GE EPM 5100, EPM 5300 MODBUS registers: read online

Connect GE to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous GE modbus logging and log.

Do you not know the meter address? Scan the device address online

GE (EPM 5100) - MODBUS Values

Registers in the map: 94 (the first 79 are listed below; the browser reader and the data loggers use the complete map). function 1 (coil status). function 3 (holding registers). function 4 (input registers). byte order big-endian. data types: integer, single, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
0Clear power demandWword 
1Initialize meter word 
2Clear energy (var-hour) word 
3Clear meter errors word 
6Firmware revision singleformula
8COC software revision singleformula
4Serial number integer 
3000Hour smallint 
3001Minute smallint 
3002Seconds smallint 
3005Pulse value interval time for pulse KYZ output 1 single 
3007Pulse value interval time for pulse KYZ output 2 single 
3009Pulse units for KYZ output 1 word 
3010Pulse units for KYZ output 2 word 
3011Programming flags word 
3013Demand interval length (in minutes) smallint 
3014Number of sub-intervals smallint 
3015Display scroll time smallint 
3016Meter configuration word 
3017Potential transformer ratio single 
3019Current transformer ratio single 
3021Energy display format word 
3022Demand display format word 
3023Voltage display format word 
3024Amps display format word 
3025Energy display scale (kWh, MWh) word 
3026Demand display scale (W, kW, MW) word 
3027Voltage display scale (V, kV) word 
3028Amps display scale (A, kA) word 
1000Number of pending event messages smallint 
1002kVA max, total of all phaseskVAsingle 
1004kW max, total of all phaseskWsingle 
1006Kvar lag max, total of all phaseskvarsingle 
1008Kvar lead max, total of all phaseskvarsingle 
1010Current max phase AAsingle 
1012Current max phase BAsingle 
1014Current max phase CAsingle 
1016Kvarh lag, total of all phaseskvarsingle 
1018Kvarh lead, total of all phaseskvarsingle 
1020kWh, total of all phaseskWsingle 
1022kQh, total of all phases single 
1024kVAh, total of all phaseskVAsingle 
1026Average power factor since last reset, all phases single 
1028Power factor, total of all phases, at maximumkVAsingle 
1030Apparent power demand , total of all phaseskVAsingle 
1032Real power demand total of all phaseskWsingle 
1034Reactive power demand (kvar lag), total of all phaseskvarsingle 
1036Reactive power demand (kvar lead), total of all phaseskvarsingle 
1038Current demand, phase AAsingle 
1040Current demand, phase BAsingle 
1042Current demand, phase CAsingle 
1044Power factor, all phases (over last demand interval) single 
1046Real power , phase AkWsingle 
1048Real power , phase BkWsingle 
1050Real power , phase CkWsingle 
1052Reactive power , phase Akvarsingle 
1054Reactive power , phase Bkvarsingle 
1056Reactive power , phase Ckvarsingle 
1058Apparent power , phase AkVAsingle 
1060Apparent power , phase BkVAsingle 
1062Apparent power , phase CkVAsingle 
1064Power factor, phase A single 
1066Power factor, phase B single 
1068Power factor, phase C single 
1070Apparent power , total of all phaseskVAsingle 
1072Real power , total of all phaseskWsingle 
1074Reactive power , total of all phaseskvarsingle 
1076L-N voltage, phase A-NVsingle 
1078L-N voltage, phase B-NVsingle 
1080L-N voltage, phase C-NVsingle 
1082L-L voltage, phase A-BVsingle 
1084L-L voltage, phase B-CVsingle 
1086L-L voltage, phase C-AVsingle 
1088Total power factor of all phases single 
1090Real power , total of all phases at maximum kVAkWsingle 
1092Current, phase AAsingle 
1094Current, phase BAsingle 
1096Current, phase CAsingle 
1098Neutral currentAsingle 

This is not the complete map: 79 of 94 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

GE (EPM 5300) - MODBUS Registers Map

Registers in the map: 132 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: word.

MODBUS offsetDescriptionUnitsData typeScale
278Volt an, Instant word 
317Volt an, Average word 
356Volt an, Max word 
395Volt an, Min word 
279Volt bn, Instant word 
318Volt bn, Average word 
357Volt bn, Max word 
396Volt bn, Min word 
280Volt cn, Instant word 
319Volt cn, Average word 
358Volt cn, Max word 
397Volt cn, Min word 
281Volt ab, Instant word 
320Volt ab, Average word 
359Volt ab, Max word 
398Volt ab, Min word 
282Volt bc, Instant word 
321Volt bc, Average word 
360Volt bc, Max word 
399Volt bc, Min word 
283Volt ca, Instant word 
322Volt ca, Average word 
361Volt ca, Max word 
400Volt ca, Min word 
284Amp A, Instant word 
323Amp A, Average word 
362Amp A, Max word 
401Amp A, Min word 
285Amp B, Instant word 
324Amp B, Average word 
363Amp B, Max word 
402Amp B, Min word 
286Amp C, Instant word 
325Amp C, Average word 
364Amp C, Max word 
403Amp C, Min word 
287Amp N, Instant word 
326Amp N, Average word 
365Amp N, Max word 
404Amp N, Min word 
288Watt, Instant word 
327Watt, Average word 
366Watt, Max word 
405Watt, Min word 
289Var, Instant word 
328Var, Average word 
367Var, Max word 
406Var, Min word 
290Va, Instant word 
329Va, Average word 

