xxxx input registers (30000 and up, 0-based offset = address minus 30000)
32-bit float values
two registers per value
4-byte value byte order
the LSB is at the lower address and the MSB at the higher address

Registers in the map: 65 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single, string(4).

MODBUS offsetDescriptionUnitsData typeScale
132Serial no string(4) 
0Voltage V1NVsingle 
2Voltage V2NVsingle 
4Voltage V3NVsingle 
6Average voltage LNVsingle 
8Voltage V12Vsingle 
10Voltage V23Vsingle 
12Voltage V31Vsingle 
14Average voltage LLVsingle 
74Current I1Asingle 
76Current I2Asingle 
78Current I3Asingle 
80Average currentAsingle 
82kW1kWsingle 
84kW2kWsingle 
86kW3kWsingle 
88kVA1kVAsingle 
90kVA2kVAsingle 
92kVA3kVAsingle 
94kVAr1kvarsingle 
96kVAr2kvarsingle 
98kVAr3kvarsingle 
100TotalkWsingle 
102TotalkVAsingle 
104Totalkvarsingle 
106PFI single 
108PF2 single 
110PF3 single 
112AveragePFsingle 
114FrequencyHzsingle 
116kWhkWhsingle 
120kVArhkvarhsingle 
122kW MAX active powerkWsingle 
130kVA MAX apparent powerkVAsingle 
142Total kWh (Load 1 and load 2)kWhsingle 
144Total kVArh (Load 1 and load 2)kvarhsingle 
146Existing kW MAX active powerkWsingle 
148Existing kVA MAX apperant powerkVAsingle 
16Current I1Asingle 
18Current I2Asingle 
20Current I3Asingle 
22Average currentAsingle 
24kW1kWsingle 
26KW2kwsingle 
28kW3kWsingle 
30kVAIkVAsingle 
32kVA2kVAsingle 
34kVA3kVAsingle 
36kVAr1kvarsingle 
38kVAr2kvarsingle 

This is not the complete map: 50 of 65 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.