Fronius Inverter (Common) logger. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
40071Total AC currentAword
40072AC current phase AAword
40073AC current phase BAword
40074AC current phase CAword
40075Scale factor AC currentSFsmallint
40076AC voltage phase ABVword
40077AC voltage phase BCVword
40078AC voltage phase CAVword
40079AC voltage phase A neutral wireVword
40080AC voltage phase B neutral wireVword
40081AC voltage phase C neutral wireVword
40082Scale factor AC voltageSFsmallint
40083AC in feed powerWsmallint
40084Scale factor AC in feed powerSFsmallint
40085AC frequencyHzword
40086Scale factor AC frequencySFsmallint
40087Apparent powerVAsmallint
40088Scale factor apparent powerSFsmallint
40089Reactive powerVarsmallint
40090Scale factor reactive powerSFsmallint
40091Power factor%smallint
40092Scale factor power factorSFsmallint
40093Total fed-in energyWhdword
40095Scale factor total energySFsmallint
40096DC currentAword
40097Scale factor DC currentSFsmallint
40098DC voltageVword
40099Scale factor DC voltageSFsmallint
40100DC powerWsmallint
40101Scale factor DC powerSFsmallint
40102Housing temperatureCsmallint
40103Heat sink temperatureCsmallint
40104Transformer temperatureCsmallint
40105Other temperatureCsmallint
40106Scale factor temperatureSFsmallint
40107Operating modeBitmaskword


Fronius Inverter (110,111.112,113) data logging
Fronius Inverter (Common) data logging