CET PMC-220, PMC-350-C, PMC-43 MODBUS registers: read online
Connect CET to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous CET modbus logging and log.
03 read holding registers, 05 force single coil, 16 preset multiple registers
Byte order
big endian
Registers in the map: 324 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, word.
MODBUS offset
Description
Units
Data type
Scale
0
Uan
V
single
2
Ubn
V
single
4
Ucn
V
single
6
Uln average
V
single
8
Uab
V
single
10
Ubc
V
single
12
Uca
V
single
14
Ull average
V
single
16
Ia
A
single
18
Ib
A
single
20
Ic
A
single
22
I average
A
single
24
kWa
W
single
26
kWb
W
single
28
kWc
W
single
30
kW total
W
single
32
Kvara
var
single
34
Kvarb
var
single
36
Kvarc
var
single
38
Kvar total
var
single
40
kVAa
VA
single
42
kVAb
VA
single
44
kVAc
VA
single
46
kVA total
VA
single
48
PFa
single
50
PFb
single
52
PFc
single
54
PF total
single
56
Frequency
Hz
single
58
Uan/Uab (3P3W) angle
deg
single
60
Ubn/Ubc (3P3W) angle
deg
single
62
Ucn/Uca (3P3W) angle
deg
single
64
Ia angle
deg
single
66
Ib angle
deg
single
68
Ic angle
deg
single
70
In (Calculated)
A
single
72
IR1
A
single
×0.001
74
Displacement PFa
single
76
Displacement PFb
single
78
Displacement PFc
single
80
Displacement PF total
single
86
TC11
single
88
TC21
single
90
TC31
single
92
TC41
single
96
DI status1, 2
word
98
DO status 1, 3
word
100
Setpoint alarm status4
word
101
Wiring diagnostic status5
word
102
SOE pointer6
dword
This is not the complete map: 50 of 324 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
03 read holding registers, 05 force single coil, 16 preset multiple registers
Byte order
big endian
Registers in the map: 338 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, word.
MODBUS offset
Description
Units
Data type
Scale
0
Uan
V
single
2
Ubn
V
single
4
Ucn
V
single
6
Uln average
V
single
8
Uab
V
single
10
Ubc
V
single
12
Uca
V
single
14
Ull average
V
single
16
Ia
A
single
18
Ib
A
single
20
Ic
A
single
22
I average
A
single
24
kWa
W
single
26
kWb
W
single
28
kWc
W
single
30
kW total
W
single
32
Kvara
var
single
34
Kvarb
var
single
36
Kvarc
var
single
38
Kvar total
var
single
40
kVAa
VA
single
42
kVAb
VA
single
44
kVAc
VA
single
46
kVA total
VA
single
48
PFa
single
50
PFb
single
52
PFc
single
54
PF total
single
56
Frequency
Hz
single
58
Uan/Uab (3P3W) angle
deg
single
60
Ubn/Ubc (3P3W) angle
deg
single
62
Ucn/Uca (3P3W) angle
deg
single
64
Ia angle
deg
single
66
Ib angle
deg
single
68
Ic angle
deg
single
70
In (Calculated)
A
single
72
I41
A
single
74
Displacement PFa
single
76
Displacement PFb
single
78
Displacement PFc
single
80
Displacement PF total
single
82
AI1 scaled
single
86
RTD 11
deg C
single
88
RTD 21
deg C
single
90
AO1
single
96
DI status1, 2
word
98
DO status1, 3
word
100
Setpoint status4
word
101
Wiring diagnostic status5
word
102
SOE log pointer6
dword
This is not the complete map: 50 of 338 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
holding registers (4XXXXX) and write only coil registers (0XXXXX) for DO control
Register addressing
6-digit addressing scheme
Offset calculation
addresses used as printed, no 400001 or 000001 subtraction
Function codes
03 read holding registers, 05 force single coil, 16 preset multiple registers
Registers in the map: 66 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
2
VB1
V
dword
×0.01
4
VC1
V
dword
×0.01
6
VLN average
V
dword
×0.01
8
Vab
V
dword
×0.01
10
Vbc
V
dword
×0.01
12
Vca
V
dword
×0.01
14
VLL average
V
dword
×0.01
16
Ia
A
dword
×0.001
18
Ib
A
dword
×0.001
20
Ic
A
dword
×0.001
22
I average
A
dword
×0.001
24
kWa1
kW
integer
×0.001
26
kWb1
kW
integer
×0.001
28
kWc1
kW
integer
×0.001
30
kW
kW
integer
×0.001
32
Kvara1
integer
×0.001
34
Kvarb1
integer
×0.001
36
Kvarc1
integer
×0.001
38
Kvar
integer
×0.001
40
kVAa1
kVA
integer
×0.001
42
kVAb1
kVA
integer
×0.001
44
kVAc1
kVA
integer
×0.001
46
kVA
kVA
integer
×0.001
48
PFa1
smallint
×0.001
49
PFb1
smallint
×0.001
50
PFc1
smallint
×0.001
51
PF
smallint
×0.001
52
FREQ
Hz
word
×0.01
53
I4
A
dword
×0.001
55
Voltage unbalance
word
×0.001
56
Current unbalance
word
×0.001
57
dPFa*, 1
smallint
×0.001
58
dPFb*, 1
smallint
×0.001
59
dPFc*, 1
smallint
×0.001
60
kW demand
kW
integer
×0.001
62
Kvar demand
integer
×0.001
64
kVA demand
kVA
integer
×0.001
66
Ia demand
A
dword
×0.001
68
Ib demand
A
dword
×0.001
70
Ic demand
A
dword
×0.001
72
Va angle
word
×0.01
73
Vb angle
word
×0.01
74
Vc angle
word
×0.01
75
Ia angle
word
×0.01
76
Ib angle
word
×0.01
77
Ic angle
word
×0.01
78
I residual#, 3
word
×0.1
79
Temperature#, 4
smallint
×0.1
95
Alarm#, 5
word
96
DO status#, 6
word
This is not the complete map: 50 of 66 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.