Ginlong Solis PV MODBUS registers: read online

Connect Ginlong Solis to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Ginlong Solis data logging and capture.

Do you not know the meter address? Scan the device address online

Ginlong Solis (PV) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Interface
RS-485
Function codes
0x04 read input registers
Setting register function codes
0x03, 0x06, 0x10
On/off register function codes
0x05, write only
Register addressing
addresses used in the actual frame, no offset or conversion required

Registers in the map: 89 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
2999Product model word 
3000DSP software version word 
3001LCD software version word 
3002Protocol software version word 
3021System time yearaword 
3022System time month word 
3023System time dayaword 
3024System time word 
3025System time word 
3026System time second word 
3028Inverter total power generationkWdword 
3030Inverter power generation in the monthkWdword 
3032Inverted last month's power generationkWdword 
3034Inverter power generation todaykWword 
3035Inverter yesterday's power generationkWword 
3036Inverter power generation this yearkWdword 
3038Inverter last year's power generationkWdword 
3048Dc voltage 1Vword×0.1
3049Dc current 1Aword×0.1
3050Dc voltage 2Vword×0.1
3051Dc current 2Aword×0.1
3052Dc voltage 3Vword×0.1
3053Dc current 3Aword×0.1
3054Dc voltage 4Vword×0.1
3055Dc current 4Aword×0.1
3056Total dc output powerWdword 
3070Dc bus voltageVword×0.1
3071Dc bus half voltageVword×0.1
3072Ab line voltage / phase A voltageVword×0.1
3073Bc line voltage / phase B voltageVword×0.1
3074Ca line voltage / C phase voltageVword×0.1
3075Phase A currentAword 
3076Phase B currentAword 
3077Phase C currentAword×0.1
3078Active powerWinteger 
3082Apparent powerVinteger 
3091National standard word 
3092Inverter temperature word×0.1
3093Grid frequencyHzword×0.01
3094Current state of the inverter word 
3103Actual power word 
3104Actual power smallint×0.01
3114Set the flag bit word 
3125Electricity meter total active power generationWhdword 
3127Meter voltage word 
3128Meter current word 
3129Meter active power integer 
3131Energy storage control switch word 
3132Battery voltageVword×0.1
3133Battery currentAsmallint×0.1

This is not the complete map: 50 of 89 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.