ABB DMTME multimeters data logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
4098
Phase voltage l1-n
Volt
dword
4100
Phase voltage l2-n
Volt
dword
4102
Phase voltage l3-n
Volt
dword
4104
Line voltage l1-l2
Volt
dword
4106
Line voltage l2-l3
Volt
dword
4108
Line voltage l1-l3
Volt
dword
4112
Line current l1
mA
dword
4114
Line current l2
mA
dword
4116
Line current l3
mA
dword
4118
3-phase sys. power factor
 
integer
4120
Power factor l1
 
integer
4122
Power factor l2
 
integer
4124
Power factor l3
 
integer
4134
3-phase sys. apparent power
VA
dword
4136
Apparent power l1
VA
dword
4138
Apparent power l2
VA
dword
4140
Apparent power l3
VA
dword
4142
3-phase sys. active power
Watt
dword
4144
Active power l1
Watt
dword
4146
Active power l2
Watt
dword
4148
Active power l3
Watt
dword
4150
3-phase reactive power
VAr
dword
4152
Reactive power l1
VAr
dword
4154
Reactive power l2
VAr
dword
4156
Reactive power l3
VAr
dword
4158
3-phase sys. active energy
Wh
dword
4160
3-phase sys. reactive energy
VArh
dword
4166
Frequency
mHz
dword
4512
Current transformer ratio
 
dword
4514
Voltage transformer ratio
 
dword

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.