Connect Klemsan to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Klemsan logging and read.

Do you not know the meter address? Scan the device address online

Klemsan (KLEA 110P,ECRAS,POWYS) - Measurement Data

Connection and addressing notes

Protocol
Modbus
32-bit float and integer values
occupy two registers
Register step
2
Counter write protection
settings password in the Settings Protection field
Counter change enable
2222 in the Enable Counter Change field

Registers in the map: 267 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single.

MODBUS offsetDescriptionUnitsData typeScale
0Phase 1 voltage (l n) single 
2Phase 1 2 voltage (l l) single 
4Phase 1 current single 
6Phase 1 cos single 
8Phase 1 power factor single 
10Phase 1 active power single 
12Phase 1 reactive power single 
14Phase 1 apparent power single 
16Phase 1 thdv single 
18Phase 1 thdi single 
20Phase 2 voltage (l n) single 
22Phase 2 3 voltage (l l) single 
24Phase 2 current single 
26Phase 2 cos single 
28Phase 2 power factor single 
30Phase 2 active power single 
32Phase 2 reactive power single 
34Phase 2 apparent power single 
36Phase 2 thdv single 
38Phase 2 thdi single 
40Phase 3 voltage (l n) single 
42Phase 3 1 voltage (l l) single 
44Phase 3 current single 
46Phase 3 cos single 
48Phase 3 power factor single 
50Phase 3 active power single 
52Phase 3 reactive power single 
54Phase 3 apparent power single 
56Phase 3 thdv single 
58Phase 3 thdi single 
60Average voltage (l n) single 
62Average voltage (l l) single 
64Total current single 
66System power factor single 
68Total active power single 
70Total reactive power single 
72Total apparent power single 
74System frequency single 
76Neutral current single 
78Phase 1 voltage harmonics 1 single 
80Phase 1 voltage harmonics 3 single 
82Phase 1 voltage harmonics 5 single 
84Phase 1 voltage harmonics 7 single 
86Phase 1 voltage harmonics 9 single 
88Phase 1 voltage harmonics 11 single 
90Phase 1 voltage harmonics 13 single 
92Phase 1 voltage harmonics 15 single 
94Phase 1 voltage harmonics 17 single 
96Phase 1 voltage harmonics 19 single 
98Phase 1 voltage harmonics 21 single 

This is not the complete map: 50 of 267 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Klemsan (KLEA 220P,POWYS 3121) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
32-bit float and integer values
occupy two registers
Register step
2
Counter write protection
settings password in the Settings Protection field
Counter change enable
2222 in the Enable Counter Change field

Registers in the map: 267 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single.

MODBUS offsetDescriptionUnitsData typeScale
0Phase 1 voltage (l n) single 
2Phase 1 2 voltage (l l) single 
4Phase 1 current single 
6Phase 1 cos single 
8Phase 1 power factor single 
10Phase 1 active power single 
12Phase 1 reactive power single 
14Phase 1 apparent power single 
16Phase 1 thdv single 
18Phase 1 thdi single 
20Phase 2 voltage (l n) single 
22Phase 2 3 voltage (l l) single 
24Phase 2 current single 
26Phase 2 cos single 
28Phase 2 power factor single 
30Phase 2 active power single 
32Phase 2 reactive power single 
34Phase 2 apparent power single 
36Phase 2 thdv single 
38Phase 2 thdi single 
40Phase 3 voltage (l n) single 
42Phase 3 1 voltage (l l) single 
44Phase 3 current single 
46Phase 3 cos single 
48Phase 3 power factor single 
50Phase 3 active power single 
52Phase 3 reactive power single 
54Phase 3 apparent power single 
56Phase 3 thdv single 
58Phase 3 thdi single 
60Average voltage (l n) single 
62Average voltage (l l) single 
64Total current single 
66System power factor single 
68Total active power single 
70Total reactive power single 
72Total apparent power single 
74System frequency single 
76Neutral current single 
78Phase 1 voltage harmonics 1 single 
80Phase 1 voltage harmonics 3 single 
82Phase 1 voltage harmonics 5 single 
84Phase 1 voltage harmonics 7 single 
86Phase 1 voltage harmonics 9 single 
88Phase 1 voltage harmonics 11 single 
90Phase 1 voltage harmonics 13 single 
92Phase 1 voltage harmonics 15 single 
94Phase 1 voltage harmonics 17 single 
96Phase 1 voltage harmonics 19 single 
98Phase 1 voltage harmonics 21 single 

