bg

Accuenergy Acuvim L Power Meter Acuvim L MODBUS registers: read online

Connect Accuenergy Acuvim L Power Meter to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Accuenergy Acuvim L Power Meter data logging and capture.

Do you not know the meter address? Scan the device address online

Accuenergy Acuvim L Power Meter - MODBUS Mapping

Registers in the map: 61 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
1536Frequency F single 
1538Phase voltage v1 single 
1540Phase voltage v2 single 
1542Phase voltage v3 single 
1544Line voltage v12 single 
1546Line voltage v23 single 
1548Line voltage v31 single 
1550Phase (line) current i1 single 
1552Phase (line) current i2 single 
1554Phase (line) current i3 single 
1556Neutral line current in single 
1558Phase power pa single 
1560Phase power pb single 
1562Phase power pc single 
1564System power psum single 
1566Phase reactive power qa single 
1568Phase reactive power qb single 
1570Phase reactive power qc single 
1572System reactive power single 
1574System apparent ssum single 
1576Phase power factor PFa single 
1578Phase power factor PFb single 
1580Phase power factor PFc single 
1582System power PFsum single 
1584Voltage unbalance factor single 
1586Current unbalance factor single 
1590Phase apparent power sa single 
1592Phase apparent power sb single 
1594Phase apparent power sc single 
1598Apparent power demand single 
1600Power demand P_Dmd single 
1602Reactive power demand single 
1604Phase A current demand single 
1606Phase A current demand single 
1608Phase C current demand single 
1024Total harmonic distortion of v1 or v12 word 
1025Total harmonic distortion of v2 or v23 word 
1026Total harmonic distortion of v3 or v31 word 
1027Total harmonic distortion of i1 THD_ i1 word 
1028Total harmonic distortion of i2 THD_ i2 word 
1029Total harmonic distortion of i3 THD_ i3 word 
342Import energy ep imp dword×0.1
344Export energy ep exp dword×0.1
346Import reactive energy eq imp dword×0.1
348Export reactive energy eq exp dword×0.1
350Apparent energy es dword×0.1
352Phase A import energy ep imp dword×0.1
354Phase A export energy ep_exp dword×0.1
356Phase B import energy ep_imp dword×0.1
358Phase B export energy ep_exp dword×0.1

This is not the complete map: 50 of 61 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection