CET (PMC-53A) logging. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
2UbnVsingle
4UcnVsingle
6Uln averageVsingle
8UabVsingle
10UbcVsingle
12UcaVsingle
14Ull averageVsingle
16IaAsingle
18IbAsingle
20IcAsingle
22I averageAsingle
24kWaWsingle
26kWbWsingle
28kWcWsingle
30kW totalWsingle
32Kvaravarsingle
34Kvarbvarsingle
36Kvarcvarsingle
38Kvar totalvarsingle
40kVAaVAsingle
42kVAbVAsingle
44kVAcVAsingle
46kVA totalVAsingle
48PFa single
50PFb single
52PFc single
54PF total single
56FrequencyHzsingle
58Uan/Uab (3P3W) angleDsingle
60Ubn/Ubc (3P3W) angleDsingle
62Ucn/Uca (3P3W) angleDsingle
64Ia angleDsingle
66Ib angleDsingle
68Ic angleDsingle
70In (Calculated)Asingle
72I41Asingle
74Displacement PFa single
76Displacement PFb single
78Displacement PFc single
80Displacement PF total single
82AI1 scaled single
86RTD 11'Csingle
88RTD 21'Csingle
90AO1 single
96DI status1, 2 word
98DO status1, 3 word
100Setpoint status4 word
101Wiring diagnostic status5 word
102SOE log pointer6 dword
104Device operating time70.1Hourdword
There are more MODBUS items for this device. Please, download the program.