CET PMC-220, PMC-350-C, PMC-43 MODBUS registers: read online

Connect CET to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous CET modbus logging and log.

Do you not know the meter address? Scan the device address online

CET (PMC-220) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Function codes
03 read holding registers, 16 preset multiple registers
Data format
16/32-bit integers and IEEE 754 floats
Byte order
big endian

Registers in the map: 18. function 3 (holding registers). byte order big-endian. data types: integer, single, word.

MODBUS offsetDescriptionUnitsData typeScale
0VVsingle 
2IAsingle 
4kWkWsingle 
6Kvarkvarsingle 
8kVAkVAsingle 
10P.F single 
12FrequencyHzsingle 
38FP counterHzword 
39Comm. counterHzword 
40kWh importkWhinteger×0.01
42kWh exportkWhinteger×0.01
44kWh netkWhinteger×0.01
46kWh totalkWhinteger×0.01
48Kvarh importkvarhinteger×0.01
50Kvarh exportkvarhinteger×0.01
52Kvarh netkvarhinteger×0.01
54Kvarh totalkvarhinteger×0.01
56kVAhkVAhinteger×0.01

CET (PMC-350-C) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Function codes
03 read holding registers, 05 force single coil, 16 preset multiple registers
Byte order
big endian

Registers in the map: 324 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, word.

MODBUS offsetDescriptionUnitsData typeScale
0UanVsingle 
2UbnVsingle 
4UcnVsingle 
6Uln averageVsingle 
8UabVsingle 
10UbcVsingle 
12UcaVsingle 
14Ull averageVsingle 
16IaAsingle 
18IbAsingle 
20IcAsingle 
22I averageAsingle 
24kWaWsingle 
26kWbWsingle 
28kWcWsingle 
30kW totalWsingle 
32Kvaravarsingle 
34Kvarbvarsingle 
36Kvarcvarsingle 
38Kvar totalvarsingle 
40kVAaVAsingle 
42kVAbVAsingle 
44kVAcVAsingle 
46kVA totalVAsingle 
48PFa single 
50PFb single 
52PFc single 
54PF total single 
56FrequencyHzsingle 
58Uan/Uab (3P3W) angledegsingle 
60Ubn/Ubc (3P3W) angledegsingle 
62Ucn/Uca (3P3W) angledegsingle 
64Ia angledegsingle 
66Ib angledegsingle 
68Ic angledegsingle 
70In (Calculated)Asingle 
72IR1Asingle×0.001
74Displacement PFa single 
76Displacement PFb single 
78Displacement PFc single 
80Displacement PF total single 
86TC11 single 
88TC21 single 
90TC31 single 
92TC41 single 
96DI status1, 2 word 
98DO status 1, 3 word 
100Setpoint alarm status4 word 
101Wiring diagnostic status5 word 
102SOE pointer6 dword 

This is not the complete map: 50 of 324 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

CET (PMC-43) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Register type
holding registers (4XXXXX)
Register addressing
6-digit addressing scheme
Offset calculation
addresses used as printed, no 400001 subtraction
Function codes
03 read holding registers, 16 preset multiple registers

Registers in the map: 45. function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
2VB1Vdword×0.01
4VC1, 2Vdword×0.01
6VLN average1Vdword×0.01
8VabVdword×0.01
10Vbc2Vdword×0.01
12Vca2Vdword×0.01
14VLL averageVdword×0.01
16IaAdword×0.001
18IbAdword×0.001
20IC2Adword×0.001
22I averageAdword×0.001
24kWa1kWinteger×0.001
26kWb1kWinteger×0.001
28kWc1, 2kWinteger×0.001
30kWkWinteger×0.001
32Kvara1 integer×0.001
34Kvarb1 integer×0.001
36Kvarc1, 2 integer×0.001
38Kvar integer×0.001
40kVAa1kVAinteger×0.001
42kVAb1kVAinteger×0.001
44kVAc1, 2kVAinteger×0.001
46kVAkVAinteger×0.001
48P.F.a1 smallint×0.001
49P.F.b1 smallint×0.001
50P.F.c1, 2 smallint×0.001
51P.F smallint×0.001
52FREQHzword×0.01
53I4*, 2 dword×0.001
55Voltage unbalance*, 4 word×0.001
56Current unbalance*, 4 word×0.001
98SOE pointer#, 6 dword 
100kWh importkWhdword×0.1
102kWh exportkWhdword×0.1
106Kvarh importkvarhdword×0.1
108Kvarh exportkvarhdword×0.1
112kVAh dword×0.1
718Va THD word×0.0001
719Vb THD word×0.0001
720Vc THD*, 1 word×0.0001
721Ia THD word×0.0001
722Ib THD word×0.0001
723Ic THD*, 1 word×0.0001
1010CT ratio1 word 
1011Wiring mode word 

CET (PMC-53A) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Function codes
03 read holding registers, 05 force single coil, 16 preset multiple registers
Byte order
big endian

Registers in the map: 338 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, word.