This is not the complete map: 50 of 267 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Klemsan (KLEA Energy Analyzer) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Access
read only
Reference
data table 4-4 of the Modbus protocol section
32-bit float values
occupy two registers
Register step
2

Registers in the map: 42. function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Average voltage of three phasesVsingle 
2Total current of three phasesAsingle 
4Total active power of three phasesWsingle 
6Total reactive power of three phasesvarsingle 
8Total apparent power of three phasesVAsingle 
10Average cos of three phases single 
12Average pf of three phases single 
14Voltage V1 2Vsingle 
16Voltage V2 3Vsingle 
18Voltage V3 1Vsingle 
20Average of line to line voltage of three phasesVsingle 
22Neutral currentAsingle 
24Total har. distortion of voltage for three phases%single 
26Total har. distortion of voltage for three phases%single 
28Phase1 voltageVsingle 
30Phase1 currentAsingle 
32Phase1 active powerWsingle 
34Phase1 reactive powervarsingle 
36Phase1 apparent powerVAsingle 
38Phase1 cos single 
40Phase1 power factor single 
42Phase1 frequencyHzsingle 
44Phase1 total har. distortion of voltage%single 
46Phase1 total har. distortion of current%single 
48Phase1 voltage first harmonic%single 
50Phase1 voltage third harmonic%single 
52Phase1 voltage 5th harmonic%single 
54Phase1 voltage 7th harmonic%single 
56Phase1 voltage 9th harmonic%single 
58Phase1 voltage 11th harmonic%single 
60Phase1 voltage 13th harmonic%single 
62Phase1 voltage 15th harmonic%single 
64Phase1 voltage 17th harmonic%single 
66Phase1 voltage 19th harmonic%single 
68Phase1 voltage 21st harmonic%single 
70Phase1 voltage 23rd harmonic%single 
72Phase1 voltage 25th harmonic%single 
74Phase1 voltage 27th harmonic%single 
76Phase1 voltage 29th harmonic%single 
78Phase1 voltage 31st harmonic%single 
80Phase1 voltage 33rd harmonic%single 
82Phase1 voltage 35th harmonic%single 

Klemsan (Rapidus) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Time read function
03h read holding registers
Time write function
13h write multiple registers as printed in the document
Register addressing
word offsets
32-bit float and integer values
occupy two registers

Registers in the map: 314 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, single.

MODBUS offsetDescriptionUnitsData typeScale
0Average voltageVsingle 
2Total currentAsingle 
4Total active powerWsingle 
6Total reactive powervarsingle 
8Total appearent powerVAsingle 
10Average cos single 
12AveragePFsingle 
14L-L voltage 1-2Vsingle 
16L-L voltage 2-3Vsingle 
18L-L voltage 3-1Vsingle 
20Average L-L voltageVsingle 
22Neutral currentAsingle 
24Total THDV%single 
26Total THDI%single 
28VoltageVsingle 
30CurrentAsingle 
32Active powerWsingle 
34Reactive powervarsingle 
36Appearent powerVAsingle 
38Cos single 
40Pf single 
42FrequencyHzsingle 
44Total V harmonic distortion%single 
46Total I harmonic distortion%single 
48V harmonics 1%single 
50V harmonics 3%single 
52V harmonics 5%single 
54V harmonics 7%single 
56V harmonics 9%single 
58V harmonics 11%single 
60V harmonics 13%single 
62V harmonics 15%single 
64V harmonics 17%single 
66V harmonics 19%single 
68V harmonics 21%single 
70V harmonics 23%single 
72V harmonics 25%single 
74V harmonics 27%single 
76V harmonics 29%single 
78V harmonics 31%single 
80V harmonics 33%single 
82V harmonics 35%single 
84V harmonics 37%single 
86V harmonics 39%single 
88V harmonics 41%single 
90V harmonics 43%single 
92V harmonics 45%single 
94V harmonics 47%single 
96V harmonics 49%single 
98V harmonics 51%single 

This is not the complete map: 50 of 314 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps