Ginlong Solis (PV) logging. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
3021System time yearaword
3022System time month word
3023System time dayaword
3024System time word
3025System time word
3026System time second word
3028Inverter total power generationkWdword
3030Inverter power generation in the monthkWdword
3032Inverted last month's power generationkWdword
3034Inverter power generation todaykWword
3035Inverter yesterday's power generationkWword
3036Inverter power generation this yearkWdword
3038Inverter last year's power generationkWdword
3048Dc voltage 1Vword
3049Dc current 1Aword
3050Dc voltage 2Vword
3051Dc current 2Aword
3052Dc voltage 3Vword
3053Dc current 3Aword
3054Dc voltage 4Vword
3055Dc current 4Aword
3056Total dc output powerWdword
3070Dc bus voltageVword
3071Dc bus half voltageVword
3072Ab line voltage / phase A voltageVword
3073Bc line voltage / phase B voltageVword
3074Ca line voltage / C phase voltageVword
3075Phase A currentAword
3076Phase B currentAword
3077Phase C currentAword
3078Active powerWinteger
3082Apparent powerVinteger
3091National standard word
3092Inverter temperature word
3093Grid frequencyHzword
3094Current state of the inverter word
3103Actual power word
3104Actual power smallint
3114Set the flag bit word
3125Electricity meter total active power generationWhdword
3127Meter voltage word
3128Meter current word
3129Meter active power integer
3131Energy storage control switch word
3132Battery voltageVword
3133Battery currentAsmallint
3134Battery current direction word
3135Llcbus voltageVword
3136Bypassac voltageVword
3137Bypass ac currentAword
3138Battery capacity soc word
3139Battery health soh word
3140Battery voltageVword
3141Battery currentAsmallint
3142Battery charge current limitAword
3143Battery discharge current limitAword
3144Battery failure information 01 word
3145Battery failure information 02 word
3146House load power word
3147Bypass load power word
3148Battery power integer
3168Total power imported from grid dword
3172Total power exported to grid dword
3249Meter placement word
3250Meter ac voltage AVword
3251Meter ac current AAword
3252Meter ac voltage BVword
3253Meter ac current BAword
3254Meter ac voltage cVword
3255Meter ac current CAword
3256Meter active power AkWinteger
3258Meter active power BkWinteger
3260Meter active power CkWinteger
3262Meter total active powerkWinteger
3264Meter reactive power AVarinteger
3266Meter reactive power BVarinteger
3268Meter reactive power CVarinteger
3270Meter total reactive powerVarinteger
3272Meter apparent power AVinteger
3274Meter apparent power BVinteger
3276Meter apparent power CVinteger
3278Meter total apparent powerVinteger
3280Meter power factor smallint
3282Meter total active energy imported from gridkWdword
32852Meter total active energy exported to gridkWdword

Ginlong Solis (PV) data logging