MODBUS offsetDescriptionUnitsData typeScale
0UanVsingle 
2UbnVsingle 
4UcnVsingle 
6Uln averageVsingle 
8UabVsingle 
10UbcVsingle 
12UcaVsingle 
14Ull averageVsingle 
16IaAsingle 
18IbAsingle 
20IcAsingle 
22I averageAsingle 
24kWaWsingle 
26kWbWsingle 
28kWcWsingle 
30kW totalWsingle 
32Kvaravarsingle 
34Kvarbvarsingle 
36Kvarcvarsingle 
38Kvar totalvarsingle 
40kVAaVAsingle 
42kVAbVAsingle 
44kVAcVAsingle 
46kVA totalVAsingle 
48PFa single 
50PFb single 
52PFc single 
54PF total single 
56FrequencyHzsingle 
58Uan/Uab (3P3W) angledegsingle 
60Ubn/Ubc (3P3W) angledegsingle 
62Ucn/Uca (3P3W) angledegsingle 
64Ia angledegsingle 
66Ib angledegsingle 
68Ic angledegsingle 
70In (Calculated)Asingle 
72I41Asingle 
74Displacement PFa single 
76Displacement PFb single 
78Displacement PFc single 
80Displacement PF total single 
82AI1 scaled single 
86RTD 11deg Csingle 
88RTD 21deg Csingle 
90AO1 single 
96DI status1, 2 word 
98DO status1, 3 word 
100Setpoint status4 word 
101Wiring diagnostic status5 word 
102SOE log pointer6 dword 

This is not the complete map: 50 of 338 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

CET (PMC-53) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Register type
holding registers (4XXXXX) and write only coil registers (0XXXXX) for DO control
Register addressing
6-digit addressing scheme
Offset calculation
addresses used as printed, no 400001 or 000001 subtraction
Function codes
03 read holding registers, 05 force single coil, 16 preset multiple registers

Registers in the map: 66 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
2VB1Vdword×0.01
4VC1Vdword×0.01
6VLN averageVdword×0.01
8VabVdword×0.01
10VbcVdword×0.01
12VcaVdword×0.01
14VLL averageVdword×0.01
16IaAdword×0.001
18IbAdword×0.001
20IcAdword×0.001
22I averageAdword×0.001
24kWa1kWinteger×0.001
26kWb1kWinteger×0.001
28kWc1kWinteger×0.001
30kWkWinteger×0.001
32Kvara1 integer×0.001
34Kvarb1 integer×0.001
36Kvarc1 integer×0.001
38Kvar integer×0.001
40kVAa1kVAinteger×0.001
42kVAb1kVAinteger×0.001
44kVAc1kVAinteger×0.001
46kVAkVAinteger×0.001
48PFa1 smallint×0.001
49PFb1 smallint×0.001
50PFc1 smallint×0.001
51PF smallint×0.001
52FREQHzword×0.01
53I4Adword×0.001
55Voltage unbalance word×0.001
56Current unbalance word×0.001
57dPFa*, 1 smallint×0.001
58dPFb*, 1 smallint×0.001
59dPFc*, 1 smallint×0.001
60kW demandkWinteger×0.001
62Kvar demand integer×0.001
64kVA demandkVAinteger×0.001
66Ia demandAdword×0.001
68Ib demandAdword×0.001
70Ic demandAdword×0.001
72Va angle word×0.01
73Vb angle word×0.01
74Vc angle word×0.01
75Ia angle word×0.01
76Ib angle word×0.01
77Ic angle word×0.01
78I residual#, 3 word×0.1
79Temperature#, 4 smallint×0.1
95Alarm#, 5 word 
96DO status#, 6 word 

This is not the complete map: 50 of 66 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.