Arch Meter PA310, PA33, PA34 MODBUS registers: read online

Connect Arch Meter to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Arch Meter logger and poll.

Do you not know the meter address? Scan the device address online

Arch Meter (PA310) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Default baud rate
19200 bps
Stop bits
1
Default device address
15
Setup parameters
holding registers with Modicom addresses
Address register
44097 (0x1000), range 1-200, default 15
Baud rate register
44098 (0x1001), 1 = 9600, 2 = 19200 (default)
Stop bits register
44099 (0x1002), 1 = 1 stop bit (default), 2 = 2 stop bits

Registers in the map: 296 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). function 4 (input registers). byte order big-endian. data types: dword, integer, single, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
0Pt ratio single 
2Ct ratio single 
4098Stopbit word 
4100Wiring word 
4114ClrkWhsmallint 
4128Kt value smallint 
4129Voltage transform er ratio word 
4130Current transform er ratio word 
4131Year word 
4132Month word 
4133Date word 
4134Hour word 
4135Minute word 
4136Second word 
4137Day of week word 
4144Demand flag smallint 
4145Sub interval smallint 
4146Interval multipli er smallint 
4147Lp_data_group1_ clr word 
4148Lp_group1_datac ounter smallint 
4149Lp group1 intlen gth smallint 
4150Lp_g1_ch1_save data smallint 
4151Lp G1 Ch2 save data smallint 
4152Lp_g1_ch3_save data smallint 
4153Lp G1 Ch4 save data smallint 
4154Lp_g1_ch5_save data smallint 
4155Lp G1 Ch6 save data smallint 
4156Lp_g1_ch7_save data smallint 
4157Lp G1 Ch8 save data smallint 
4158Lp_g1_ch9_save data smallint 
4159Lp G1 ch10 save data smallint 
4160Lp_g1_ch11_save data smallint 
4161Lp_g1_ch12_save data smallint 
4162Lp data group2 cfr smallint 
4163Lp group2 datac ounter smallint 
4164Lp group2 intlen gth smallint 
4165Lp G2 Ch1 save data smallint 
4166Lp G2 Ch2 save data smallint 
4167Lp G2 Ch3 save data smallint 
4168Lp G2 Ch4 save data smallint 
4169Lp G2 Ch5 save data smallint 
4170Lp G2 Ch6 save data smallint 
4171Lp G2 Ch7 save data smallint 
4172Lp G2 Ch8 save data smallint 
4173Lp G2 Ch9 save data smallint 
4864Kwh_deliver_a single 
4866Kwh receiver a single 
4868Kvarh_iagging_a single 
4870Kvarh_ieading_a single 
4872Kvah a single 

This is not the complete map: 50 of 296 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Arch Meter (PA33) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Interface
RS-485
Stop bits
1
Setup parameters
holding registers
Baud rate register
44097 (0x1000), 0 = 9600, 1 = 19200, 2 = 38400
Stop bits register
44098 (0x1001), 0 = 1 stop bit (default), 1 = 2 stop bits

Registers in the map: 84 (the first 54 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). function 4 (input registers). byte order big-endian. data types: dword, integer, single, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
4098Meter ratio word 
4099Pt ratio word 
4100Ct ratio word 
4106Wiring mode word 
0R(r s) voltageVword×0.1
1S(s t) voltageVword×0.1
2T(t r) voltageVword×0.1
3R currentAword×0.1
4S currentAword×0.1
5T currentAword×0.1
6FrequencyHzword×0.1
7PfPFsmallint 
8KwkWword×0.1
9Kvarkvarword×0.1
10KwhkWhdword×0.1
12Kvarhkvarhdword×0.1
4352V a single 
4354I aAsingle 
4356Kw_akWsingle 
4358Kvar akvarsingle 
4360Kva_akVAsingle 
4362Pf a single 
4364Kwh_a single 
4366Kvarh_a single 
4368Kvah_a single 
4370V b single 
4372I_bAsingle 
4374Kw bkWsingle 
4376Kvar bkvarsingle 
4378Kva_bkVAsingle 
4380Pf_b single 
4382Kwh b single 
4384Kvarh b single 
4386Kvah_b single 
4388V_cVsingle 
4390I cAsingle 
4392Kw ckWsingle 
4394Kvar ckvarsingle 
4396Kva ckVAsingle 
4398Pf_c single 
4400Kwh c single 
4402Kvarh c single 
4406V_avg(v_d)Vsingle 
4408I avg(i d)Asingle 
4410Kw_tot(kw_d)kWsingle 
4412Kvar_tot(kvar_d)kvarsingle 
4414Kva tot(kva d)kVAsingle 
4416Pf tot(pf d) single 
4418Kwh tot(kwh d) single 
4420Kvarh totkvarh d) single 
4422Kvah tot(kvah d) single 
4608V_aVdword 
4610I_aAdword×0.1
4612Kw_akWinteger×0.1

This is not the complete map: 54 of 84 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Arch Meter (PA34) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Interface
RS-485
Stop bits
1
Setup parameters
holding registers
Baud rate register
44097 (0x1000), 0 = 9600, 1 = 19200, 2 = 38400
Stop bits register
44098 (0x1001), 0 = 1 stop bit (default), 1 = 2 stop bits

Registers in the map: 15. function 3 (holding registers). function 4 (input registers). byte order big-endian. data types: dword, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
4098Meter ratio word 
4099Pt ratio word 
4100Ct ratio word 
0R(r s) voltageVword×0.1
1S(s t) voltageVword×0.1
2T(t r) voltageVword×0.1
3R currentAword×0.1
4S currentAword×0.1
5T currentAword×0.1
6FrequencyHzword×0.1
7PfPFsmallint×0.001
8KwkWsmallint×0.1
9Kvarkvarsmallint×0.1
10KwhkWhdword×0.1
12Kvarhkvarhdword×0.1