Acrel (ADL3000) data logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
10 | Total import kwh | | dword |
20 | Total export kwh | | dword |
30 | Total kvarh | | dword |
40 | Total import kvarh | | dword |
50 | Total export kvarh | | dword |
60 | Year month | | word |
61 | Day time | | word |
62 | Minute second | | word |
97 | Phase A voltage | | word |
98 | Phase B voltage | | word |
99 | Phase C voltage | | word |
100 | Phase A current | | word |
101 | Phase B current | | word |
102 | Phase C current | | word |
103 | Phase A kw | | word |
104 | Phase B kw | | word |
105 | Phase C kw | | word |
106 | Total kw | | word |
107 | Phase A kvar | | word |
108 | Phase B kvar | | word |
109 | Phase C kvar | | word |
110 | Total kvar | | word |
111 | Phase A kva | | word |
112 | Phase B kvr | | word |
113 | Phase C kva | | word |
114 | Total kva | | word |
115 | Phase A power factor | | word |
116 | Phase B power factor | | word |
117 | Phase C power factor | | word |
118 | Total power factor | | word |
119 | Frequency | | word |
331 | Ct ratio | | dword |
Acrel (ACR10R) data logging
Acrel (ADL100) data logging
Acrel (ADL300) data logging
Acrel (ADL3000) data logging
Acrel (PZ300) data logging
Acrel (PZ72-E3,P80-E3,PZ96-E3) data logging
Acrel (PZ80) data logging
Acrel (PZ96) data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.