MODBUS offset | Description | Units | Data type |
1032 | Vendor name | | string(64) |
1064 | Model name | | string(64) |
1096 | Display name | | string(64) |
1276 | Serial number | | string(64) |
2108 | Software version | | string(48) |
1355 | Nominal voltage | volts | uint16 |
1361 | Phases to display on meter front | | uint16 |
1605 | Field replaceable unit | | uint16 |
1668 | Nominal frequency | hertz | uint16 |
1810 | Output current rating | amperes | uint16 |
3000 | Status | | uint16 |
4002 | Vab | volts | single |
4004 | Vbc | volts | single |
4006 | Vca | volts | single |
4008 | V (L-l) average | volts | single |
4010 | Van | volts | single |
4012 | Vbn | volts | single |
4014 | Vcn | volts | single |
4016 | V (L-n) average | volts | single |
4497 | Phase angle vab | degrees-phase | single |
4499 | Phase angle vbc | degrees-phase | single |
4501 | Phase angle vca | degrees-phase | single |
4525 | V (L-l) average - long-term average | volts | single |
4527 | V (L-n) average - long-term average | volts | single |
5002 | Ia | amperes | single |
5004 | Ib | amperes | single |
5006 | Ic | amperes | single |
5010 | In | amperes | single |
5012 | Iavg | amperes | single |
5014 | Demand ia peak | amperes | single |
5016 | Demand ib peak | amperes | single |
5018 | Demand ic peak | amperes | single |
5250 | Demand ia | amperes | single |
5252 | Demand ib | amperes | single |
5254 | Demand ic | amperes | single |
5258 | Demand in | amperes | single |
5262 | Demand in peak | amperes | single |
5338 | Phase angle ia | degrees-phase | single |
5340 | Phase angle ib | degrees-phase | single |
5342 | Phase angle ic | degrees-phase | single |
5448 | Ia - long-term average | amperes | single |
5450 | Ib - long-term average | amperes | single |
5452 | Ic - long-term average | amperes | single |
5454 | In - long-term average | amperes | single |
6000 | Real power phase A | watts | single |
6002 | Real power phase B | watts | single |
6004 | Real power phase C | watts | single |
6006 | Real power | watts | single |
6064 | Apparent power phase A | volt-amperes | single |
6066 | Apparent power phase B | volt-amperes | single |