Electro Industries Shark 200 data logger. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
8Meter serial number string(16)
16Meter type word
17Firmware version string(4)
19Map version word
20Meter configuration word
21ASIC version word
22Boot firmware version string(4)
24Option slot 1 usage word
25Option slot 2 usage word
26Meter type name string(16)
278Volts A-N dword
279Volts B-N dword
280Volts C-N dword
281Volts A-B dword
282Volts B-C dword
283Volts C-A dword
284Amps A dword
285Amps B dword
286Amps C dword
287Neutral current dword
288Watts, 3-Ph totalwattsdword
289VARs, 3-Ph total dword
290VAs, 3-Ph total dword
291Power factor, 3-Ph total dword
292Frequency dword
293Watts, phase Awattsdword
294Watts, phase B dword
295Watts, phase C dword
296VARs, phase A dword
297VARs, phase B dword
298VARs, phase C dword
299VAs, phase A dword
300VAs, phase B dword
301VAs, phase C dword
302Power factor, phase A dword
303Power factor, phase B dword
304Power factor, phase C dword
999Volts A-N dword
1001Volts B-N dword
1003Volts C-N dword
1005Volts A-B dword
1007Volts B-C dword
1009Volts C-A dword
1011Amps A dword
1013Amps B dword
1015Amps C dword
1017Watts, 3-Ph total dword
1019VARs, 3-Ph total dword
1021VAs, 3-Ph totalVAssingle
1023Power factor, 3-Ph total single
There are more MODBUS items for this device. Please, download the program.