This is not the complete map: 50 of 132 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

GE (EPM 6000) - Measurement Data

Connection and addressing notes

Protocol
Modbus RTU
Default password
5555
Password usage
5555 is used when passwords are disabled in the programmable settings
COM1 setup register
30025 (0x7548)
COM1 protocol field
ppp, 1 = Modbus RTU, 2 = Modbus ASCII, 3 = DNP
COM1 baud rate field
bbb, 1 = 9600, 2 = 19200, 4 = 38400, 6 = 57600
COM1 reply delay field
dddd, reply delay x 50 ms
COM2 setup register
30026
COM2 address register
30027, range 1-247
Word order
high order half in the lower addressed register
Undefined registers
read as 0

Registers in the map: 102 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single, smallint, string(16), string(4), word.

MODBUS offsetDescriptionUnitsData typeScale
17Firmware version string(4) 
19Map version word 
21ASIC version word 
0Meter name string(16) 
8Meter serial number string(16) 
16Meter type word 
20Meter configuration word 
39GE part number string(16) 
899Watts, 3-Ph total single 
901VARs, 3-Ph total single 
903VAs, 3-Ph total single 
999Volts A-N single 
1001Volts B-N single 
1003Volts C-N single 
1005Volts A-B single 
1007Volts B-C single 
1009Volts C-A single 
1011Amps A single 
1013Amps B single 
1015Amps C single 
1017Watts, 3-Ph total single 
1019VARs, 3-Ph total single 
1021VAs, 3-Ph total single 
1023Power factor, 3-Phtotal single 
1025Frequency single 
1027Neutral current single 
1099W-hours, received integer 
1101W-hours, delivered integer 
1103W-hours, net integer 
1105W-hours, total integer 
1107VAR-hours, positive integer 
1109VAR-hours, negative integer 
1111VAR-hours, net integer 
1113VAR-hours, total integer 
1115VA-hours, total integer 
1999Amps a, average single 
2001Amps b, average single 
2003Amps c, average single 
2005Positive watts, 3-Ph,Average single 
2007Positive VARs, 3-Ph,Average single 
2009Negative watts, 3-Ph,Average single 
2013VAs, 3-Ph, average single 
2015Positive PF, 3-Ph,Average single 
2017Negative PF, 3-PF,Average single 
2999Volts A-N, minimum single 
3001Volts B-N, minimum single 
3003Volts C-N, minimum single 
3005Volts A-B, minimum single 
3999Volts A-N, %THD word 
4000Volts B-N, %THD word 

This is not the complete map: 50 of 102 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

GE (EPM 7000,EPM 7100) - MODBUS Measurements

Registers in the map: 150 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single, smallint, string(16), string(4), string(8), word.

MODBUS offsetDescriptionUnitsData typeScale
17Firmware version string(4) 
19Map version word 
21ASIC version word 
22Boot Firmware Version string(4) 
0Meter name string(16) 
8Meter SerialNumber string(16) 
16Meter type word 
20MeterConfiguration word 
24Option slot 1Usage word 
25Option slot 2Usage word 
26Meter type name string(8) 
278Integer readings block occupies these registers, see below word 
279Volts B-N word 
280Volts C-N word 
281Volts A-B word 
282Volts B-C word 
283Volts C-A word 
284Amps A word 
285Amps B word 
286Amps C word 
289VARs, 3-Ph total smallint 
290VAs, 3-Ph total word 
291Power factor, 3-Phtotal smallint 
294Watts, phase B smallint 
295Watts, phase C smallint 
296VARs, phase A smallint 
297VARs, phase B smallint 
298VARs, phase C smallint 
299VAs, phase A word 
300VAs, phase B word 
303Power Factor,Phase B smallint 
304Power Factor,Phase C smallint 
999Volts A-N single 
1001Volts B-N single 
1003Volts C-N single 
1005Volts A-B single 
1007Volts B-C single 
1009Volts C-A single 
1011Amps A single 
1013Amps B single 
1015Amps C single 
1017Watts, 3-Ph total single 
1019VARs, 3-Ph total single 
1021VAs, 3-Ph total single 
1023Power factor, 3-Phtotal single 
1025Frequency single 
1027Neutral current single 
1029Watts, phase A single 
1031Watts, phase B single 
1033Watts, phase C single 

This is not the complete map: 50 of 150 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.